Proceedings of Engineering and Technology – PET

Volume 17, Issue 2, 2017, Pages 97-101

Pipelines Corrosion Due to the Electromagnetic Pollutioncaused by the High Voltage Power Lines

M. Ouadah, O. Touhami, R. Ibtiouen, A. Bouzida, S. Bouyegh, D.Allou, A.Haddad

Abstract: This paper studies the effect of theelectromagnetic pollution caused by the high voltage powerlines on the corrosion of the buried pipeline. In this objective,the finite element method (FEM) was used to calculate themagnetic field distribution and the induced current densitiesin the buried pipeline caused by both horizontal and verticalconfiguration of the HVPL during steady state conditions. Inorder to diagnose the effect of the electromagnetic pollutionon the corrosion of the pipeline, the electrochemicalimpedance spectroscopy (EIS)measurements were used tocharacterize the corrosion polarization properties of X70 steelin simulated soil at various AC current densities. The resultsshow that, the electromagnetic pollution caused by the highvoltage power lines affect the electrochemical characteristicsof the X70 steel pipeline and accelerate the corrosion of thepipeline.

Keywords : Electromagnetic pollution, high voltage power line, induced current density, X70 steel pipeline, corrosion, Finite Element Method, Electrochemical impedance spectroscopy

Centre de Recherche en Technologies Industrielles - CRTI - www.crti.dz

Powered by TCPDF (www.tcpdf.org)

Références

Documents relatifs

To achieve this objective, firstly the electromagnetic interference between the double circuit HVPL and the X70 steel pipeline (the distribution of the magnetic field and the induced

The induced voltage onto the pipeline was calculated for different separation distance between conductors, the existence of the earth wire, separation distance between transmission

In order to diagnose the effect of the electromagnetic pollution on the corrosion of the pipeline, the electrochemical impedance spectroscopy (EIS) measurements were used

The induced voltage onto the pipeline was calculated for the horizontal and the vertical configuration of the power line, the existence of the earth wire, various separation

The induced voltage onto the pipeline was calculated for the horizontal and the vertical configuration of the power line, the existence of the earth wire, various separation

In this research, the induced voltage in the oil buried pipelines due to the magnetic fields produced by nearby 400kV transmission lines have been computed on normal and

Keywords : Induced Voltages, Electric Power Transmission Lines, pipeline, AC Corrosion, cathodic protection, soil resistivity, AC interference. Centre de Recherche en

The paper studies the electromagnetic interference problem between an existing high voltage power line and a newly designed underground pipeline cathodically