Publisher’s version / Version de l'éditeur:
Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la
première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.
Questions? Contact the NRC Publications Archive team at
PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.
https://publications-cnrc.canada.ca/fra/droits
L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.
Technical Note (National Research Council of Canada. Division of Building Research), 1960-01-01
READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.
https://nrc-publications.canada.ca/eng/copyright
NRC Publications Archive Record / Notice des Archives des publications du CNRC : https://nrc-publications.canada.ca/eng/view/object/?id=a168d451-ec8c-46b4-a6a0-04e2f5ab1018 https://publications-cnrc.canada.ca/fra/voir/objet/?id=a168d451-ec8c-46b4-a6a0-04e2f5ab1018
NRC Publications Archive
Archives des publications du CNRC
This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.
For the publisher’s version, please access the DOI link below./ Pour consulter la version de l’éditeur, utilisez le lien DOI ci-dessous.
https://doi.org/10.4224/40001177
Access and use of this website and the material on it are subject to the Terms and Conditions set forth at Design notes on panel conditioning room: Building M-59
DIVISION OF BUILDING RESEARCH
NATIONAL RESEARCH COUNCIL OF CANADA
'fE
C
1HIIi ][ CAlL
NOTlE
セ
セi
NOT FOR PUBLICATIONPREPARED BY G.T. Tamura CHECKED BY A.G. Wilson
FOR INTERNAL USE
APPROVED ByN .B.Hutcheon
セ
7
January1960
PREPARED FOR Divisional Use
SUBJECT DESIGN NOTES ON PANEL CONDITIONING ROOM - BUILDING M
52
This Note provides the basis for the detailed design of a conditioning system required for the Panel Conditioning Room of the Fire BUilding, M59,
of the Division. The conditioning room located in the west end of the furnace room (room 124) of the Fire Research Building M59
is intended for drying concrete wall and floor specimens. The conditioning room is to consist of two compartments adjacent and セー・ョ to each other with the larger compartment being able to take four concrete walls positionedvertically side by side, and the smaller compartment located above the mezzanine floor being able to take four concrete floors laid horizontally, one above the other. Concrete floor and wall speci-mens are to be dried by circulating air inside the compartments, and heating of recirculated air and laboratory air to obtain the required relative humidity of the air inside the compartments. The layout of the air conditioning systems proposed is shown in Fig. 1.
DESIGN DATA
The capacity of the air conditioning system for removal of moisture was based on the most severe ウオイイセ・イ condition of 80°F
dew point temperature. By heating the air in the compartments to 110°F, the relative humidity of the air is
40%
at this dew pointtemperature. Allowing the relative humidity to rise to
50%
gives.006 lb. moisture removal per lb. of dry air. Introducing 500 cfro laboratory air into the compartments gives 300 lb. moisture
removal per day which is 1% of the weight of one large specimen. For other conditions the relative humidity and temperature of the conditioning room air can be controlled to give the required rate
,
,
2
-of moisture- removal. Steam heater coil is sized to supply 64,000
Btu/hr. to maintain conditioning room temperature of 110oF. based on the heat required to raise 500 afm of laboratory air at 70°F and
500 cfro of recirculated 。Qセ at 110°F to 170°F. This heating rate セセ also that required to provide the estimated heat requirements
'or the enclosure for 70°F outside.
AIR CIRCULATION FOR CONCRETE WALLS
Air recirculation in the larger compartment is obtained with the use of three propeller fans with a capacity of 1000 crm each. The fans are placed on the floor on the west end of the
compartment to blow air diagonally upward between the masonry walls. Electrical outlets should be provided for five fans. DBR will
provide fans.
AIR CIRCULATION FOR CONCRETE FLOORS
セ・ air in the compartment holding the floor specimen is recirculated by a centrifugal fan located outside the compartment and below the mezzanine floor. The air drawn from the larger compartment is directed upward -through two vertical ducts with a total of ten rectangular supply openings located and sized such that air is discharged at 4000 fpm between the concrete floors. The layout for this system 1s shown in Fig. 2.
RELATIVE HUMIDITY SYSTEM
The relative humidity system as shown in Fig. 3 consists of centrifugal fan, ductwork, steam heater COil, dampers and
controls to the heater coil and the dampers. The required temperature in the conditioning room is maintained by means of a modulating steam valve on the.heater coil actuated by the temperature sensing element, located at the compartment air inlet side of the R.H. system. The required relative humidity of the conditioning room is obtained by positioning interlinked dampers on the two inlet ducts by a modulated damper motor actuated by a relative humidity sensing element, also located a t the compartment air inlet side of the RoH. system.
When the compartments are at less than the required relative humidity, the damper across the laboratory air inlet duct is to be closed and the damper across the recirculation air inlet duct opened. When the relative humidity in the compartments exceeds the u per limit, the damper in the laboratory air inlet duct is to be opened and the damper in the recirculation air inlet duct partially closed so that
500 cfm laboratory air and 500 cfm recirculated air are heated and ejected into the compartments. The additional 500 cfro of laboratory air blown into the compartments displaces air in the compartment which is expelled through cracks in the enclosure.
A hand damper is located on the inlet recirculati.on D.i:e
" . _...'W'rl/4WA DIViSION OF BUILDING RESEARCH. NATIONAL RESEARCH COUNCIL CANADA -.
-
I • \l. U "- 0 '. 0 0 • " s o セ...-1.
1-_.,-
-{イNセ
/-'--'
__4 --1'- ,; -, 'セイ
- I Iul
\ , \ !I
I-<:-1
I-M :'1 セi '-j ,J-
.
,U-.
.}iセ
I
セ
I
/ I I,--.
.
I. 'J J T 0 0 TITLE DRAWING No.BQ205\-t
..
I
, I Iセ
j
Hセ
II
o·g' II 1.Pl't, I '1.1" 1.1 Mセ[ᄋMMMMMQ ,....---I I I =0 _I «) .J =-
/--
LJ
)( ,,-t Bッアᄋセl IIッセᄋセ 1\ GiセGKセG"'s' r -
III
" N 300 DRAWl G No. 5 -<..'" •CTiAWA DIVISION OF BUILDING RESEARCH. NATIONAL RESEARCH COUNCIL CANADA J c:l セ :r l-ll) a () () -.:t....v...Ll \.9 • • セ 0 0 O\r
- r-Ii J • I ... •