Resistivity assessment of an earth-filled dike with a permanent hydraulic head (Canal de Roanne à Digoin, France): 4D effects on 2D ERT monitoring

N/A
N/A
Protected

Academic year: 2021

Partager "Resistivity assessment of an earth-filled dike with a permanent hydraulic head (Canal de Roanne à Digoin, France): 4D effects on 2D ERT monitoring"

Copied!
3
0
0

Texte intégral

(1)

HAL Id: hal-01551781

https://hal.archives-ouvertes.fr/hal-01551781

Submitted on 30 Jun 2017

HAL is a multi-disciplinary open access

archive for the deposit and dissemination of sci-entific research documents, whether they are pub-lished or not. The documents may come from teaching and research institutions in France or abroad, or from public or private research centers.

L’archive ouverte pluridisciplinaire HAL, est destinée au dépôt et à la diffusion de documents scientifiques de niveau recherche, publiés ou non, émanant des établissements d’enseignement et de recherche français ou étrangers, des laboratoires publics ou privés.

Resistivity assessment of an earth-filled dike with a

permanent hydraulic head (Canal de Roanne à Digoin,

France): 4D effects on 2D ERT monitoring

G. Bièvre, L. Oxarango, R. Clément, T. Günther, D. Goutaland, M. Massardi

To cite this version:

G. Bièvre, L. Oxarango, R. Clément, T. Günther, D. Goutaland, et al.. Resistivity assessment of an earth-filled dike with a permanent hydraulic head (Canal de Roanne à Digoin, France): 4D effects on 2D ERT monitoring. 3rd Internat. Workshop on Geoelectrical Monitoring GELMON 2015, Nov 2015, Vienna, Austria. 2 p. �hal-01551781�

(2)

G

EL

M

ON

2015

Berichte Geol. B.-A., 112, ISSN 10178880 3rd Internat. Workshop on Geoelectrical Monitoring

GELMON 2015, Vienna, 24.-26.11.2015

35

Hydrology I

13

Resistivity assessment of an earth-filled dike with a permanent hydraulic

head (Canal de Roanne à Digoin, France): 4D effects on 2D ERT monitoring

G. Bièvre

(1)*

, L. Oxarango

(2)

, R. Clément

(3)

, T. Günther

(4)

, D. Goutaland

(5)

and M. Massardi

(6)

(1) ISTerre, Université Grenoble Alpes, Grenoble, France (2) LTHE, Université Grenoble Alpes, Grenoble, France (3) IRSTEA, Antony, France

(4) LIAG, Hanover, Germany

(5) CEREMA, Laboratoire de Clermont-Ferrand, Clermont-Ferrand, France (6) CEREMA, Laboratoire d'Autun, Autun, France

* gregory.bievre@ujf-grenoble.fr

Several geophysical and geotechnical techniques were tested on an earth-filled canal dike in the framework of a French research program (labelled DOFEAS). The aim of this program was to test the ability of geophysical techniques, first, to image the body of the dike and to detect weak zones associated with known leakages and, second, to monitor the evolution of geophysical parameters (mainly electrical resistivity) with time in relation with the evolution of water circulation and internal erosion. The chosen site is an earth-filled dike (3 to 4m high) relying upon Jurassic marly limestones. The dike contains a permanent hydraulic head and exhibits 2 leakage zones in the study area. Repair works, conducted after the canal was emptied, allowed to visually identify the seepage entries (a few tens of cm each in diameter) within the canal. Drillings, in situ and laboratory tests allowed to build a hydrogeotechnical model of the site. Probes were installed in boreholes to monitor the water table variation over time. Active geophysical experiments including seismic refraction and tomography (P- and S-waves), surface wave inversion (SWI) and electrical resistivity tomography (ERT), were used to characterize the geometry of the sub-surface. Concerning the time-lapse ERT survey, 128 electrodes, spread each 1 m, were permanently installed on the dike crest. Measurements were conducted using a Wenner-Schlumberger protocol (around 3600 measurements). 7 sequences were acquired during 2 months prior, during and after repair works. These works induced variations in the water level within the canal. The combined effects of the complex 3D geometry of the dike and of the varying water level were numerically determined to correct the geometric factor k. Compared to the analytical k, the geometric factor corrected from the topographic effects induced complex resistivity variations between 8 and 18%, depending on the electrode spacing but also on the water level into the canal. Furthermore, numerical simulations also showed that, depending on the water level into the canal, the electrical current density within the dike could also be affected by a factor of up to two. This indicates that a more or less important part of the measured resistivity carries information which originates from the water. However, a full 3D correction of the measured apparent resistivity would require to know the 3D resistivity distribution within the ground.

(3)

G

EL

M

ON

2015

Berichte Geol. B.-A., 112, ISSN 10178880 3rd Internat. Workshop on Geoelectrical Monitoring

GELMON 2015, Vienna, 24.-26.11.2015

36

The time-lapse inversion of the ERT data allowed to locate the main pipe within the dike, at a depth of around 3.4m, just above the interface between the bedrock and the dike body. This location was in agreement with the visual location of the seepage. Corrected resistivity were found to be more realistic than with the analytical k factor and allowed a better detection of the main pipe. However, the second and smaller pipe was not detected, probably because of a too low contrast.

These results confirm the applicability of calibrated geophysical techniques for assessing earth dike geometry. They also suggest that the correction for the 3D to 4D effects provides a better detection of anomalies (i.e. seepage pipe) evolving with time.

Références

Documents relatifs

Although the embedded temperature probes are closer to the river side of the levee (Figure 1), we used the same temperature profile model for compensating both inverted

To validate our approach, we present a platform used to generate activity monitoring systems dedicated to specific applications, we also describe in details the technical validation

Roger-Estrade J, Richard G, Caneill J, Boizard H, Coquet Y, Defossez P, Manichon H (2004) Morphological characterisation of soil structure in tilled fields: from a diagnosis method

Keywords: 4D ERT; ATES; Temperature monitoring; Time-Lapse; Electrical Resistivity Tomography; Shallow geothermal system; Heat storage;

Natural history of allergic sensitization in infants with early-onset atopic 1 dermatitis: results from ORCA Study... Figures: 3

Tropospheric NO 2 columns were retrieved from the measurements and strongly enhanced values were observed under clear sky conditions close to Frankfurt, but also over clouds, in

hydrogels were also prepared from gelatin solutions with GG microgels in PBS, so the strength might be lower than that of the MR hydrogels prepared form water

En essayant de résumer ces chapitres consacrés à la « formation des échelles », c’est à dessein que j’ai omis de parler des fameux « résidus », terme qu’emploie