Publisher’s version / Version de l'éditeur:

Technical Note (National Research Council of Canada. Division of Building Research), 1961-10-01

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

NRC Publications Archive

Archives des publications du CNRC

For the publisher’s version, please access the DOI link below./ Pour consulter la version de l’éditeur, utilisez le lien DOI ci-dessous.

https://doi.org/10.4224/20338414

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

Performance of a Cavity Wall in Laboratory Moisture Penetration Tests

Ritchie, T.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

NRC Publications Record / Notice d'Archives des publications de CNRC:

https://nrc-publications.canada.ca/eng/view/object/?id=f231b728-8f6b-416c-b55a-dfa403714376 https://publications-cnrc.canada.ca/fra/voir/objet/?id=f231b728-8f6b-416c-b55a-dfa403714376

(2)

DIVISION OF BUILDING RESEARCH

'JrE C1HI N II

CAlL

NOTlE

347

NOT FOR PUBLICATION FOR INTERNAL USE

PREPARED BY T. Ritchie CHECKED BY EVG APPROVED BY NBH

PREPARED FOR Record Purposes

DATE October 1961

SUBJECT PERFORMANCE OF A CA VIT Y WALL IN LABORA TOR Y

MOISTURE PENETRATION TESTS

Testing the resistance to me>isture penetration of brick walls was undertaken in 1960 -61 to determine the influence of brick and mortar properties on the performance of brick masonry. A cavity wall was included for comparison with solid walls under study. The effect of filling the cavity with a specially prepared insulating material on the performance of the wall was also studied.

CAVITY WALL CONSTRUCTION

Cavity walls have been used extensively in Great Britain and other European countries as a means of overcoming rain penetration of masonry walls. In recent years in the United States many important buildings have been constructed of cavity walls. The principle of operation, m.ethod of construction, and properties of cavity walls have been reviewed (1).

The cavity wall used in the tests now reported was a conventional 10-inch (nominal) wall, consisting of two 4-inch brick walls separated by a 2 -inch air space. The two walls were tied together with galvanized steel

Z -bar s, and the "gutter" at the base of the wall was forrned of combined copper foil and tarred paper flashing. Vertical joints of the bottom course of bricks in the outer half of the wall were omitted to provide

drains for the cavity. A "window" was formed in the back part of the wall by ornitting several bricks. The opening was cover ed by a rigid sheet of

(3)

2

-clear plastic material sealed to the brickwork, through which the inner surface of the outer part of the wall could be observed during the test.

In a later test, when the cavity was filled, the back of the insulating material could be observed during the test.

The walls were about 3 1/2 feet wide and 4 feet high, constructed by an experienced bricklayer, and were stored for a month before being tested for moisture penetration. The method of test described in reference (2) was followed, except that an air pressure difference of 2 inches of

water was used (approximately equivalent to wind of 50 mph blowing against the wall of a building). The 10-inch cavity wall was compared with 8 -inch walls of conventional construction, in which header bricks were used every sixth course. The same types of brick and mortar were used for ,both types of wall.

MATERIALS

The bricks were smooth-faced yellow bricks made in the Toronto area. They had been formed by the extrusion method and had three perforations. The initial rate of absorption of the bricks was high; it ranged from 63 to 81 grams per minute per 30 square inch for 20 samples tested. The average compressive strength of 5 samples was 7840 psi.

The mortar was made of masonry cement and sand in proportions by volume of 1:3. The materials were hoe-mixed with water in a trough to a consistency considered suitable by the bricklayer. During construction of the walls the mortar joints of one face were tooled to concave shape.

RESULTS

The 8-inch solid wall was extremely leaky. Dampness appeared on the back surface 12 minutes after the start of the test. In the

first hour of test close to 4 gallons of water had leaked from the back surface of the wall, and in 24 hours of test more than 110 gallons of water had passed through the wall.

In testing the cavity wall without insulation in the air space it was not possible to establish an air pressure difference across the wall of 2 inches of water. The weep holes in the outer part of the wall

required the air pressure difference to be established across the inner part of the wall, but it was too air -permeable for the capacity of the apparatus. Air leakage from some of the joints could be felt with the hand, and only about 1 1/4 inches of air pressure difference across the wall was obtained

(4)

3

-in the test. When the cavity was filled with insulation, however, pressure of 2 inches of water was obtained for the test.

During the test of the unfilled cavity wall str earns of water could be seen flowing down the inner surface of the outer wall. In 24 hours of test, however, no dampness was seen on the back surface of the inner wall, and no moisture apparently had crossed the cavity.

After 24 hours the wall was removed from the test apparatus, and the cavity was filled with "water -repellent" vermiculite, poured into the

cavity from the top. Sheets of plastic sealed to the bricks at the sides of the wall held the material in the cavity. The insulation-filled cavity wall was tested for 6 days and in that time there was no sign of dampness on the back of the wall. The insulating material could be observed through the window, and there appeared to be no dampness in that part of it next to the window. When the test was completed the wall was removed from the apparatus and the cavity was opened by removing the sheets of plastic along the sides. It was observed that the insulating material adjacent to the outer part of the wall was damp, and the dampness extended into the material about 1/4 to 3/8 inch. The moisture content of the

insulating material as received was 0.5 per cent of.the oven-dry weight (80G

C) and that of a sample of the material taken from the wall immediately after the test was 7. 3 per cent. There was no noticeable loss of insulating material from the cavity during the test due to drainage of water from the weep -holes.

ADDITIONAL TESTS

The same brick used in the walls described previously was also used in constructing a solid 8 -inch wall with a rp.ortar composed of portland cement, lime and sand (l:l :6). Although this wall performed considerably better than the 8 -inch wall in which the masonry cement mortar セ。ウ used it was nevertheless considered to be quite permeable. In 24 hours of test more than 69 gallons of water passed through it.

In,another wall, built of masonry cement mortar. the bricks were treated with a silicone water -repellent material before construction to reduce

the high rate of water absorption of the bricks which is generally as sociated with poor bonding of mortar to brick and water permeability of the brickwork. The performance of this wall was better than that of the cement -lime

mortar, but even so, an appreciable amount of leakage through the wall took place.

CONCLUSIONS

(5)

4

-cement-lime mortar to construct 8 -inch solid brick walls. Under test conditions simulating heavy wind -driven rain the walls wer e quite pern"leable. When the same brick was used by the same bricklayer to construct a 10 -inch cavity wall. however, there was no penetration

of moisture through the wall. The usefulness of cavity wall construction as a means of overcoming moisture penetration of brick walls appeared to be well demonstrated in these tests.

The particular combinations of brick and mortars used in the tests resulted in relatively permeable masonry; the performance probably could have been improved somewhat by the use of

a

more suitable mortar. SOlne degree of water permeability of a solid wall constructed of this particular brick would be expected. however, regardless of the mortar. Cavity wall construction therefore appears to be a positive means of overcoming leakage through this type of brickwork which probably would occur under severe wetting conditions.

The performance of the insulation -filled cavity wall was consider ed highly satisfactory. Ther e was no evidence that water leaking through the outer

part of the wall could "travel across this type of insulating material to the inner part of the wall.

REFERENCES

(1) Ritchie, T. Cavity walls. National Research Council. Division of Building Research. Canadian Building Digest No. 21. Ottawa. September 1961.

(2) Ritchie, T. and W. G. Plewes. walls. ASTM Bulletin No. (Reprinted as NRC 5999.)

Moisture penetration of brick masonry 249, October 1960. p. 39 -43.

Références

Documents relatifs

Among the various factors that may affect the fluid dynamics of the blood flow, the geometry of the bifurcations (angles), the distance separating two consecutive bifurcations,

(1) و رﻴﺸﺘ أ ﻰﻝإ ﺔﻴﺨﻴرﺎﺘﻝا دﻫاوﺸﻝا ﻗإ نﻼﻋإ لوأ ن لﻜﺸ ﻰﻠﻋ رﻬظ ﻲﻋﺎﻨ تﺎﻜوﻜﺴﻤ ﺔﻴﻀﻓ ﺔﻨﻴدﻤ ﻲﻓ ) Cyrene ( ﻓإ لﺎﻤﺸ ﺎﻴﻘﻴر ، ﺒﻗ ﺢﻴﺴﻤﻝا دﻴﺴﻝا دﻼﻴﻤ نﻤ نرﻗ

Furthermore, we found that this gene was essential for corneal wound healing promoted by atRA on HCE cells and on a mouse model of corneal injury by promoting cell migration..

However, even as transmedia texts provide the chance to engage deeper with a text and take advantage of the type of deep involvement in soap opera texts mentioned in the

Impact of the dairy matrix structure on milk protein digestion kinetics:

/ La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur. Access

1) Tid1 inhibits Rad51- and Rad54-mediated D-loop formation in vitro in an ATPase- independent manner by competing with Rad54 for binding to the Rad51 filament (Figure.. 1