International Journal of Electrical Power & Energy Systems

Volume 91, Issue 1, 2017, Pages 34-41

Corrosive effects of the electromagnetic induction caused by the high voltage power lines on buried

X70 steel pipelines

M. Ouadah, O. Touhami, R. Ibtiouen, M.F. Benlamnouar, M. Zergoug

Abstract: This paper diagnoses the corrosive effects of the electromagnetic induction caused by double circuit high voltage power lines (HVPL) on the buried X70 steel pipelines. To achieve this objective, firstly the electromagnetic interference between the double circuit HVPL and the X70 steel pipeline (the distribution of the magnetic field and the induced AC current densities in the buried X70 steel pipeline) and the factors affecting this interference such as the vertical distance between the double circuit HVPL and the X70 steel pipeline, and the conductor phase sequence orientation were studied. Then, electrochemical measurements were used to characterize the corrosion polarization properties of X70 steel in simulated soil at various AC current densities. The results show that with an increase in the AC current density, the corrosion rate of the X70 steel increased, indicating that the induced AC current density has accelerated the corrosion degree of X70 steel, by comparison with that in the absence of the AC current density.

We can conclude from these results that the electromagnetic induction caused by the double circuit high voltage power lines affects the electrochemical characteristic of the X70 steel pipeline and accelerates the corrosion of the pipeline.

Keywords : Electromagnetic induction, high voltage power line, induced AC current density, X70 steel pipeline, corrosion, Finite element method.

Centre de Recherche en Technologies Industrielles - CRTI - www.crti.dz

Powered by TCPDF (www.tcpdf.org)

Références

Documents relatifs

The induced voltage onto the pipeline was calculated for different separation distance between conductors, the existence of the earth wire, separation distance between transmission

In order to diagnose the effect of the electromagnetic pollution on the corrosion of the pipeline, the electrochemical impedance spectroscopy (EIS) measurements were used

Abstract: This paper diagnosis the effect of the AC current densities induced by the electromagnetic interference between high voltage power line and buried power line on the

Abstract—This paper diagnoses the effect of the AC current densities induced by the electromagnetic interferences between high voltage power line and buried power line on

The induced voltage onto the pipeline was calculated for the horizontal and the vertical configuration of the power line, the existence of the earth wire, various separation

This research evaluates and analyzes the electromagnetic interference effects on oil and gas buried pipelines created by the nearby high voltage transmission lines. The aim is to

First we analyze the magnetic field for horizontal and vertical configurations, then we study the effect of the soil conductivity in the level of the induced voltage in

Considering that the electromagnetic field is a special case of the gravitational field [10], the structure of which has the character of a standing gravitational wave for