AUG 2 19W ENGINEERING DATA TRANSMITTAL
Page 1 of j[_— 626324
2. To: (Receiving Organization)
Distribution
3. From: (Originating Organization)
SNF Project W-441
4. Related EDT No.:
N/A_
5. Proj./Prog./Dept./Div.
SNF Project W-441
6. Design Authority/ Design Agent/Cog.
Engr.:
C. Van Katwijk
7. Purchase Order No.
N/A
8. Originator Remarks:
N/A
9. Equip./Component No.
N/A
10. System/Bldg./Facility:
SNF CVDF
11. Receiver Remarks:
N/A
11 A. Design Baseline Document? [ ] Ves [ X ] No 12. Major Assm. Dug, No.
N/A
13. Permit/Permit Application No.
N/A
14. Required Response Date:
N/A
• 1 5 . DATA TRANSMITTED ( F > CG) < H ) < I >
(A) Item
No.
(B) Document/Drawing No.
(C) Sheet
No.
(Dl Rev.
No.
(E| Title or Description of Data Transmitted
Approval Desig-
nator
Reason for Trans- mittal
Origi- nator Dispo- sition
Receiv- er Dispo-
sition
1 SNF-4914 0 CONDUIT FOR SAFETY
CLASS WIRING
tj
SQ 2 1 N/A
16. KEY
Approval Designator (F) Reason for Transmittal (G) Disposition (H) & II)
E. S, Q, D or N/A (see W H C - C M - 3 - 5 , S e c . 1 2 . 7 )
1 . Approval 4. Review 2. Release 5. Post-Review
3. Information 6. Dist. (Receipt Acknow. Requiredl
1. Approved
2. Approved w / c o m m e n t 3. Disapproved w / c o m m e n t
4. Reviewed no/Comment 5. Reviewed w / c o m m e n t 6. Receipt acknowledged 17. SIGNATURE/DISTRIBUTION
(See Approval Designator for required signatures) (G)
Rea- son
(H)
Disp. (J I Name (KJ Signature I D Date (Ml MSIN
(G) Rea- son
(HI
Disp. (J) Name (K) Signature <U Date (Ml MSIN
Designated Engineer C. Van Katwijk, See Distribution
lCtf
' Design Authority D. WhitehurstV^^-yyj^
S a f e t y . Brehm
&^tf&jj^fy
<tf'fcf
Ramsgat*
19.
T. Choho
Authorized Rej
for Receiving Organization
tuft
ative Date
u
Design' Cognizant
21. DOE APPROVAL (if required) Ctrl. No.
• Approved
[3 Approved w/comments [] Disapproved w/comments
BD-7400-172-2 (05/96) GEF097
s
SNF-4914, Rev. 0C O N D U I T F O R SAFETY C L A S S W I R I N G
Carl Van Katwijk
Numatec Hairford, Richland, WA 99352
U.S. Department of Energy Contract DE-AC06-96RL13200 EDT/ECN: 626324
Org Code: 2G300 B&R Code: 39EW40400
UC: 620
Charge Code: 105559/A000 Total Pages: 34
Key Words: Conduit for Safety Class Wiring Abstract: Conduit for Safety Class Wiring
TRADEMARK DISCLAIMER. Reference herein lo any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise, docs not necessarily constitute or imply its endorsement, recommendation, or favoring by the United Slates Government or any agency thereof or its contractors or subcontractors.
Printed in the United States of America. To obtain copies of this document, contact: Document Control Services. P.O. Box 950, Mailstop H6-08, Richland WA 99352. Phone (509) 372-2420; Fax (509) 376-4989. I A M A ' A SAfSO
AUG 2 1999.
DATE:
ID;
STA:
( g )
Rel il^ape Approval
Approved for Public Release
Commercial Grade Item Upgrade Dedication Form
[: '•" -.' "" Section 1 Part information
Item No.: N A Manufacturer: Supplier:
Mfg. Part/Model No.: Supplier's P/N:
Part Description:
End Use Description:
•-,' • Section 2aCompone it Information
. . . . ...
Equipment No.: See a t t a c h e d Section 9
Specification No.: W - 4 4 1 - C I , Section 1 6 1 1 0
Manufacturer: A m e r i c a n Electric
Past P.O. No.: N A
Procurement and/or Equipment Supplier (if different from manufacturer): N A Equip. Supplier's Part No.:
Model No.: S e e a t t a c h e d N A
Section 9
Component Description: Rigid conduit, nipples, sealtight flex c o n n e c t o r s , struts and straps, condulets, locknuts/grounding locknuts, w a s h e r s , spring nuts, flexible metal conduit/cqniniectors; :
tWMMi'i'U-iUi-i'. . •.
. Section 2b Commercial Availability of the Item.;.<,:..,..
. J M ; : ;.:<1. is the Item available from a catalogue of a qualified NQA1 supplier? (coordinate with project CGI interface Engineer or BTR) 1 ] YES (go to#2 below)
[X] NO (go to procedure step 6.3.2, proceed to dedicate Item.)
If not available from a qualified NQA1 supplier, is it available from an ISO 9000 supplier? (coordinate with project CGI interface Engineer or BTR)
[ j YES (go to #2 below, then go to procedure step 6.3.2, proceed to dedicate Item) [ X ] NO (go to procedure step 6.3.2, proceed to dedicate Item.)
2. List of Candidate qualified suppliers or ISO 9000 suppliers
company name & type contact name phone N A
SNF-4914. Rev. 0 Page 1 of 33
3. Recommended Procurement Strategy (coordinate with project CGI interface Engineer or BTR}:
N A
ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Commercial Grade Item Upgrade Dedication Form
SNF-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
1'ago 2 o f 33
Section 2c CGI Determination
1. Question #1: is the Item subject to design or specification requirements that are unique to nuclear facilities or activities?
[ ] YES (the Item is not commercial grade) [ X ] NO (continue)
2. Question #2: Is the Item used in applications other than nuclear facilities or activities?
[ j NO (the item is not commercial grade) [ X ] YES (continue)
3. Question #3: Is the Item ordered from manufacturer/supplier on the basis or specifications set forth in the published product information (e.g. manufacturer's catalog)?
[ ] NO (the Item is not commercial grade) [ X ] YES (continue)
[ X I All three criteria have been satisfied. The Item meets the definition of commercial grade.
== v = . . ; = . . Section 2d Reason for Dedication
51:::: :=5=;:=Y ;;=::••• TJhfe: ab^Ss/ectescribed Item is being Dedicated for use in the application cited for the following reason(s):
[ X ] Item is being purchased from a non ESL manufacturer supplier as commercial grade to be used in a Safety Class application.
[ ] Item is being purchased from a non ESL manufacturer supplier as commercial grade to be used in a Safety Significant application.
[ ] Item was purchased from a non ESL manufacturer supplier as commercial grade to be used in a Safety Class application.
[ ] Item was purchased from a non ESL manufacturer supplier as commercial grade to be used in a Safety Significant application.
[ ] Other flike-for-like', similar, substitution, replacement evaluation) vf::M(;<;M'.-: Section 3 Failure Effects Evaluation
A. Part/Component Safety Function:
1. Provide conduit p r o t e c t i o n , structural support f o r safety class w i r i n g . 2. M a i n t a i n critical function before, during, and after Seismic Event.
3.
B. Part/Component Functional Mode:
Safety Function #1:
[ J Active - Mechanical or Electrical change of state is required to occur for the component to perform its safety function
I X ] Passive - Change of state is not required for the component to perform its safety function Safety Function #2:
[ j Active - Mechanical or Electrical change of state is required to occur for the component to perform its safety function.
[ X ] Passive - Change of state is not required for the component to perform its safety function Safety Function #3:
[ ] Active - Mechanical or Electrical change of state is required to occur for the component to perform its safety function.
[ ] Passive - Change of state is not required for the component to perform its safety function
Commercial Grade Item Upgrade Dedication Form
SNK-4914. Rev. 0Title C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 3 o f 33
C. Host Component Safety Function (if applicable): N A 1.
0. Failure Mode(s) and the effects on component or system safety function (see Worksheet 1):
1. Fracture or material f a t i g u e leads t o loss of structural support a n d possible d a m a g e t o w i r i n g . 2. Loss of sealtight integrity of fittings could result in moisture corrosion and possible d a m a g e t o
w i r i n g .
4.
Section 4 Environmental & Natural Phenomena Hazard Design Environmental Qualification Required:
Yes[ ] No [ X ]
Environmental Condition B
If yes: Environmental Qualification Requirements Limiting Environmental Conditions:
Required Safety Functions:
Qualification Period:
Natural Phenomena Hazard (NPH) Design Required:
Yes [ X ] No [ ] H N F - P R O - 9 7 , R e v . 0
If yes: NPH Design Requirements Performance Category: P C - 3
NPH Design Req'ts.: Seismic Condition C Required Safety Functions: Provide protection and support for safety class w i r i n g . M a i n t a i n critical function b e f o r e , during, a n d after Seismic E v e n t . Section 5 Component Functional Classification
[ X ] Safety Class (SC) [ ] General Service (GS) ( ] Safety Significant (SS) If part/component classification is different from host component/system, document basis. N A
SetfKon jS(^served) _ Section 7 (Reserved) .
Section 8 References (for Functional Classification)
National Codes/Standards: IEEE Safety Analysis Report (SAR): Drawings: H N F - S D - S N F - S E L - 0 0 2 ,
6 2 8 H N F - S D - S N F - S A R - 0 0 2 , Rev. 6 A
Rev. 4 A
Vendor Manual/Manufacturer/SupplierInformation: Rigid C o n d u i t - L T V Steei Tubular Products/Galvite
Rigid C o n d u i t N i p p l e s / C o n n e c t o r s / L o c k n u t s / B e a m C l a m p s / R e d u c e r s - A p p l e t o n Catalog C F - 2 Pages 4 , 5 , 6 , 7 , 1 0 ;
C o v e r s a n d g a s k e t s for Form 3 5 Conduit O u t l e t Boxes - A p p l e t o n C a t a l o g A - 8 , Pages 6 a n d 7 C o n d u i t Nipples - C o n d u i t Pipe Products Catalog Page KG
Flexable Steel C o n d u i t - T h o m a s & Betts Liquidtight Flexible M e t a l Conduit a n d F i t t i n g s / C o n n e c t o r s , Pages 8 a n d 2 3 .
ECN No. NA CGI No. CGI-SNF-P-93-2-CI-052
Commercial Grade Item Upgrade Dedication Form
KNI-'-4vl4. Ucv.O ECN No. NA CGI No. CGI-SNF-D-93-2-C1-0S2Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
| Page 4 of 33
Other:
Section 9 Critical Characteristics
Critical Characteristics Verification Acceptance Criteria/Tolerances Acceptance ID
Document A m e r i c a n Electric Method
Purchase O r d e r s
C 1 8 8 R 1 2 T M 3 1 5 7 6 / 1 6 / 9 9 ; C 1 8 8 R 1 2 T M 3 1 5 8 , 6 / 1 6 / 9 9 a n d C 1 8 8 R 1 2 T M 3 1 6 8 , 6 / 1 7 / 9 9 H N F - S D - S N F - S E L - 0 0 2 , R e v . 6 A
Funclion
1. Item Identification Critical Characteristics
T"
M a n u f a c t u r e r , All Rigid Conduit j
1 / 2 " Rigid C o n d u i t 3 / 4 " Rigid C o n d u i t 1 " Rigid Conduit 1 1 / 4 " Rigid Conduit 1 1 / 2 " Rigid C o n d u i t
T h r e a d e d Rigid C o n d u i t Nippies, Page K G
M a n u f a c t u r e r , All Rigid C o n d u i t Nipples
1 / 2 "
3 / 4 "
1 "
1 1 / 2 "
(necessary for reasonable assurance that the Item delivered is the I L T V Steel Tubular Products/Galvite : 1 , IN Verify UL marking on the conduit sample
lot.
Verify Size marking on the conduit sample lot or verify identifying
dimensions on t h e conduit sample lot as f o l l o w s :
Nominal 0 . 6 2 2 " I D s Nominal 0 . 8 2 4 " ID
Nominal 1 . 0 4 9 " ID Nominal 1 . 3 8 0 " ID Nominal 1 . 6 1 0 " ID
| 1 , I N
C o n d u i t Pipe Products
V e r i f y UL marking on t h e sample lot.
V e r i f y Size marking on t h e sample lot or verify identifying dimensions on the sample lot as f o l l o w s :
Nominal 1 / 2 "
Nominal 3 / 4 "
Nominal 1 "
Nominal 1 1 / 2 "
i X
Commercial Grade Item Upgrade Dedication Form
SNT-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1 -052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 5 of 33
T h r e a d e d Rigid Conduit Bushed Nipples, Page 6
M a n u f a c t u r e r , All Rigid C o n d u i t Bushed Nipples
C N - 5 0
C N - 7 5
C N - 1 0 0
C N - 1 2 5
C N - 1 5 0
T h r e a d e d Rigid Conduit, C o n n e c t o r s , Page 5
M a n u f a c t u r e r , All T h r e a d e d Rigid C o n d u i t 3 Piece C o n n e c t o r s
E C - 5 0
E C - 7 5
E C - 1 0 0
E C - 1 2 5
E C - 1 5 0
1 , IN
; x
A p p l e t o n Electric C o m p a n y
Verify UL marking on the sample lot.
Verify part identifying marking on the sample lot or verify identifying
Dimensions on t h e sample lot as f o l l o w s : Nominal 1 / 2 " - " A " D i m e n s i o n , Nominal 7 / 1 6 "
N o m i n a l 3 / 4 " - " A " D i m e n s i o n , Nominal 1 / 2 "
N o m i n a l 1 " - " A " D i m e n s i o n , N o m i n a l 5 / 8 "
Nominal 1 1 / 4 " - " A " D i m e n s i o n , N o m i n a l 1 1 / 1 6 "
Nomina! 1 1 / 2 " - " A " D i m e n s i o n , Nominal 7 / 8 "
A p p l e t o n Electric C o m p a n y
Verify UL marking on the sample lot.
V e r i f y identifying marking on the sample lot or identifying dimensions on the sample lot as f o l l o w s :
N o m i n a l 1 / 2 " - " A " D i m e n s i o n , Nominal 1 7 / 1 6 "
Nominal 3 / 4 " - " A " D i m e n s i o n , Nominal 1 9 / 1 6 "
Nominal 1 " - " A " D i m e n s i o n , Nominal 1 1 1 / 1 6 "
A " D i m e n s i o n , Nominal Nominal 1 1 / 4
2 1 / 8 "
Nominal 1 1 / 2 2 3 / 1 6 "
- " A " D i m e n s i o n , Nominal
1 , I N
Commercial Grade Item Upgrade Dedication Form
SXT-4914. Rev. 0 Title: C O N D U I T F O R S A F E T Y CLASS W I R I N GI'agc 6 of 33
T h r e a d e d Rigid C o n d u i t , R e d u c e r s , Page 7
M a n u f a c t u r e r , A l ! T h r e a d e d Rigid Conduit Reducers
R B 7 5 - 5 0 R B 1 0 0 - 5 0 R B 1 5 0 - 5 0 R B 1 0 0 - 7 5 R B 1 5 0 - 7 5 R B 1 2 5 - 1 0 0 R B 1 5 0 - 1 0 0
Rigid C o n d u i t C o n d u l e t , F o r m 3 5 , Page 6
M a n u f a c t u r e r , All Rigid Conduit C o n d u l e t F o r m 3 5
L B / T / L R / L L - 1 / 2 "
L B / T / L R / L L - 3 / 4 "
L B / T / L R / L L - 1 "
L B / T / L B / L L - 1 1 / 2 "
Rigid C o n d u i t L o c k n u t s , Page 1 0
M a n u f a c t u r e r , All Rigid C o n d u i t Locknuts / Grounding Locknuts
B L - 5 0 / G L - 5 0 B L - 7 5 / G L - 7 5 B L - 1 0 0 / G L - 1 0 0 B L - 1 2 5 / G L - 1 2 5 B L - 1 5 0 / G L - 1 5 0
A p p l e t o n Electric C o m p a n y
Verify UL marking on the sample lot.
Verify identifying marking on the parts in the sample lot or verify identifying dimension on t h e sample lot as f o l l o w s : 3 / 4 " - 1 / 2 "
1 " - 1 / 2 "
1 1 / 2 " - 1 / 2 "
1 " - 3 / 4 "
1 1 / 2 " - 3 / 4 "
1 1 / 4 " - 1 "
1 1 / 2 " - 1 "
A p p l e t o n Electric C o m p a n y
V e r i f y UL marking on the sample lot.
Verify Size marking on the condulet sample lot or verify identifying dimension on t h e condulet sample lot as f o l l o w s : N o m i n a l 1 / 2 "
N o m i n a l 3 / 4 "
N o m i n a l 1 "
N o m i n a l 1 1 / 2 "
A p p l e t o n Electric C o m p a n y
V e r i f y UL marking on t h e sample lot.
V e r i f y Size marking on t h e locknut sample lot or verify identifying dimension on the locknut s a m p l e lot as f o l l o w s : Nominal 1 / 2 "
Nominal 3 / 4 "
Nominal 1 "
Nominal 1 1 / 4 "
Nominal 1 1 / 2 "
1 , IN
1 , IN
1 , IN ECN No. NA CGI No. CGI-SNF-D-93-2-C1 -052
Commercial Grade Item Upgrade Dedication Form
SNT-49I4. Rev. 0Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Pago 7 of 33
Rigid M e t a l C o n d u i t B e a m C l a m p s , Page 4
M a n u f a c t u r e r , Ail Rigid M e t a l C o n d u i t B e a m C l a m p s
B H - 5 0 2 B H - 5 0 3
Liquidtight Flexible Steel C o n d u i t , Page 8
M a n u f a c t u r e r , All Flexible C o n d u i t
T y p e L A - 1 1 T y p e L A - 1 2 T y p e L A - 1 3
T y p e L A - 1 4 T y p e L A - 1 5
Liquidtight Flexible M e t a l C o n d u i t Fittings, Page 2 3 M a n u f a c t u r e r , Flexible C o n d u i t C o n n e c t o r s
5 3 3 2
5 3 3 3
5 3 3 4
5 3 3 5
5 3 3 6
A p p l e t o n Electric C o m p a n y
Verify identifying marking on t h e sample lot or verify identifying dimensions on the sample lot as f o l l o w s :
2" Size, J a w O p e n i n g Nominal 1 5 / 1 6 "
2 1 / 2 " Size, J a w Opening Nominal 1 1 / 1 6 "
T h o m a s & Betts
Verify UL marking on t h e conduit sample lot.
Verify Size marking on t h e conduit sample lot or verify identifying
dimensions on the conduit sample lot as f o l l o w s :
Nominal 1 / 2 " D i a m e t e r Nominal 3 / 4 " D i a m e t e r Nominal 1 " D i a m e t e r Nominal 1 1 / 4 " D i a m e t e r Nominal 1 1 / 2 " D i a m e t e r
1 , IN
T h o m a s and Betts
Verify UL marking on the sample lot.
Verify identifying marking on the sample lot or verify identifying dimensions on the sample lot as f o l l o w s :
Nominal 1 / 2 " - " A " D i m e n s i o n , Nominal 1 3 / 8 "
Nomina! 3 / 4 " - " A " D i m e n s i o n , Nominal 1 2 1 / 3 2 "
Nominal 1 " - " A " D i m e n s i o n , Nominal 1 7 / 8 "
Nominal 1 1 / 4 " - " A " D i m e n s i o n , Nomina) 2 9 / 3 2 "
Nominal 1 1 / 2 " - " A " D i m e n s i o n , Nominal 2 2 3 / 3 2 "
1 , IN
1 , I N ECN No. NA . CGI No. CGI-SNF-D-93-2-C1-052
Commercial Grade Item Upgrade Dedication Form
SNF-4914. Rev. 0 ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
I'agc if of 33
M e t a l Framing C h a n n e l s / P i p e 1 , IN
i
X |S t r a p s , Pages 7 and 3 9 ; [
M a n u f a c t u r e r , A l l Framing S u p e r s t r u t
I
C h a n n e l s / P i p e S t r a p s
S u p e r s t r u t
Half S l o t Channel A - 1 2 0 0 - H S
N o m i n a l 1 5 / 8 " x 1 5 / 8 " , 1 2 g a g e .
i
7 0 2 Pipe S t r a p s
Verify identifying marking on the sample
7 0 2 Pipe S t r a p s lot or verify identifying dimensions on the !
sample lot as f o l l o w s : !
7 0 2 - 1 / 2 Pipe O D Nominal 0 . 8 4 0 " 1 4 gage i
7 0 2 - 3 / 4 Pipe O D Nominal 1 . 0 5 0 " 1 4 gage
7 0 2 - 1 Pipe O D Nominal 1 . 3 1 5 " 1 4 gage
7 0 2 - 1 1 / 4 Pipe O D Nominal 1 . 6 6 0 " 1 4 gage i
7 0 2 - 1 1 / 2 Pipe O D Nominal 1 . 9 0 0 " 1 4 gage
j
Fender W a s h e r , Page 2 - 1 , A B C Fasteners 1 , I N
: x j
M a n u f a c t u r e r
2 0 0 0 4 1 / 4 " x 1 1 / 4 "
2 0 0 0 8 3 / 8 " x 1 1 / 2 "
2 0 0 1 5 1 / 2 " x 2 "
1
Fasteners, Pages 4 0 and 4 2 1 , IN X
M a n u f a c t u r e r P o w e r s t r u t PS 1 4 6 C o n t i n u o u s N o m i n a l 3 / 8 "
T h r e a d e d Rod N o m i n a l 1 / 2 "
N o m i n a ! 5 / 8 "
Nominal 3 / 4 "
PS R S C l a m p i n g N u t w i t h ]
Regular S p r i n g . j
PS RS 1/4" x 2 0 i
3 / 8 " x 1 6 1 / 2 " x 1 3
5 / 8 " x 1 1
i
3 / 4 " x 1 0 !
7 / 8 " x 9 i. - .: L .
i
2. Physical Critical Characteristics (for reasonable assurance that the Item delivered is the Item specified)
All Size Rigid C o n d u i t , M a t e r i a l Steel (Note 3 ) 1 , IN
x
1 , T
All Size Rigid C o n d u i t Nipples, Steel (Note 3 ) 1 , IN X
Material 1 , T
All Size T h r e a d e d Rigid Conduit Steel ( N o t e 3 ) 1 . IN i X I
Bushed Nipples, M a t e r i a l 1 , T
' i
Commercial Grade Item Upgrade Dedication Form
SNf:-4'J14. Rev. 0 ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052Title: C O N D U I T F O R S A F E T Y C L A S S W I R I N G
Page 9 of 33
T h r e a d e d Rigid Conduit, T h r e e Piece C o n n e c t o r s , Material
Steel ( N o t e 3 ) 1 , IN
1 , T X
T h r e a d e d Rigid C o n d u i t , R e d u c e r s , M a t e r i a l
Steel ( N o t e 3) 1 , I N
1 . T X
Rigid C o n d u i t C o n d u i e t Form 3 5 , Material
Steel (Note 3 ) M , IN 1 , T
X
Rigid C o n d u i t ,
L o c k n u t s / G r o u n d i n g L o c k n u t s , M a t e r i a l
Steel ( N o t e 3 ) 1, IN j X 1, T
:
I !
Rigid M e t a l C o n d u i t , B e a m C l a m p s , M a t e r i a l
Steel (Note 3} 1 , I N X
i 1 . T |
All Size Liquidtight Flexible Steel C o n d u i t , J a c k e t i n g M a t e r i a l
Flexible P V C C o m p o u n d ( N o t e 3 ) I 1 , IN j x [
M, T i |
I Flexible Steel C o n d u i t ,
C o n n e c t o r s , M a t e r i a l
Steel ( N o t e 3 ) j 1 , IN j X 1 , T
Framing C h a n n e l , M a t e r i a l Steel ( N o t e 3 ) 1 , IN X
1 , T Framing Channel 7 0 2 Pipe
S t r a p s , Material
Steel (Note 3) : 1 , IN X
: 1 , T
Fender W a s h e r , M a t e r i a l Zinc C o a t e d Steel (Note 3 ) i 1 , IN X
! 1 . T F a s t e n e r s ,
PS 1 4 6 C o n t i n u o u s T h r e a d e d R o d .
PS RS C l a m p i n g N u t w i t h Regular S p r i n g .
1 , IN • X
Steel ( N o t e 3 ) ! ^ T j
I
ISteel (Note 3}
' !
3. Performance Critical Characteristics (for
•• — '. i — ' — ! I j !
reasonable assurance that the Item will perform its intended safety function(s))
Environmental N o t e 1 ! i !
Seismic Condition C N o t e 2 1 , T
i 1 , A
X
j
Commercial Grade Item Upgrade Dedication Form
ECN No. NA CGI No. CGI-SNF-D-93-2-CI-052
SNi;-4'>14. Rev. 0
Title: C O N D U I T F O R S A F E T Y C L A S S W I R I N G
Page I0 ol" 33
4. Notes and Legend:
1 . T h e c o m p o n e n t s are n o t subject to degradation f r o m t h e 4 0 ° F or 6 0 % RH o r 1 1 5 ° F and 2 2 % RH conditions and are suitable for Environmental Condition B application.
2 . M a i n t a i n critical f u n c t i o n b e f o r e , during, and after Seismic e v e n t . E q u i p m e n t t h a t has been shaker-table t e s t e d should n o t be installed in a plant {Ref. IEEE S t a n d a r d 3 4 4 - 1 9 8 4 , Section 7 ) . C o n s e q u e n t l y , the seismic t e s t constitutes a destructive t e s t . Seismic Design m a y be verified by analyis of t h e installed conduit s y s t e m .
3 . M a t e r i a l verification a c c e p t a n c e m e t h o d m a y be by either inspection or t e s t .
I Acceptance Method:
J 1. Special Test and Inspection 1, IN for Inspection
; 1 J for Test
| 1,A for Acceptance by Analysis
| 2. Commercial Grade Survey
| 3. Source Verification i 4. Vendor/Item History
Section 10 initial. Review :and Approval Approvals:
Designated Engineer:
Design Authority:
QA Engineer:
Commercial Grade Item Upgrade Dedication Form
SNT-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 11 of 33
WORKSHEET 1
DETERMINATION OF FAILURE MECHANISMS/MODES Section 1
Typical Failure Definition Applicable to Component i
Mechanisms under Evaluation
Fracture Separation of a solid accompanied by little or no Yes[X ] No [ ]; If Yes, indicate failure macroscopic plastic deformation. Mode: Fracture or material fatiaue-loss of
structural protection to wiring
Corrosion The gradual deterioration of a material due to Yes[ ] No [ X j ; If Yes, indicate failure chemical or electrochemical reactions, such as Mode
oxidation, between the material and its environment.
Erosion Destruction of materials by the abrasive action of Yes[ ] No [ X j; If Yes, indicate failure ! moving fluids, usually accelerated by the presence Mode
of solid particles carried with the fluid.
Open Circuit An electrical circuit that is unintentionally broken so Yes( ] No [ X j; If Yes, indicate failure that there is no complete path for current flow. Mode
Short Circuit An abnormal connection by which an electrical Yes( ] No [ X J; If Yes, indicate failure current is connected to ground, or to some Mode
conducting body, resulting in excessive current flow.
Blockage Clogging of a filtering medium resulting in the Yes[ ] No [ X ]; If Yes, indicate failure | inability to perform its purification function or Mode
blockage of flow.
Seizure Binding of a normally moving item through excessive Yes[ ] No [ X ]; If Yes, indicate failure ; pressure, temperature, friction, jamming. Mode
Unacceptable Mechanical oscillations produced are beyond the Yes[ ] No [ X ]; If Yes, indicate failure Vibration defined permissible limits due to unbalancing, poor Mode
support, or rotation at critical speeds.
Loss of Properties A loss of mechanical and physical properties of a Yes[ ] No [ X ]; If Yes, indicate failure material due to exposure to high temperatures, Mode
radiation exposure.
Excess Strain Under the action of excessive external forces the Yes[X ] No [ ]; If Yes, indicate failure material of the part has been deformed or distorted. Mode; Material fatiaue leads to loss of
structural support and enclosure of wirina Mechanical Creep From prolonged exposure to high temperature and Yes I ] No [ X ]; If Yes, indicate failure
stress, the object will show a slow change in its Mode physical (shape and dimension) and mechanical
characteristics.
Ductile Fracture Fracture characterized by tearing of metal YesjX ] No ( ]; If Yes, indicate failure accompanied by appreciable gross plastic Mode: Fracture or material fatiaue - loss of deformation. structural support and protection of wiring : Section 2 Additional Failure Modes Applicable to the Component Under Evaluation
1.
2.
3.
4.
Commercial Grade Item Upgrade Dedication Form
SXT-4914. Rev. 0 ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052Title: C O N D U I T F O R S A F E T Y C L A S S W I R I N G
Tage 12 of 33
C H E C K L I S T I A C C E P T A N C E M E T H O D 1
S P E C I A L T E S T / I N S P E C T I O N V E R I F I C A T I O N
lllllllllllllilll^;;;::'
SECTION 1Item Description: Rigid conduit, nipples, sealtight flex c o n n e c t o r s , c o n d u l e t s , struts and s t r a p s , f e n d e r w a s h e r s , l o c k n u t s , grounding l o c k n u t s , spring n u t s , flexible m e t a l c o n d u i t / c o n n e c t o r s .
System #: 9 3 - 2
Equip #: N A
Procurement and/or Mode! #: S e e C a t a l o g N u m b e r s in S e c t i o n 8 a n d Characteristics in S e c t i o n 9 .
Manufacturer (Address/Phone):
V a r i o u s - S e e S e c t i o n s 8 and 9 .
P.O. #
Supplier (Addrcss/Phonc):
SECTION 2 CRITICAL CHARACTERISTICS TO BE VERIFIED BY METHOD 1.
Insp Test Post- Test
[ X ] [ 1
1 1
1. Description and characteristics for identification. (See 1 2 items listed b e l o w under inspection.
[ X ] [ X ]
[ 1
2. Material verification for identification. (See 1 2 items b e l o w under inspection)
[ 1 [ X ]
I ]
3, Seismic Condition C (Seismic verification m a y be by t e s t or by analysis) [ ] ( 1 [ ] 4.[ ] [ ] [ ] 5.
[ ] ( 1 [ 1 6.
I
1 [ ] [ ] 7.I I
f ]I ]
8.SECTION 3 VERIFIED BY INSPECTION
* See Attachment H of Desk Instruction for Sampling Size: Reduced Sampling Plan W a s S e l e c t e d D u e t o T h e Product History a n d Simplicity of Product
Characteristic: M a n u f a c t u r e r , All Rigid Conduit Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: L T V STEEL T U B U L A R P R O D U C T S / G A L V I T E As Found: Passed: Y / N (Circle)
Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
SN1--4914, Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 13 of 33
Characteristic: All Rigid C o n d u i t
Sample Size*: R E D U C E D S A M P L I N G PLAN
Size / Acceptance Criteria: V e r i f y UL marking on the conduit sample lot.
V e r i f y Size marking on t h e conduit sample lot or verify identifying dimensions on the conduit sample lot as f o l l o w s :
1 / 2 " / N o m i n a l 0 . 6 2 2 ID 3 / 4 " / N o m i n a l 0 . 8 2 4 I D 1 " / Nominal 1 . 0 4 9 ID 1 1 / 4 " / N o m i n a l 1 . 3 8 0 ID 1 1 / 2 " / N o m i n a l 1 . 6 1 0 ID
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: T h r e a d e d Rigid Conduit Nippies, M a n u f a c t u r e r Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: C o n d u i t Pipe Products As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: T h r e a d e d Rigid Conduit Nippies Sample Size*: R E D U C E D S A M P L I N G PLAN
Size / Acceptance Criteria: Verify UL marking on the sample lot.
V e r i f y Size marking on t h e sample lot or verify identifying dimensions on the sample lot as f o l l o w s : 1 / 2 " / Nominal 1 / 2 "
3 / 4 " / Nominal 3 / 4 "
1 " / N o m i n a l 1 "
1 1 / 2 " / N o m i n a l 1 1 / 2 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
SNl-'-4914, Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 14 of 33
Characteristic: T h r e a d e d Rigid C o n d u i t Bushed Nippies, M a n u f a c t u r e r Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: T h r e a d e d Rigid Conduit Bushed Nipples Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number / Acceptance Criteria: Verify UL marking on t h e sample lot.
V e r i f y part identifying m a r k i n g on t h e s a m p l e lot or verify identifying Dimensions on the sample lot as f o l l o w s :
C N - 5 0 / N o m i n a l 1/2"; " A " D i m e n s i o n , Nominal 7 / 1 6 "
C N- 7 5 / N o m i n a l 3 / 4 " ; " A " D i m e n s i o n , N o m i n a l 1/2"
C N- 1 0 0 / N o m i n a l 1 " ; " A " D i m e n s i o n , Nominal 5 / 8 "
C N- 1 2 5 / N o m i n a l 1 1/4"; " A " D i m e n s i o n , Nominal 1 1 / 1 6 "
C N- 1 5 0 / N o m i n a ! 1 1/2"; " A " D i m e n s i o n , Nominal 7 / 8 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic; M a n u f a c t u r e r , T h r e a d e d Rigid Conduit 3 Piece C o n n e c t o r s Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
SNF-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-0S2
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 15 of 33
Characteristic: All T h r e a d e d Rigid Conduit 3 Piece C o n n e c t o r s Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: Verify UL marking on t h e sample lot.
V e r i f y identifying marking on t h e sample lot or identifying dimensions on t h e sample lot as f o l l o w s : E C - 5 0 / N o m i n a l 1 / 2 " ; "A" D i m e n s i o n , Nominal 1 7 / 1 6 "
E C - 7 5 / N o m i n a l 3 / 4 " ; " A " D i m e n s i o n , N o m i n a l 1 9 / 1 6 "
E C - 1 0 0 / N o m i n a l 1 " ; " A " D i m e n s i o n , N o m i n a l 1 1 1 / 1 6 "
E C - 1 2 5 / N o m i n a l 1 1 / 4 " ; " A " D i m e n s i o n , N o m i n a l 2 1 / 8 "
E C - 1 5 0 / N o m i n a l 1 1 / 2 " ; " A " Dimension,. Nominal 2 3 / 1 6 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , T h r e a d e d Rigid Conduit Reducers Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: All T h r e a d e d Rigid Conduit Reducers Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: Verify UL marking on t h e sample lot.
V e r i f y identifying marking on t h e parts in t h e sample lot or verify identifying dimensions on t h e sample lot as f o l l o w s :
R B 7 5 - 5 0 / 3 / 4 " - 1 / 2 "
R B 1 0 0 - 5 0 / 1 " - 1 / 2 "
R B 1 5 0 - 5 0 / 1 1 / 2 " - 1 / 2 "
RB 1 0 0 - 7 5 / 1 " - 3 / 4 "
R B I 5 0 - 7 5 / 1 1 / 2 " - 3 / 4 "
R B 1 2 5 - 1 0 0 / 1 1 / 4 " - 1 "
R B 1 5 0 - 1 0 0 / 1 1 / 2 " - 1 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
Commercial Grade Item Upgrade Dedication Form
SN1--4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page l(i of 33
Characteristic: M a n u f a c t u r e r , Ail Rigid Conduit Condulet Form 3 5 Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: A l l Rigid C o n d u i t Condufet Form 3 5 Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: V e r i f y UL marking on t h e sample lot.
V e r i f y Size marking on t h e condulet sample lot or verify identifying dimensions on t h e c o n d u l e t sample lot as f o l l o w s :
L B / T / L R / L L - 1 1 2 " I Nominal 1 / 2 "
L B / T / L R / L L - 3 / 4 " / N o m i n a ! 3 / 4 "
L B / T / L R / L L - 1 " / Nominal 1 "
L B / T / L R / L L - 1 1 / 2 " / N o m i n a l 1 1 / 2 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , All Rigid Conduit Locknuts A n d Grounding Locknuts Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
SNI--4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
I'age 17 of 33
- - -
Characteristic: All Rigid C o n d u i t L o c k n u t s A n d G r o u n d i n g L o c k n u t s Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: Verify UL marking on t h e s a m p l e lot.
Verify Size m a r k i n g on t h e l o c k n u t s a m p l e lot or verify identifying d i m e n s i o n s on t h e l o c k n u t s a m p l e lot a s f o l l o w s :
B L - 5 0 , G L - 5 0 / Nominal 1 / 2 "
B L - 7 5 , G L - 7 5 / N o m i n a l 3 / 4 "
B L - 1 0 0 , G L - 1 0 0 / Nominal 1 "
B L - 1 2 5 , G L - 1 2 5 / Nominal 1 1 / 4 "
B L - 1 5 0 , G L - 1 5 0 / Nominal 1 1 / 2 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , Rigid C o n d u i t Beam C l a m p s Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: A p p l e t o n Electric C o m p a n y As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: Alt Rigid C o n d u i t B e a m C l a m p s Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: Verify identifying m a r k i n g on t h e s a m p l e lot or verify identifying d i m e n s i o n s on t h e s a m p l e lot a s f o l l o w s :
B H- 5 0 2 / 2 " Size; J a w O p e n i n g Nominal 1 5 / 1 6 "
B H- 5 0 3 / 2 1 / 2 " Size; J a w O p e n i n g Nominal 1 1 / 1 6 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , Liquidtight Flexible S t e e l C o n d u i t . Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: T h o m a s & B e t t s
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
Commercial Grade Item Upgrade Dedication Form
SNF-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 18 of 33
Characteristic: All Flexible Steel Conduit Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: V e r i f y UL marking on the conduit sample lot.
V e r i f y Size marking on t h e conduit sample lot or verify identifying dimensions on t h e conduit sample lot as f o l l o w s :
T y p e L A - 1 1 / N o m i n a l 1 / 2 " D i a m e t e r T y p e L A - 1 2 / Nominal 3 / 4 " D i a m e t e r T y p e L A - 1 3 / N o m i n a l 1 " D i a m e t e r T y p e L A - 1 4 / N o m i n a ! 1 1 / 4 " D i a m e t e r T y p e L A - 1 5 / N o m i n a l 1 1 / 2 " D i a m e t e r As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , Flexible M e t a l C o n d u i t C o n n e c t o r s Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: T h o m a s and Betts
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: All Flexible M e t a l Conduit C o n n e c t o r s Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: V e r i f y UL marking on t h e sample lot.
V e r i f y identifying marking on t h e sample lot or verify identifying dimensions on t h e sample lot as f o l l o w s :
5 3 3 2 / Nominal 1 / 2 " - " A " D i m e n s i o n , Nominal 1 3 / 8 "
5 3 3 3 / Nominal 3 / 4 " - " A " D i m e n s i o n , N o m i n a ! 1 2 1 / 3 2 "
5 3 3 4 / N o m i n a l 1 " - " A " D i m e n s i o n , N o m i n a l 1 7 / 8 "
5 3 3 5 / N o m i n a l 1 1 / 4 " - " A " D i m e n s i o n , N o m i n a l 2 9 / 3 2 "
5 3 3 6 / N o m i n a l 1 1 / 2 " - " A " D i m e n s i o n , N o m i n a l 2 2 3 / 3 2 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , Framing Channels/Pipe Straps Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: Superstrut
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
SNK-4914. Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052 Page 19 of 33 Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Characteristic: All Framing C h a n n e l s / Pipe S t r a p s Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: Half Slot C h a n n e l , A - 1 2 0 0 - H S / Nominal 1 5 / 8 " x 1 5 / 8 " ; 1 2 g a g e . 7 0 2 S e r i e s Pipe S t r a p s : Verify identifying m a r k i n g on t h e s a m p l e lot or verify identifying d i m e n s i o n s on t h e s a m p l e lot a s f o l l o w s :
7 0 2 - 1 / 2 / Pipe OD Nominal 0 . 8 4 0 " , 1 4 g a g e 7 0 2 - 3 / 4 / Pipe OD Nominal 1 . 0 5 0 " , 1 4 g a g e 7 0 2 - 1 / Pipe OD Nomina! 1 . 3 1 5 " , 1 4 g a g e 7 0 2 - 1 1 / 4 / P i p e OD Nominal 1 . 6 6 0 " , 1 4 g a g e 7 0 2 - 1 1/2 / Pipe OD Nominal 1 . 9 0 0 " , 1 4 g a g e As Found: Passed: Y / N (Circle)
Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , F e n d e r W a s h e r s Sample Size*: R E D U C E D S A M P L I N G PLAN Acceptance Criteria: ABC F a s t e n e r s
As Found: Passed: Y / N (Circle)
Receipt Inspection Plan / Report #: :
References (see Section 8):
Characteristic: F e n d e r W a s h e r s
Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: 2 0 0 0 4 / 1/4" x 1 1/4"
2 0 0 0 8 / 3 / 8 " x 1 1/2"
2 0 0 1 5 / 1/2" x 2 "
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a n u f a c t u r e r , F a s t e n e r s Sample Size*: R E D U C E D S A M P L I N G PLAN Acceptance Criteria: P o w e r s t r u t
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
Commercial Grade Item Upgrade Dedication Form
SNT-4914, Rev. 0E C N N o . NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 20 of 33
Characteristic: Fasteners
Sample Size*: R E D U C E D S A M P L I N G PLAN
ID Number/Acceptance Criteria: PS 1 4 6 C o n t i n u o u s T h r e a d e d Rod / Nominal 3 / 8 "
/ N o m i n a l 1 / 2 "
/ N o m i n a l 5 / 8 "
/ Nominal 3 / 4 "
PS RS Clamping N u t w i t h Regular Spring / 1 / 4 " x 2 0 / 3 / 8 " x 1 6 / 1 / 2 " x 1 3 / 5 / 8 " x 1 1 / 3 / 4 " x 1 0 / 7 / 8 " x 9 As Found: Passed: Y / N (Circle)
Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: M a t e r i a l Identification, Alt Items ( 1 1 items f r o m S e c t i o n 9 - 2 ) Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: Steel
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 7):
Characteristic: M a t e r i a l Identification, Flexible Steel Conduit J a c k e t Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: Flexible P V C C o m p o u n d As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Characteristic: Material Identification, Fender W a s h e r s Sample Size*: R E D U C E D S A M P L I N G PLAN
Acceptance Criteria: Zinc C o a t e d Steel
As Found: Passed: Y / N (Circle) Receipt Inspection Plan / Report #:
References (see Section 8):
Commercial Grade Item Upgrade Dedication Form
ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
SNI:-4914, Rev. 0
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 21 of 33
SECTION 4 VERIFIED BY SPECIAL TEST .
* See Attachment H of Desk Instruction for Sampiing Size Test To Be Performed by:
[ ] Purchaser
[ ] Supplier/Manufacturer**
[ ] Other
Number of Items to be Tested: Reduced Sampling Plan W a s S e l e c t e d D u e T o T h e Product History and Simplicity O f Product
Test/Inspection Location:
Characteristic for Test: Seismic Condition C - All Items { 1 3 items f r o m Section 9 - 2 ) Acceptance Criteria: M a i n t a i n Critical Function Before, D u r i n g , and A f t e r Seismic E v e n t .
Sample Size*: S a m p l e Size is N A because seismic verification of t h e installed conduit s y s t e m w i t h f i t t i n g s , s u p p o r t s , e t c , will be d o n e by analysis. Physical testing is n o t a n t i c i p a t e d .
Actual Test Value:
Test Plan and Report #: References (sec Section 8):
Characteristic for Test:
Acceptance Criteria:
Sample Size*: R E D U C E D S A M P L I N G PLAN Actual Test Value:
Test Plan and Report #: References (sec Section 8):
Characteristic for Test:
Acceptance Criteria:
Sample Size*. R E D U C E D S A M P L I N G PLAN Actual Test Value:
Test Plan and Report #: References (sec Section 8):
** If Supplier/Manufacturer or Other. Refer to Ctrl Cheekhsi-2 for Support Information
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0 ECN No. N A CGI No. C G I - S N F - D - 9 3 - 2 - C 1 - 0 5 2Title: C O N D U I T F O R S A F E T Y C L A S S W I R I N G
Page 22 o f 33
• Section 5 Test/ inspection Sunrtmaiy (Acceptance Method 1) ' .- 1. S U M M A R Y O F V E R I F I E D C R I T I C A L C H A R A C T E R I S T I C S , T H E I R V E R I F I C A T I O N M E T H O D S , A N D R E S U L T S I T E M D E S C R I P T I O N :
Critical Characteristics Verification Results
Critical Characteristics Acceptance CritenaTole ranees ID Function Method T/IN
Procedure or RR<*
Check- list !D
Number Tested
Number Failed
Verifying Organization
Printed Name Signature Date
M a n u f a c t u r e r , All Rigid C o n d u i t
1 / 2 " Rigid Conduit 3 / 4 " Rigid Conduit 1 " Rigid Conduit 1 1/4" Rigid Conduit 1 1 / 2 " Rigid Conduit
L T V Steel Tubular Products/Galvite Verify UL marking on the conduit sample lot.
Verify Size marking on the conduit sample lot or verify identifying dimensions on t h e c o n d u i t sample lot a s f o l l o w s :
Nominal 0 . 6 2 2 " ID Nominal 0 . 8 2 4 " ID N o m i n a l 1 . 0 4 9 " ID Nominal 1 . 3 8 0 " ID Nominal 1 . 6 1 0 " ID
X IN
M a n u f a c t u r e r , All Rigid Conduit Nipples
1/2"
3 / 4 "
1 "
1 1 / 2 "
C o n d u i t Pipe Products
Verify UL marking on the sample lot.
Verify Size marking on t h e sample lot or verify identifying dimensions on the sample lot a s f o l l o w s :
Nominal 1 / 2 "
Nominal 3 / 4 "
N o m i n a ! 1 "
N o m i n a l 1 1 / 2 "
X IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0E C N No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R SAFETY CLASS W I R I N G
Page 23 of 33
M a n u f a c t u r e r , All Rigid Conduit Bushed Nipples
C N - 5 0
C N - 7 5
C N - 1 0 0
C N - 1 2 5
C N - 1 5 0
A p p l e t o n Electric C o m p a n y
Verify UL marking on the sample lot. Verify part identifying marking on t h e sample lot or verify identifying Dimensions on t h e sample lot as f o l l o w s : N o m i n a ! 1 / 2 " - " A "
D i m e n s i o n , Nominal 7 / 1 6 "
Nominal 3 / 4 " - " A "
D i m e n s i o n , Nominal 1 / 2 "
Nominal 1 " - " A "
D i m e n s i o n , Nominal 5 / 8 "
Nominal 1 1 / 4 " - " A "
Dimension, Nominal 1 1 / 1 6 "
Nominal 1 1 / 2 " - " A "
D i m e n s i o n , Nominal 7 / 8 "
X IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev.OE C N No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R SAFETY CLASS W I R I N G
Page 24 o f 33
M a n u f a c t u r e r , All T h r e a d e d Rigid Conduit 3 Piece C o n n e c t o r s
E C - 5 0
E C - 7 5
E C - 1 0 0
E C - 1 2 5
E C - 1 5 0
A p p l e t o n Electric C o m p a n y
Verify UL marking on t h e sample lot.
Verify identifying marking on the sample lot or identifying dimensions on t h e sample lot as f o l l o w s : Nominal 1 / 2 " - " A "
D i m e n s i o n , Nominal 1 7 / 1 6 "
Nominal 3 / 4 " - " A "
D i m e n s i o n , Nominal 1 9 / 1 6 "
Nominal 1 " - " A "
D i m e n s i o n , Nominal 1 1 1 / 1 6 "
Nominal 1 1 / 4 " - " A "
D i m e n s i o n , Nominal 2 1 / 8 "
Nominal 1 1 / 2 " - " A "
D i m e n s i o n , Nominal 2 3 / 1 6 "
IN
Commercial Grade Item Upgrade Dedication Form
SNF-49I4, Rev. 0 E C N N O NA C G I No. CGI-SNF-D-93-2-C1-052Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 25 of 33
M a n u f a c t u r e r , All T h r e a d e d Rigid Conduit Reducers
R B 7 5 - 5 0 R B 1 0 0 - 5 0 R B 1 5 0 - 5 0 R B 1 0 0 - 7 5 R B 1 5 0 - 7 5 R B 1 2 5 - 1 0 0 R B 1 5 0 - 1 0 0 M a n u f a c t u r e r , Rigid M e t a l Conduit Condulet Form 3 5
LB/T/LR/LL-112"
L B / T / L R / L L - 3 / 4 "
L B / T / L R / L L - 1 "
LB/T/LR/LL-1 1/2"
A p p l e t o n Electric C o m p a n y
V e r i f y U L marking o n t h e sample lot. Verify identifying marking on the parts in the sample lot or verify identifying dimensions on the sample lot as f o l l o w s : 3 / 4 " - 112"
1 " - 1 / 2 "
1 1 / 2 " - 1/2"
1 " - 3 / 4 "
1 1 / 2 " - 3 / 4 "
1 114" - 1 "
1 1 / 2 " - 1 "
A p p l e t o n Electric C o m p a n y
V e r i f y U L marking on the s a m p l e lot.
V e r i f y Size marking on the c o n d u l e t sample lot or verify identifying dimensions on the c o n d u i e t sample lot as f o l l o w s :
Nominal 1 / 2 "
Nominal 3 / 4 "
Nominal 1 "
Nominal 1 1 / 2 "
IN
IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R SAFETY CLASS W I R I N G
Page 26 of 33
M a n u f a c t u r e r , All Rigid Conduit Locknuts / Grounding Locknuts
B L - 5 0 , G L - 5 0 B L - 7 5 , G L - 7 5 B L - 1 0 0 , G L - 1 0 0 B L - 1 2 5 , G L - 1 2 5 B L - 1 5 0 , G L - 1 5 0
A p p l e t o n Electric C o m p a n y
V e r i f y UL marking on t h e sample lot.
Verify Size marking on the l o c k n u t sample lot or verify identifying dimensions on the locknut sample lot as f o l l o w s :
Nominal 1/2"
Nominal 3 / 4 "
Nominal 1 "
Nominal 1 1 / 4 "
Nominal 1 1 / 2 "
X IN
M a n u f a c t u r e r , Rigid M e t a l Conduit Beam Clamps
B H - 5 0 2
B H - 5 0 3
A p p l e t o n Electric C o m p a n y
Verify identifying marking on the sample lot or verify identifying dimensions on the sample lot as f o l l o w s : 2 " Size, J a w Opening Nominal 1 5 / 1 6 "
2 1 / 2 " Size, J a w Opening Nominal 1 1 / 1 6 "
X IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0 ECN No. NA CGi No. CGI-SNF-D-93-2-C1-052Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 27 of 33
M a n u f a c t u r e r , All Flexible S t e e l C o n d u i t
T y p e L A - 1 1 T y p e L A - 1 2 T y p e L A - 1 3 T y p e L A - 1 4
T y p e L A - 1 5
T h o m a s & Betts
Verify UL marking on the conduit sample l o t . Verify Size marking o n the conduit sample lot or verify identifying dimensions on t h e conduit sample lot as f o l l o w s :
Nominal 1 / 2 " Diameter Nominal 3 / 4 " Diameter Nominal 1 " D i a m e t e r Nominal 1 1 / 4 "
Diameter
Nominal 1 1 / 2 "
Diameter
IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 28 of 33
M a n u f a c t u r e r , Flexible M e t a l C o n d u i t
C o n n e c t o r s
5 3 3 2
5 3 3 3
5 3 3 4
5 3 3 5
5 3 3 6
T h o m a s a n d B e t t s
V e r i f y U L marking on the sample lot.
Verify identifying marking on t h e sample lot or verify identifying dimensions on the sample lot as f o l l o w s : Nominal 1 / 2 " - " A " • D i m e n s i o n , Nominal 1 3 / 8 "
Nominal 3 / 4 " - " A "
D i m e n s i o n , Nominal 1 2 1 / 3 2 "
Nominal 1 " - " A "
D i m e n s i o n , Nominal 1 7 / 8 "
Nominal 1 1 / 4 " - " A "
D i m e n s i o n , Nominal 2 9 / 3 2 "
Nominal 1 1 / 2 " - " A "
D i m e n s i o n , Nominal 2 2 3 / 3 2 "
IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0E C N No. NA C G I No. CGI-SNF-D-93-2-C1-052
Title: C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 29 of 33
M a n u f a c t u r e r , Framing C h a n n e l s / P i p e Straps
Half Slot Channel A - 1 2 0 0 - H S
7 0 2 Pipe Straps
7 0 2 - 1 / 2
7 0 2 - 3 / 4
7 0 2 - 1
7 0 2 - 1 1/4
7 0 2 - 1 1/2
Superstrut
Nominal 1 5 / 8 " x 1 5 / 8 " , 1 2 g a g e .
Verify identifying marking on the sample lot or verify identifying dimensions on the sample lot as f o l l o w s : Pipe O D Nominal 0 . 8 4 0 " , 1 4 gage Pipe O D Nominal 1 . 0 5 0 " , 1 4 gage Pipe O D Nominal 1 . 3 1 5 " , 1 4 gage Pipe O D Nominal 1 . 6 6 0 " , 1 4 gage Pipe O D Nominal 1 . 9 0 0 " , 1 4 gage
X IN
M a n u f a c t u r e r , Fender W a s h e r
2 0 0 0 4 2 0 0 0 8 2 0 0 1 5
A B C Fasteners
1 / 4 " x 1 1 / 4 "
3 / 8 " x 1 1 / 2 "
1 / 2 " x 2 "
x IN
Commercial Grade Item Upgrade Dedication Form
SNF-4914, Rev. 0ECN No. NA CGI No. CGI-SNF-D-93-2-C1-052
Title C O N D U I T F O R S A F E T Y CLASS W I R I N G
Page 3 0 of 33
M a n u f a c t u r e r , Fasteners
PS 1 4 6 Continuous T h r e a d e d Rod
PS RS Clamping N u t w i t h Regular Spring.
PS RS
P o w e r s t r u t
Nominal 3 / 8 " ' Nominal 1 / 2 "
Nominal 5 / 8 "
Nominal 3 / 4 "
1 / 4 " x 2 0 3 / 8 " x 1 6 1 / 2 " x 1 3 5 / 8 " x 1 1 3 / 4 " x 1 0 7 / 8 " x 9
X IN
M a t e r i a l Identification:
All Size Rigid M e t a l C o n d u i t ,
Steel
X I N , T
T h r e a d e d Rigid M e t a l C o n d u i t , Nipples
Steel X IN, T
T h r e a d e d Rigid M e t a l C o n d u i t , Bushed Nipples
Steel X IN, T
T h r e a d e d Rigid M e t a l C o n d u i t , 3 Piece C o n n e c t o r s
Steel X IN, T
T h r e a d e d Rigid M e t a l C o n d u i t , Reducers
Steel X IN, T
T h r e a d e d Rigid M e t a l C o n d u i t , C o n d u l e t Form 3 5
Steel X I N , T
Rigid M e t a l Conduit, Locknuts/Grounding
Steel X I N , T