Publisher’s version / Version de l'éditeur:
ASHRAE Transactions, 97, 2, pp. 347-353, 1991
READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.
https://nrc-publications.canada.ca/eng/copyright
Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la
première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.
Questions? Contact the NRC Publications Archive team at
PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.
NRC Publications Archive
Archives des publications du CNRC
This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.
Access and use of this website and the material on it are subject to the Terms and Conditions set forth at
Overall and component airtightness values of a five-story apartment
building
Shaw, C. Y.; Magee, R. J.; Rousseau, J.
https://publications-cnrc.canada.ca/fra/droits
L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.
NRC Publications Record / Notice d'Archives des publications de CNRC:
https://nrc-publications.canada.ca/eng/view/object/?id=191d2070-2a50-4031-9771-b8c8e078fc41 https://publications-cnrc.canada.ca/fra/voir/objet/?id=191d2070-2a50-4031-9771-b8c8e078fc41
Overall and component
airtightness values of a five-story
apartment building
Shaw, C.Y.; Magee, R.J.; Rousseau, J.
NRCC-34049
A version of this document is published in :ASHRAE Transactions, 97(2), pp. 347-353, 91
The material in this document is covered by the provisions of the Copyright Act, by Canadian laws, policies, regulations and international agreements. Such provisions serve to identify the information source and, in specific instances, to prohibit reproduction of materials without written permission. For more information visit http://laws.justice.gc.ca/en/showtdm/cs/C-42
Les renseignements dans ce document sont protégés par la Loi sur le droit d’auteur, par les lois, les politiques et les règlements du Canada et des accords internationaux. Ces dispositions permettent d’identifier la source de l’information et, dans certains cas, d’interdire la copie de documents sans permission écrite. Pour obtenir de plus amples renseignements : http://lois.justice.gc.ca/fr/showtdm/cs/C-42
OVERALL AND COMPONENT AIRTIGHTNESS
VALUES OF A FIVE-STORY APARTMENT
BUILDING
C.Y. Shaw, Ph.D., P.E.Member ASHRAE
ABSTRACT
R.J. Magee
Fan pressurization and balanced fan pressurization tests were conducted on afive-story apartment building to deter-mine its air leakage characteristics. The overall airtightness of the building envelope and the airtightness values of the exterior walls of three individual stories were obtained, as well as the airtightness values of interior partitions, stair-wells, and floor/ceiling separations. The methods used to measure the airtightness values are described, and the test results are reported.
INTRODUCTION
The envelopes and interior partitwns of apartment buildings are not airtight. The cracks and openings in them permit some air leakage into and out of a building. They also allow the indoor air to flow from one area to another inside the building. These airflows contribute to the build-ing's heating and cooling load and also to the transport of pollutants inside. With a renewed demand for energy conservation and a growing concern for indoor air quality, there is an increased need to understand and control such airflows.
Several airflow models have been developed for predic-ting such air movement (Kurabuchl et al. 1990; Said 1990). One of the major problems in applying these models is the lack of air leakage characteristics for various types of buildings, particularly for the interior partitions of high-rise apartment buildings. This paper describes a project carried out to measure the airtightness values (air leakage rates measured by the fan depressurization method) of the exterior walls and interior partitions of a five-story
apart-ment building. The methods used and the results obtained
are presented.
TEST BUILDING
The five-story masonry building was constructed in 1981 (Figure 1 and Table 1). The building has a basement, a ground floor, and four typical stories. The basement houses a party room, a laundry room, storage areas, a transformer vault, and a mechanical room. Approximately half the ground floor is occupied by commercial tenants and is separated from the rest of the building. The garbage room is also located on the ground floor. Each typical story
(second through fifth floors) has 12 apartment units-six on
each side of a corridor (Figure 2) . The elevator shaft, enclosed garbage chute, and electrical/service room are located at the center of the corridor. There are two
stair-J. Rousseau ·
Figure 1 Test building showing test setup for measuring airtightness of the building envelope
wells, one on each end of the building. The south stairwell has a hatchway to the outside.
The building has a central heating and ventil ating system that supplies air to the corridor of each story through two supply air registers. There are no return air grilles in the corridor. Return air is drawn into the heating and ventilating system through a dampered opening in the outdoor air supply duct inside the basement mechanical room.
TABLE 1
Description of Test Building
Year Constructed: 1981
Year Tested: 1989 Hei ght (stories): 5
Wall Construction
Exterior Wall: 80 mm (3 in) Face brick 25 mm (1 in) Air space 200 mm (8 in) Co ncrete block 38 mm (1.5 in) Rigid glass fiber
insulation
Metal Studs
38 mm (1.5 in) Semi- rigid glass ti ber
insulat i on Vapor Barrier
1 2 mm (0.5 in) Gypsum board Internal ャセ。QQZ@ 13 mm (0. 5 in) Gypsum board 92 mm (3.5 inl Metal studs 38 mm (1.5 in) Insulation blanket 13 mm (0.5 in) Gypsum board
C.Y. Shaw is a Senior Researcher and Robert
.T.
Magee is a Technical Officer at the Institute for Research in Construction, NationalResearch Council, Ottawa, Ontario, Canada. Jacques Rousseau is a Project Manager at Canada Mortgage and Housing Corp., Ottawa.
347
N
-Figure 2 Typical floor plan
. e。」セ@ ゥZョ、ゥカゥセオ。ャ@ apartment unit is heated by a fan coil umt eqwp_Ped wtth a hot water heating coil. There is no outdoor a1r supply to the fan coil unit or to individual
ャャーセイエュ・ョエ@ units. Ventilation air is drawu into the apartment
urut from the corridor by discharging the indoor air to the
outdoors through the kitchen and balhr oom exhaust fans when they are operated by the occupants.
TEST METHODS
The test methods were modified from those developed previously (Shaw et al. 1973; Tamura and Shaw 1976; Shaw 1980; Shaw et al. 1990). A brief description of these methods is given below.
Airtightness Value of the Whole Building
The overall airtightness value was measured using the fan depressurization method (Shaw 1980; Shaw et al.
1990). As shown in Figure 1, a large vane-axial fan was
used
I?
depressurize the test building. The fan airflow couldbe adjusted between 0 and 23 m3/s (approx.imately 0 to
50,000 cfm). The. fan inlet キセ@ 」ッョョ・」エセ@ by 12m (39.3 ft)
of PNセ@ m (3 ft). diameter ductmg to a plywood panel
tem-porarily replacwg a rear entrance door that connected to both stairwells. All interior doors to the stairwells were kept open to provide a free-flow path for the air drawn by the fan from the floor spaces through the stajrwells to the
ッオエ、セッイウN@ Because the building was fully occupied, for
secunty reasons the entrance door to each apartment unit
was kept closed during the test. A previous study c0nducted on a similar building had indicated that opening or closing the entrance door to each apartment unit had no effect on the .measured overall airtightness values (Shaw 1980). Durwg the test, the building's ventilation system was shut down (with fresh air intake dampers closed) and the dampers in all window air conditioners were closed. Also, the garbage room exhaust fan was shut off and the vent sealed, as was the vent to the transformer vault.
. The セゥ 、 ャッキ@ イ。セ・@ was measured upstream of the fan
キセ・@ usmg a patr of total-pressure-averaging tubes.
Airflow rate measurements are accurate to within 5% of the
ュ・。 ウ オイセ@ カ。ャセ ・ウ L@ as determined. during calibration by
c?mpan son With measurements usmg the pitot tube
traver-smg method. The pressure di fferences across the building envelope at both. the ground and roof levels were measured
using an ・ ャ・」エセセ」@ manometer with a strip chart recorder
(accurate to Within 5% of the measu red values as specified
by the manufacturer). The average of the pressure differen-ces measured at the ground and roof levels was used to
'
.
348
represent the mean pressure difference across the building
envelope. pセッイ@ to and. immediately after the test, the fan
was sealed w1th a plastic sheet and the pressure differences across the envelope at the ground and roof levels were
measured. セィ・ウ・@ "base readings" were then avera-ged and
subtracted from the test results to minimize-weath_er effects (wind and stack action).
As an 。ャセ・ャャ_。エゥセ・@ to 1!5ing a vane-ax.ial fan, the supply fan of the bmldmg s heatwg and ventilating system can be
used. for エィセ@ test in some cases (Shaw et al. 1973). To
obtam ュ・。ョキァヲオセ@ results, the capacity of the supply fan
should be suffic1ent to produce a minimum pressure
、ゥヲヲ・イ・ョセ・@ across the buildjng envelope of about 30 Pa. For conductwg such a test, the heating and ventilating system is operated under 100% outdoor air by closing both the main
return Hセ、@ exhaust, if any) dampers. Different airflow
rates, キィゥセィ@ are needed to produce four or five different
ーイ・ウ セ オイ・@ 、ゥヲヲ・イセョセ@ across the building envelope, can be
obt:amed by adJUStmg the. outdoor or supply air damper.
This セ・エ_Mッ、@ was also applied to measure the aixtightoess of
the butldmg envelope. Very poor results were obtained due to insufficient capacity of the supply fan of the building's heating and ventilating system.
Airtightness Values of Exterior Walls and Floor/Ceiling Separations
of Individual Stories
The balanced .
fll:'l
depressurization technique was usedto measure the a1rt1ghtness values of exterior walls and floor/ceiling separations of individual stories (Shaw 1980). As shown in Figure 3a, a variable-speed fan was used as the primary depressurization apparatus for a selected test
ウエセイケN@ The fan airflow could be adjusted between 0 and 1.3
m Is (0 and 2, 7 50 cfm). The fan inlet was connected by 7. 3
m (24 ft) of 0.46 m (1.5 ft) diameter ducting to a plywood
panel temporarily replacing a stairwell door on the ·test story. The outside stairwell door at the ground floor was kept open du?ng the test to allow the air from the test story to exhaust dtrectly to the outdoors. The airflow rate was
measured upstream of the fan intake with a pair of
total-pressure-averaging tubes.
Figure 3
ja) INDIVIDUAL STOREYS
1. fnセ@
;:
セエG」Zセキョ@ f'1.0WCONTROl4. Pltt..sW!lE LU:J.SIJO!UG DEVICE
5, PP.ES5unE OAL\JlCING FAN
('o) HfO!V.OUAL APAATMEIH uセOQts@
Test setup f or measuring airtightness values of building components
The pressure differences across the exterior wall of the test story and across the two floor/ceiling separations were
each measured using an electronic manometer with セ@ strip
chart recorder. Two balancing fans with manual dampers were similarly installed in the stairwell doors to the stories above and below. These fans were used to control the pressures in these two stories and thereby control the flow of leakage air through the floor/ceiling separations into the test story.
For measuring the airtightness value of the exterior wall, the pressures in the test story and the stories above ar\d below were balanced using the two balancing fans (Figure 3a) to minimize the flow of leakage air through th.e tloorlceiling separations into the test story. For measuring the airtightness values of floor/ceiling separations, two additional tests were conducted immediately after the above test. During each test, only one balancing fan was used ; therefore, the pressure difference across only one floor/ceil-ing separation was reduced to zero. The pressure difference across the other floor/ceiling separation was measured
simultaneously with the p.ressure difference across the
exterio•· wall. The measured leakage rates during this test,
therefore, included the exterior wall leakage of the test floor and that of the' unbalanced floor/ceiling separation. By subtracting from the result the exterior wall air leakage rate at the same pressure difference across the exterior wall (this component could be calculated from U1e results of the first test), the airtightness value of the floor and ceiling tion at the measured pressure difference across the
separa-tion could be determined.
Airtightness Values of Interior Partitions and Floor/Ceiling Separations
of Individual Apartment Units
The balanced fan depressurization method was also
used to obt11in the airtightness values of interior partitions
and floor/ceiling separations of individual apartment units
(Shaw 1980). As shown
in
fゥァオセZ・@ 3b, a fan was used todepressurize a selected test apartment unit. The fan airflow
could be adjusted between 0 and 320 Lis (approximately 0
and 680 cfm). The fan inlet was connected by 3 m (10ft)
of 0.2 m (0.65 ft) diameter ducting to a plywood panel
temporarily replacing the entrance door of the test unit. All
interior doors in the apartment
unit
were kept open and allexhaust fans (e.g. , kitchen and bathroom exhaust fans) were turned off and their grilles sealed. The airflow rate was adjusted with a manual damper and measured upstream of
the fan intake with a pair of total-pressure-averaging tubes.
The pressure differences across the exterior wall and interior partitions were measured using an electronic
manometer with a strip chart .recorder.
In
addition, four balancing fans with manual damperswere installed, one for each adjacent unit (Figure 3b). By adjusting the airflow rate through each balancing fan until the pressure difference across the corresponding partition
wall or floor/ceiling separation was reduced to
zero,
the airleakage through that component could be reduced to zero.
Ideally,
a fifth
balancing fan could be used to balance thepressures between the corridor and the test apartment unit, thereby eliminating the leakage o'f air through the corrjdor
wall . In order to avoid occupant complaints, this application
of a fifth balancing fan was not carried out. As a result, the exterior wall airtightness values of individual apartment units were not measured .
Six
tests
were conducted, one after the other. The firsttest was a simple fan depressurization test in which all four balancing fans were off and sealed. The results were,
349
therefore, the overall airtightness values of the test apart-ment unit (excluding its entrance door, which was replaced by a sheet of plywood for installing the pressurization fan) .
In the second test, all four balancing fans were used to
reduce the pressure differences between the test unit and its
four adjacent units to zero. The results were the combined
airtightness values of the exterior wall and the corridor partition (excluding the entrance door) at measured pressure differences across the exterior wall.
Four more tests were conducted immediately after the
second test. The test procedures were similar to those for
individual stories; i.e., in each test, only one balancing fan
was shut down and sealed and the pressure differences
across the Wlbalanced component ao,d across the exterior
wall were measured simultaneously. The results
of
thesefour tests and those obtained from the second test were used to determine the airtightness values for the unbalanced building component using the same method as described for the floor/ceiling separations of individual stories.
Airtightness of Stairshafts
The method for stairwell leakage determination has been reported by Tamura and Shaw (1976). Similar to the test for the whole building (Figure 1), the fan with a
maximum capacity of 1.3 m3/s (2,750 cfrn) was ducted to
a
plywood panel temporarily replacing an outside stairwelldoor. All other doors to the stairwell were kept closed (but · not sealed).
The airflow rate was measured upstream of the fan
intake using a pair of エッエ。ャセーイ・ウウオイ ・ M。カ・イ 。ァゥョァ@ tubes. The
pressure differences across the stairwell wall were measured
at the ground, third, and
fifth
floors by inserting the probeinto the stairwell through the crack around the door. Again, an electronic manometer with a strip chart recorder was used. The roeasure.d values were averaged to represent the
mean
pressure difference across the shaft. Base readings tocorrect for weather effects (wind and stack action) were
conducted as described for the measurement of overall
airtightness value.
RESULTS AND DISCUSSION
The airtightness of the building, three individual stories, ten individual apartment units, and two stairwells
was measured. The measured results are presented below.
Airtightness Value of the Whole Building
Figure 4 shows the overall airtightness values per unit area of exterior wall. Also shown are the results obtained with the alternate method of using the building's heating
and ventilating system to pressurize the building interior.
The results indicate that at the maximum flow rate of 1,280
Lis (2,700 cfm) available from the
HVAC
system, thepressure difference across the building envelope was about
3 Pa (0.012 in. of water), which was inadequate to produce
meaningful
results.For compariS<>D, the measured overall airtightness values of three other apartment buildings are also shown in F igure 4 (Shaw 1980; Shaw et al. 1990) . Buildings A, D,
and V are
5,
14, and 17 stories high, respectively. Theresults indicate that the overall airtightness value of the test building is almost the same as that of Building V and is about 60% and 100% greater than those ofBuildings A anu
D at
50
Pa (0.2 in. of water) and 10 Pa (0.04 in. of water),セ@ 0 ·c v x w 0 0 セ@ v a. v 0 0 >
Mean Pressure Diff eren c e Across Exterior Wall, In Water
0 .00 0 ,05 0 . 10 0 . 1:> 0 10 0 25 O, JO o L jセ@ 0,"10 sセイMMMNMMMLMMMML MMセ MMMNセMMNM MMセMMQ@
Oセ@
1/
I
/
4.0 J.5 3.0 -2.5 0.9 0 .8 0.7 0. 6 0.5''lfll_ .... /··· /
'/OMZセ@
- - Building V"""""" '
1_0 .It - Building D LN セ ij@...
e- Te::;l Buildingif .& Test Building
0.5 } ••••• / (Supply Air Syslem)
t./
2.0 1.5 0.4 • 0.3 0.2 0.1 M M 0 I 0 20 JO 40 50 60 70 80 90 100Mean Pressure Difference Across Exterior Wall, Po
Figure 4 Overall airtightness values
Airtightness Values of Individual Stories
N
"
.§ u 0 3o 0 ·o: セ@ w セ@ D 0"
..{ ·c: ::::J セ@ a. v セ@ 0 > セ@ " c . ;::"'
セ@ <Z セ@"
> 0Exterior Walls Figure 5 shows the airtightness values of the exterior walls of the second, third, and fourth, stories. Again, the plotted results were normalized by the exterior wall area of the individual stories. As shown, the air-tightness value of the second story was about 25% smaller and, therefore, more airtight than lbat of the other lwo stories. Such a variation in results was likely caused by the conditions of windows and patio doors, which varied from apartment unit to apartment unit. For comparison, the overall airtightness value of the whole building was also included inFigure 5. The overall airtightness value per unit area of exterior wall was about the same as that of the second floor and was smaller than those of the other lwo stories. One reason for the discrepancy was that a ウゥァセ@
nificant part of the ground floor, occupied by commercial tenants, was separated from the building (i.e., no doors connecting the commercial units to the building). As a result, the exterior wall airtightness value of. the ground floor would be smaller than that of the upper floors . This, in tum, would result in a smaller overall airtightness value for the whole building.
Floor/Ceiling Separations Figure 6 shows the airtightness values of floor/ceiling separations for the ground/second, second/third, and third/fourth floors. All results were normalized by the floor area of the individual stories. The data showed a relatively high degree of scatter when compared with the results for the exterior wall airtightness determinations. This was probably because the exterior wall airtightness values were approximately nine times greater than those of the floor/ceiling separations. As the airtightness values of floor/ceiling separations were obtained indirectly by subtracting the ex erior wall leakage fcom the overall value, a small error in lhese measurements would result in a large error in the airtightness values of floor I ceiling separations.
Individual Apartment Units Ten apat1ment units on the third story were tested . Of the ten, permission was
350 N E ,; ... --' 0 セ@ 0
セ@
w 0 0 " < ·c ::::J v a."
セ@ 0 > "' "' v c := "' ;.:: セ@Pressure Difference Ac r oss Ex teri or Wall, In Water 6_0 ,....o.,.o_1 _____ _ _ ッセNッ⦅S@ ___ o.,....o5_o.o..-7 __ 0.r1 o _ _ _ _ _ _ _ ッセ L jM ッ NNN⦅LN@ 50 4.0 l .O 2.0 1.0 0. 9 0.8 0 . 7
•
o Overall nd 0 • 2 Fl. Exterior Wall rd 3 1h Fl . Exterior Wall ., 4 Fl. Exterior Wall 0 .6 GMセMMM セセMMGMMMMMMMMMGセMセセMNNオ@ 10 JO 50 70 100Pressure Difference Across Exterior Wall, Po
1.0 0.8 0.) 0.6 0.5 0.4 O.J 0. 2 N
セ@
0 セ@ ...,Figure 5 Overall and individual floor exterior wall air-tightness values O.JO N E ,; ... 0 .20 --' c· .!?
e
0"-"
Vl 0 0"
<
0.10 ·c 0.09 ::::J i; O.OB a. 0.07"
0 0 0.06 > セ@ " 0.05 .5 .c "' セ@ <Z O.O ot 0 ,0.} 2Pre ssure Difference Ac r oss Floor/Ceiling Separation, In Wate r
0 ,01 0.0) P セ PU@ 0_07 0. 10
"'
1st/2 nd Floor•
2nd/3rd Floor a Jrd/4th Floor•
4th/5th Floor "' 0•
•
0 6 7 8 9 10 10Pressure Difference Across Fl oor /Cei ling Separation , Po
0.05() N
'
E 0.040.u
O.OJO c ·2 セ@ 0 a. " Vl 0 v 0 .020<
0.010 0.009 0.006 0.007 0.006 JO ·c: ::::JFigure 6 Airtightness values of floor/ceiling separation for individual swries
obtained to test six apa rtment units extensively to determine the airtightness values of individual interior ー。イエゥエゥッセウL@
flo or/ceiling separations, and the exterior wall (which includes the corridor wall leakage). In addition, the overall airtightness values of these units were also measure<! independently. Figure 7 shows typical results of one of these series of tests. The sum of the individual component air leakage rates was approximately
equal
to エィセ@ ゥョ、・ー ・ ョセ@{ll ... ...J
"
0 a::"
"'
0 .:< 0"
...JPressure Difference Across Partition, In Water
0.00 jUP イMMM MMNMMMMMLM P N Pセ@ 0.10 MMMMMケMMMMMLMMMMMMイMMM 0.15 0. 20 0.25 MMセML@ O,JO 0 Overall 17
•
Exterior Wall JOO 2 A Floor 3..
Ceiling 4 0 Left Partition RセP@ 5•
Right Partition 200Pressure Difference Across Partition, Po
700 600 500 セ@u <OO 2 0 0:: セ@
"'
0 JOO .Y 0 セ@ ...J 200 100Figure 7 Overall and partition air leakages for apart-ment 307 c Zセ@ 0 0.. Q , 0 " .{ 8.0 7.0 6.0 5.0 4.0 J .O 2.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 O.J
•
A 0•
v..
0•
APressure Difference Acr os s Parlilion, In Water
Q_Q.J 0.05 0 07 0 10 301 North 301 South J05 South 306 No rth 306 South 307 North 307 South JOB North 0 JO 1.00 0 90 0 80 o 70 • c" 0 ,60 O.JO 0 ,20 0 10 0 .09 0 08 0 .07 ᄋセ@ t 0 0.. 0 ·c: ::J 0.06 セ@ P N Pセ@ 0.2 lMN MMMM MMMGGMMMMM MMMMMセ M MMMMMM セ NNNNj@ 0.04 J Figure 8 5 6 7 a 9 to 20 Jo "o :.a 60 10 6090
Pressure Difference Ac ross Por\ilion, Po
Airtightness values of interior partitionfor in-dividual apartment units
dently measured ッカ・イM」セiャ@ value. Similar results were also
obtained for the other five tested apartment units.
F igure 8 shows the airtigh tness values for the interior
Jlarti tions . The result<> were normalized by the areas of the
partitions. As shown, the measured airtightness values for
interior partition walls at
50
Pa (0.2 in . of water) variedfrom 0. 65 (Unit 308 South) to 3.1 L /s·m2 (Unit 306 Sou )
(0 .13 to 0 .61 cfm/ftZ) . 351 N E ,;
:-:.
c Zセ@ 0 c._ 0 g .';: ·c ::J セ@ 0. " セ@ 0 > セ@ セ@ " c :c .'!' '<( 0 0.. 0 0.
< ·c ::JPressure Differe nc e Across Partition, In Water
0 Ol P Pセ@ 0 0 7 010 0 ,)0 4.0 イMMMMM M MMセMM MMMセ M MNMM MMMMM MMMNNNNNML@ l.O l .O 1.0 0.9 o.a 0.7 0.5
t
0.5 0.4 I 0 J l ! " 30t South ... .312 North o 307 So u1n • 388 No rth 0 ,70 0.60 N .::::, o.so E u o."o c" 0,)0 0.20 0. 10 0 . 09 008 0 01 0. 06 0.05 セ@.
0. u -=' 0 > 0 2 LGMMMM LセNML M NM Y@ -'-, ッ MMMM MMセLMZZZッ M MLッMM M L M」@ MMZMZ LッMMZッッ セ Qセ P セ XッGMGYッ@ 0 04Pr essure Oiflerencc Acros s pッセ| ゥ エゥッョL@ Po
Pressure Difference Acro ss Partition, ln Wolcr
0 OJ 0 .05 0 .07 0 . 1 0 O.JO <.0 イMMM MMM M セMMM MMMN MMMMMMLMMMMMMMMM MM LNNNNNNNL@ }0 2 0 1 0 0 9 08 Y 307 Norlh 0. 70 Q 6Q N 0_50 0 <O 0 )0 .::::, .§ u c セ@ 0 a. セ@ 0 1 " 0. 0.
"
セ@ a > ...,
0.6 0 5 04 OJ 0. 10 0 ,09 0 .08 0,07 0.06 0.05 " セ@ a > "' "'.
c .c. "' ;.:: 0 2 jlMMセM LML ⦅⦅NN L M Xセ Y@ -'-1 ッMM MMMM Mセセッ MM MjッMM M TセP@ セウッセNッ M Lセ ッ セ Xッ N⦅セ ァッ@ o.o-4 Figure 9Pressure Dirrerence Across Porlilion, Po
Repeatability of airtightness measurements for interior partitions
Four partitions were each measured twice during this
series of tests, as these partitions are each shared by two
adjacent apartment units. The two results of each of the
four partitions are shown in Figure 9. As shown, except for
the partition between apartment units 305 and 306, the results of the two tests agreed within 20% of each other at
pressure differences greater than 20 Pa (0.08
in.
of water) .The discrepancy was likely caused by having obtained the
airtightness result indirectly by taking the difference
between the overall value and the overall value less that of the test component. As both values were much larger than
the airtightness value of the partition, a small error in these
measurements would result in a large error in the ftnal
Pressure Diflerence Across Floor. In Woler 0 01 0_0) 0 OS 0 ,07 0, 10 0 JO 1.00 0.90 O.B O
•
Apt. J 05 0.70•
N 0 Api.J06 E 0.60 N セ@..
Apl307 ::::."
0.50 0.100 セ@ -' D Apl ,JOB 0.090 0 0 . .40.
ApU12 o.oao 0 0 c: • · · ·2nd/Jrd Storey 0.070 0 0 O.JO c;: o FLOOR D"0'
0.060 0e
0 < 0.050 "'<
·;: •'..
::> 0.20 L LセG セ L NN@.
.
0 .0 .. 0 c セ@ ::> 0. ' ' 0 .030 セ@ "' "' セ@ "' 0 2 >..
0 セ@ > " 0.10 ' 0.020 セ@ c O.C9 セ@"' :2 o.ca .s 0' ;.=.
£ 0.07 X ᄋセ@ 0.06 ·.:;: 0.05 0 0 10 0.009 00< 0,008'
.
5• '
B 9 10 10 )0 <0 so 60 70 8:>Pressure Difference Across Floor, Po Pressure Difference Across Ceiling, In Waler
001 0 OJ 0 05 0.07 o. 10 O,JO I.CO 0.90 0.80 0.70 0 Apt.J06 N .... E 0.!50
..
Ap\.307 ::::. セ@'
-' 0.50"
Apt.JOB 0,\00 .E u a...
Apt.312 0.090 c, . .§ PNセP@ 0 .060 Zセ@ セ@ • -- ·Jrd/4th Storey 0.070 "' u 0 O.JO b CEILING 0 0 2 " o.oso<
<
·c 010 0.040 ·;: ::> ::> セ@ t; 0. 0.030 0. "' ",
D.
" 0..
0 > ' > セ@ 0.10.
0 .020 "' " 0.0<; :1 c ' :2 0.06 ' ..5"'
.
£ ;.: O.C7.
' ;.="'
ᄋセ@ O.C6.
.
.
セ@ PNPセ@ 0 010 O.OOQ 0.04 0.006'
•
5 6'
6 9 10 20 JO <0 50 60 70 80Pres::;ure Oif:erence Across Ceiling, Po
Figure 10 Airtightness values of floo r and ceiling for individual apartment units
F igures lOa and lOb show the airtightness values of
floor and ceiling separations, respectively, for individual apartment units. The results also indicate that the measured
airtightness values for floor/ceiling separations at
50
Pa (0.2in. of water) varied from 0.18 (Unit 306) to 0. 68 L/s·m2
(Unit 305) (0.035 to 0.1 3 cfm/ft2). The ceilings for this
story seem to be much more airtight than the floors. The
measured floor and ceiling airtightness values for the third
story Rlso indicated the same trend. No obvious reason
could be found to explain the difference.
Stairwells The airtightness of two stairwells is shown
in Figure 11. The south stairwell, which contains the roof
access hatch, was approxinutely 40% leakier than the north
stairwell.
352
Mean Slairweii/Corridar Pressure Difference, In of waler
0.03 0,05 0.07 0.10 0.)0 2000 •ooo
•
Norlh Stoirwoll•
South Stairwell 3000"'
E"
..J 0 .; 1000 0 2000 ,; 900 0 oc oc"
"
"' BOO 0 "' -" 0 0 -" " 700 0 -' _, "セ@
"ii 5()0 セ@ ·c;·"
u; 0 u; 500 1000 900 <00 aoo 700 JOO•
セ@•
7 6 9 10 20 JO 40 50 •a 10 aogoooMean Sloirweli/Corridor Pressure Difference, Po
Figure 11 Airtightness values for stairshafts
Possible Applications of the Data
Strictly speaking, these kinds of data are valid only for the buildings or components tested. For applications where an accurate estimate of the air leakage characteristics of a
specific building is needed (e.g., airflow model validation),
the only way to obtain the data is by measurement. It is not
likely tbat a correlation between airtightness values and
designs of wall construction
can
be developed (Shaw andJones 1979). This is because most wall construction consists
of a vapor barrier and a painted interior fmish (e.g., a
painted drywall). As such a combination is much more
airtight than other materials (e.g., bricks or concrete blocks), the airtightness value of a wall assembly is
depen-dent on how well the vapor barrier/interior component is
installed. Therefore, the materials used to construct the exterior portion of a wall assembly would not likely have a
significant influence on its air leakage characteristic. As
indicated in Figure 4, the overall airtightness values of fO\If
buildings with different wall constructions are not very different from each other.
The leakage data, while specific to the building tested,
can be used for design purposes (e.g., estimating air
infi ltration rates for sizing HV AC equipment or p.redicting
air leakage rates through interior partitions for designing
smoke control systems) . For such applications, the
design-ers need a complete data set, such as the one reported for
conducting sensitivity studies . SUMMARY
The airflow capacity of the building's heating and
ventilating system was insufficient to be used for measuring
the airtigb.tness value of the building envelope. Before
planning to
use
the building' s HVAC system for suchmeasurements,
it is
advisable to measurethe maximum
airflow rate and the JlllLUraum pressure difference it can
Because windows and doors are not uniformly
distri-buted in the building envelope, tests to measure the overall
airtightness value (conducted on the whole building) and the exterior walL airtightness values of individual stories often produce different results. For this building, the overall
airtightness value for the whole building at 50 Pa w:as 3.1
L/s·m2 (0.6 cfm/ft'l). The measured exterior wall
airtight-ness
values for individual stories at 50 Pa (0.2in .
of water)varied from 4.0 to 5.1 L/s·m2 (0.79 to 1.0 cfmJft'l.
The measured airtightness values for the building
components of individual apartment units varied from
component to component. For this building, the measured
airtightness values for interior partition walls and
floor/ceil-ing separations at 50 Pa (0.2 in. of water) varied from 0.65
to 3.1 L/s·m2 (0.13 to 0.61 cfm/ft2
) and 0.18 to 0.68
L/s·m2 (0.035 to 0.13 cfm/ff), respectively.
ACKNOWlEDGMENTS
The authors acknowledge the cooperation of the Canada Mortgage and Housing Corporation, the Centretown Citizens (Ottawa) Corporation (CCOC), the tenants of the
test building, and the members of the CCOC Tenants
Committee for their cooperation in making this study
possible, particularly Mr. Glen Dunning and
his
staff ateeoc
for their assistance during the lests. The authors alsowish to acknowledge the contribution of J.T. Reardon in the
preparation of this paper and the assistance of L.P. Chabot, M. Ferron, and L. Sans Cartier in the field tests and in the processing of the data.
353
REFERENCES
Kurabuchi, T., J.B . Fang, and R.A. Grot. 1990. "A
numerical method for calculating indoor airflows using a turbulence model." NISTIR 89-4211. National Institute of Standards and Technology, U.S. Depart-ment of Commerce.
Said,
M.N.
1990. 11 Air and smoke movement model for tallbuildings." Internal Report, Institute for Research in Construction, NRC.
Shaw, C.Y. 1980. "Methods for conducting small-scale
pressurization tests and air leakage data of multi-story
apartment buildings." ASHRAE Transactions, Vol. 86,
Part 1, pp. 241 -250.
Shaw, C.Y., and L. Jones. 1979. "Air tightness and air
j.nfiltration of school buildings." ASHRAE
Transac-tions, Vol. 85, Part 1, pp. 85-95.
Shaw, C.Y., D.M. Sander, and G.T. Tamura. 1973. "Air
leakage measurements of the exterior walls of tall
buildings. " ASHRAE Transactions, Vol. 79, Part 2,
pp. 40-48.
Shaw, C.Y., S. Gasparetto, and J.T. Reardon . 1990.
"Methods for measuring air leakage in high-rise apart-ments." STP 1067, Air Change Rate and Airtightness in Buildings, pp. 222-229. Philadelphia: American
Society
of
Testing Materials.Tamura, G.T., and C.Y. Shaw. 1976. ''Air leakage data
for the design of elevator and stair shaft pressurization