• Aucun résultat trouvé

Concrete slabs for basementless houses

N/A
N/A
Protected

Academic year: 2021

Partager "Concrete slabs for basementless houses"

Copied!
6
0
0

Texte intégral

(1)

Publisher’s version / Version de l'éditeur:

Technical Note (National Research Council of Canada. Division of Building Research), 1952-11-03

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

NRC Publications Archive

Archives des publications du CNRC

For the publisher’s version, please access the DOI link below./ Pour consulter la version de l’éditeur, utilisez le lien DOI ci-dessous.

https://doi.org/10.4224/20358658

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at Concrete slabs for basementless houses

Ball, W. H.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

NRC Publications Record / Notice d'Archives des publications de CNRC: https://nrc-publications.canada.ca/eng/view/object/?id=182574d3-f5a7-4c54-9cec-33097a08f938 https://publications-cnrc.canada.ca/fra/voir/objet/?id=182574d3-f5a7-4c54-9cec-33097a08f938

(2)

In summary it would appear that a base of compacted crushed rock or other suitable material is desirable in all but

ffhilltop" locations. A minimum thickness of

6

inches is

suggested for such base.' Where additional thickness of base

is required to raise the slab to a suitable height, with respect to street levels or adjacent ground, it should be provided.

Mr.

Card suggested that in his experience builders often

wished to build basementless houses on sites which were low and

Gァ・ョセイ。ャQケオョウオゥエ。「ャ・ for any type 0f·ordinary construction. It was 'the feeling'ot the group that such an approach,was unsatisfactory

and that the selection of a suitable site, as 'regards to drainage at least, was an important item in assessing the sUitability of,,'

concrete slab construction. ;

132

',',

No.

,.

FOR INTERNAL USE

DATE Nov.

3,

1

qr;

APPROVED BY R.F.L. " セ....NエNセN " # \ • • I ' • .\

"NOTlE

CHECKED BY

Concrete Slabs for Basementle&! hセオウ・セ

DIVISION OF BUILDING RESEARCH

,'1

EClHIN J[CAlL

Summary of Meeting W.. H.B.

NATIONAL RESEARCH COUNCIL OF CANADA

SUBJECT

Base for Slab

.A discussion of the various faotors affecting the design

of "concrete slabs" for basementless houses was held at the . , _

Division of Building Research, N.R.C., on 'Wednesday, October

8,

1952.

Mr.

R.W.G. Card,

Mr.

Ira Ashfield,

Mr.

F.L. Peckover,

Mr,

A.G. Wilson,

Mr.

A.D. Kent and Mr. W.H. Ball took part. This note

has been prepared to record the scope of the talks, and also may be useful as a gUide in the assessment of a particular proposal for the construction of a concrete slab for'8,'basementless house.

Discussion of the necessity for a compacted base of

crushed rock or other suitable material for the slab led to the

.

'

following assumption:

That on well-drained granular locations no additional base would be necessary provided that the relative height between

slab and surrounding ground or streets was suitable. It was,

however, considered desirable to have the slab above adjacent ground level to provide protection a£ainst a temporary

accumulation of water from melting snow, as well as splash clearance.

PREPAR.ED BY

PREPARED FOR

(3)

-

...

,

18l.).II/: ti .. ., ',.. I f; • ZZセ I ".': :f'\..1 I ' '.'

(4)

2 -Waterproofing Between Base and Slab

The provision of suitable waterproofing was discussed and the need for a waterproof membrane between the slabs and its base was recognizedo This membrane to have the function of preventing the passage of water (either liquid or vapour) into the slab so as to protect insnlation and floor surfacing materials.

Suitabie materials and methods of installation were con-sidered. It was 。ァイ・セ、 that lightweight saturated felts would not be acceptable. The provision of an asphaltic membrane applied

on a thin concrete base was also considered. It was suggested that a single layer of heavy roll-roofing would provide adequate protection. Joints between strips to be well-lapped (perhaps 6 inches) and sealed with asphalt. In order that such a membrane might be applied without being damaged, it would probably be necessary to cover the compacted base with a thin layer of sand

(1 inch).

Section of the Slab

It was generally agreed that, while a slab of uniform section would have merit, the "grade-beam" type of slab had several practical advantages. It provides a means of retaining the compacted base, provides a firm surface against which insula-tion can be placed, and a means of maintaining strength in the slab at the edge where perimeter heating ducts are included in the slab. A slab of 6-inch minimum thickness was proposed.

Reinforcement of the Slab

The matter of slab reinforcement received considerable discussion without any overall recommendation being made. It was decided that the writer should look into the matter further in conjunction with the Building Design Section and that he should subsequently make a report on this aspect of the problem.

Several assumptions were discussed which are noted as follows:

1. It was agreed that it is reasonable to assume that frost action on the slab would not be a direct factor in the design since sufficient insulation and heat would be specified to insure that freezing temperatures would not exist under the slab. The validity of this

assumption can, of course, only be recognized in cases where the building is heated in such a manner as to keep the slab warm. It would not be appropriate where

it was proposed to heat a building with a space heater. 2. It was suggested that in locations where sand or gravel occurred naturally it would not, under ordinary circum-stances, be necessary to reinforce the slab, other than

(5)

]

3

-to provide temperature ウエ・・ャセ

3.

The problem of reinforcement for slabs built over soils which were likely to swelL or shrink with change in moisture content was discussed at some length, The

イセアオゥイ・ュ・ョエウ of the Winnipeg building cOde キ・セ・ cited as ッセ・ extreme in this respect. The proposition was" made that for. a situation such as this tqe slab could be expected to rise in the centre due to the"accumula-tion of moisture under the slab. Should drying occur at the edges of the slab, a similar distqrtion might affect the slab. Therefore, イ・ゥョヲッイ」・ュ・セエ of such slabs might usefUlly be based on this assumption.

Insulation of the Slab

,

The discussion of insulation for the slab centred maiply on how much insulation should be used, and the types of insulat!on s4itable for sqch use. It was suggested that no type of ヲゥ「イ・「ッセ、

be considered &s suitable. One to 2 inches of insulation havipg " a "k" value of 0.30, or better, is desirable. Such insulation to be applied to the edge of the slab and to extend below a flat slab for at least ウゥセ inches. Where a grade beam is used, the insula-t+on should cover, at least, the depth of the grade beam and be " not less than 12 ゥョ」ィ・セ in depth. Greater depth ュセケ be desirable! Where heat is セオーーャゥ・、 to the slab, as in the panel system, ゥョウオャ。セ

tion of the underside of the slab should be considered,

Ftbreglas board coated with asphalt in such a manner as to exclude moisture was considered to be adequate for セィゥウ type of application. Materials such as Onazote, Aero-Jablex, and Foamglaa were considered to be generally superior for. this ーオイーッセ・ due to" their high resist"ance to the entry or passage of moisture.

However, little is known about their performance under severe conditions.

The need for a protective finish for the insulation was mentioned, and the need for protection of the insulation during

construction was also emphasized. Building Services

Some of the difficulties which might arise as a result of the entry of sewer and water services to the building were mentioned. It was suggested that plans be so prepared that a minimum amount of disturbance to the support of the slab would result. Kitchen and bathroom services back-to-back near the

service side of the building would be of advantage, both from the viewpoint of installation and repair if necessary. Reinforcing of the slab over service trenches might be considered.

DiffiCUlty in reinforcement in slabs containing heat con-ducting lines was mentioned and will require special attention

(6)

r •

,

.

'.

i I , I

Références

Documents relatifs

This paper proposed a novel Bayesian regularization technique for sparse pMRI reconstruction with a BL mixture priors to handle complex-valued pMRI data and promotes two sparsity

response to corneal stimulation was also compared with the reflexive response of the muscle to the same stimulus. Cells in one class, for the most part in the

In order to identify PPARb/d- regulated miRNA involved in the skin response to UV, we compared miRNA expression in skin samples harvested from Ppard +/+ and Ppard /

Given a TCP port number pair, it returns a character string which identifies the owner of that connection on the server’s system.. The Identification Protocol was formerly

A mechanism is needed to allow the sender to transmit this sort of presentational information to the recipient; the Content-Disposition header provides this mechanism,

= Remettre l'image / le document dans son contexte et l'expliquer par rapport à celui et/ou émettre des hypothèses ou des conclusions par rapport à ce que l'on a vu.. Autres

The comparison of reliability indices between the two design methods as a function of the span length is shown in Figure 6.38, Figure 6.39, and Figure 6.40 for the

Since, the salt particles and the co-continuous polymer blend morphology lead to very different pore sizes, a particular feature of this technique is the creation of a bimodal pore