• Aucun résultat trouvé

Burnt offerings : Kemano, a deserted town in remote British Columbia, provided the ideal ground for testing a sprinkler's ability to put out house fires

N/A
N/A
Protected

Academic year: 2021

Partager "Burnt offerings : Kemano, a deserted town in remote British Columbia, provided the ideal ground for testing a sprinkler's ability to put out house fires"

Copied!
4
0
0

Texte intégral

(1)

Publisher’s version / Version de l'éditeur:

Canadian Consulting Engineer, 43, May 3, p. 26, 2002-05-01

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la

première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

NRC Publications Archive

Archives des publications du CNRC

This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

Burnt offerings : Kemano, a deserted town in remote British Columbia, provided the ideal ground for testing a sprinkler's ability to put out house fires

Su, J. Z.; Crampton, G. P.; Carpenter, D. W.; McCartney, C. J.; Leroux, P.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

NRC Publications Record / Notice d'Archives des publications de CNRC:

https://nrc-publications.canada.ca/eng/view/object/?id=d759a638-d7c6-4155-97d7-3925b00b01bf https://publications-cnrc.canada.ca/fra/voir/objet/?id=d759a638-d7c6-4155-97d7-3925b00b01bf

(2)

Burnt offerings : Kemano, a deserted town in remote British Columbia, provided the ideal ground for testing a sprinkler's ability to put out house fires

Su, J.Z.; Crampton, G.P.; Carpenter, D.W.; McCartney, C.; Leroux, P.

A version of this document is published in / Une version de ce document se trouve dans : Canadian Consulting Engineer, v. 43, no. 3, May 2002, p. 26

www.nrc.ca/irc/ircpubs

(3)

Burnt Offerings : Kemano, a deserted town in remote British Columbia, provided the ideal ground for testing a sprinkler's ability to put out house fires.

By Joseph Z.Su, George P. Crampton, Don W. Carpenter, Cameron McCartney Kemano, British Columbia, was a company town built 50 years ago by Alcan Smelters and Chemicals to support its hydroelectric station. When the station became essentially automated, making the town obsolete, an idea was born. The deserted town was donated to B.C.’s Office of the Fire Commissioner for training and research. This has been known as the Kemano Public Safety Initiative.

As part of this unique opportunity, the National Research Council of Canada was invited to conduct a series of full-scale fire experiments at the town. One series of experiments was designed to evaluate the performance of a cross-linked-polyethylene pipe sprinkler system in an abandoned house that contained furniture to simulate a normal occupancy. The house was a wood-framed bi-level structure with approximately 1,000 square feet per floor (2,000 square feet total).

The sprinkler system was tested for fires originating in a basement recreation room, in a ground floor bedroom, and in the living room. A residential sprinkler system with quick response heads (rated at 68.3°C (155°F)) was designed and installed by a residential sprinkler company. The designed flow rate was 50 L/min for the hydraulically remotest sprinkler head and 55 L/min for the hydraulically nearest one. The system was under a static pressure of 552 kPa (80 psi); during sprinkler activation, the main manifold was under a flowing pressure of 241 kPa (35 psi). The system was designed to prevent flashover in the room where fire originated and to allow response time for the fire department.

In all experiments, a single sprinkler head controlled and contained the fire within the original room within one minute of activation. The water spray cooled down the fire compartment. Since the fire was successfully controlled in each experiment, the fire damage was limited to the furniture that was near the ignition source. There was soot deposition as expected, but no structural damage. For experiments with the fire room door closed, temperature and visibility along the egress route were basically not affected by the fire inside that room.

In the recreation room, the plastic pipes and fittings were installed, without protection, on open wood joists. The equipment was exposed to temperatures as high as 140°C in two experiments. After exposure to temperatures above their rated temperature of 93°C (200°F) at 552 kPa (80 psi) for 140 seconds, the pipes and fittings were not visibly damaged, and the sprinkler system was then successfully actuated and controlled the fire.

(4)

The effectiveness of heat and smoke detectors was also investigated in the sprinkler experiments. As expected, the heat detectors, which were rated at 57°C (135°F) and a temperature rise of 8.4°C/min (15°F/min), were always actuated earlier than the sprinkler. The rate of temperature rise triggered the heat detectors. Smoke detectors, installed on the egress route, were actuated before the sprinkler when the fire room was open to the egress route but after the sprinkler when the fire room door was closed. Technical data obtained from the Kemano experiments can be used as a basis for further studies on sprinkler systems. Questions can be directed to Dr. Joseph Su at (613) 993-9616, fax (613) 954-0483, or e-mail joseph.su@nrc.ca.

Dr. Joseph Su is a researcher in the Fire Risk Management Program of the National Research Council’s Institute for Research in Construction in Ottawa. George P. Crampton, Don W. Carpenter, Cameron McCartney, and Patrice Leroux are technical officers in the same program.

Références

Documents relatifs

cependant utiliser la terminologie existante (voir par exemple [ScS00]) de suite d’interpolation faible dans X, ce qu’on notera Λ ∈ Int w (X). On vient d’expliquer que la

Pourtant, les Français ont repris à leur compte le héros Godefroi, non seulement à cause de son lieu de naissance (Boulogne-sur-mer), mais aussi parce qu'il était l'un des

Selon l ’Agence nationale de sécurité des médicaments et produits de santé (ANSM), ex-Agence française de sécurité sanitaire des produits de santé (AFSSAPS), « dans le domaine

There are a large number of observational constraints which allow us to strongly constrain the previous parameters: the ratio of radii between the blast wave and contact

• The Abbotsford - Sumas International Aquifer, q , British Columbia, Canada..

The Green Party of B.C. believes that neither a completely socialist nor a completely free enterprise system can solve the problems of resource depletion and recession cycles which

This study developed an integrated 2D and 3D Web GIS platform to evaluate the environmental livelihood of the West Moberly First Nations, the Saulteau First Nations, and

Although Introductory Grade 11 is usually offered in Grade 11, to alleviate scheduling pressure