Journal of Electrical Engineering

Volume 16, Issue 2, 2016, Pages 76-83

Diagnosis of AC corrosion on the buried pipeline due to the high voltage power line

M.Ouadah, O.TOUHAMI, R.IBTIOUEN

Abstract: This paper studies the electromagnetic effect of the high voltage power line on the X70 Steel pipeline and the factors affecting this interference. The induced voltage onto the pipeline was calculated for different separation distance between conductors, the existence of the earth wire, separation distance between transmission line and pipeline and the parallelism length.

The induced AC current density was calculated function to the induced voltage, the soil resistivity, and the holiday diameter. The electrochemical characters of the X70 steel with and without influence of the alternating currents were studied in simulated soil solution. The results indicate that the AC density accelerate the corrosion degree of X70 steel in simulated soil solution comparing with that in the absence of the AC density.

Keywords : Power lines, interference, induced voltage, induced current density, AC corrosion.

Centre de Recherche en Technologies Industrielles - CRTI - www.crti.dz

Powered by TCPDF (www.tcpdf.org)

Références

Documents relatifs

Abstract: This paper diagnosis the effect of the AC current densities induced by the electromagnetic interference between high voltage power line and buried power line on the

Abstract—This paper diagnoses the effect of the AC current densities induced by the electromagnetic interferences between high voltage power line and buried power line on

The induced voltage onto the pipeline was calculated for the horizontal and the vertical configuration of the power line, the existence of the earth wire, various separation

The induced voltage onto the pipeline was calculated for the horizontal and the vertical configuration of the power line, the existence of the earth wire, various separation

Keywords : Induced Voltages, Electric Power Transmission Lines, pipeline, AC Corrosion, cathodic protection, soil resistivity, AC interference. Centre de Recherche en

The paper studies the electromagnetic interference problem between an existing high voltage power line and a newly designed underground pipeline cathodically

Abstract: Analysis of electromagnetic interference between high voltage overhead power transmission lines and nearby gas/oil pipeline has been a topic of growing interest for

This research evaluates and analyzes the electromagnetic interference effects on oil and gas buried pipelines created by the nearby high voltage transmission lines. The aim is to