• Aucun résultat trouvé

In-situ performance of displacement ventilation system in Canadian schools with radiant heating systems

N/A
N/A
Protected

Academic year: 2021

Partager "In-situ performance of displacement ventilation system in Canadian schools with radiant heating systems"

Copied!
14
0
0

Texte intégral

(1)

Publisher’s version / Version de l'éditeur:

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la

première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

2011 ASHRAE Annual Conference: 26 June 2011, Montreal, Quebec

[Proceedings], pp. 1-13, 2011-06-26

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE. https://nrc-publications.canada.ca/eng/copyright

NRC Publications Archive Record / Notice des Archives des publications du CNRC : https://nrc-publications.canada.ca/eng/view/object/?id=0cc75aa8-49d4-4280-87a4-136300fcb171 https://publications-cnrc.canada.ca/fra/voir/objet/?id=0cc75aa8-49d4-4280-87a4-136300fcb171

NRC Publications Archive

Archives des publications du CNRC

This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

In-situ performance of displacement ventilation system in Canadian

schools with radiant heating systems

(2)

I n-sit u pe rform a nc e of displa c e m e nt ve nt ila t ion syst e m in Ca na dia n

sc hools w it h ra dia nt he a t ing syst e m s

N R C C - 5 4 4 6 4

O u a z i a , B . ; T a r d i f , M . ; M a c d o n a l d , I . A . ;

T h o m p s o n , A . ; B o o t h , D . G .

J u n e 2 0 1 1

A version of this document is published in / Une version de ce document se trouve dans:

2011 ASHRAE Annual Conference, Montreal, Quebec, June 26-29, 2011, pp.

1-13

http://www.nrc-cnrc.gc.ca/irc

The material in this document is covered by the provisions of the Copyright Act, by Canadian laws, policies, regulations and international agreements. Such provisions serve to identify the information source and, in specific instances, to prohibit reproduction of materials without written permission. For more information visit http://laws.justice.gc.ca/en/showtdm/cs/C-42

Les renseignements dans ce document sont protégés par la Loi sur le droit d'auteur, par les lois, les politiques et les règlements du Canada et des accords internationaux. Ces dispositions permettent d'identifier la source de l'information et, dans certains cas, d'interdire la copie de documents sans permission écrite. Pour obtenir de plus amples renseignements : http://lois.justice.gc.ca/fr/showtdm/cs/C-42

(3)
(4)

In-Situ performance of displacement

ventilation system in Canadian schools

with radiant heating systems

Boualem Ouazia, Ph.D. Michel Tardif, PE Iain Macdonald, Ph.D.

Member ASHRAE Member ASHRAE

Alexandra Thompson, Ph.D. Daniel Booth, Eng.

ABSTRACT

Previous research has shown that stratified ventilation systems (UFAD and DV) work well for regions where buildings require year-round cooling; however there are a growing number of buildings using this approach in Canada, where buildings require heating during winter months. This paper presents results from two field studies conducted in a school equipped with a combination of displacement ventilation and radiant heating system. The results show that the measured contaminant removal effectiveness is better than that predicted in previous studies for heating conditions. In addition, key predictors of thermal comfort are also generally within limits set by ASHRAE standards.

INTRODUCTION

There are two types of mechanical ventilation systems applied to commercial buildings: mixing ventilation  and stratified ventilation. In mixing ventilation the air is supplied in such a way that room air is fully mixed  and the contaminant concentration is the same in the whole room. In stratified ventilation, a stratified flow  is  created  using  the  buoyancy  forces  in  the  room  to  entrain  and  transport  the  air  as  well  as  heat  and  contaminants from lower levels of the space upward, where they are exhausted at or close to the ceiling.  Stratified ventilation systems, underfloor air distribution (UFAD) system and displacement ventilation (DV)),  are methods of delivering space conditioning in offices and other commercial buildings that is increasingly  being considered as a serious alternative to conventional ceiling‐based air distribution systems because of  the potential significant benefits that it can provide (Bauman, 2003). 

With  UFAD  and  DV  systems,  conditioned  air  from  the  air  handling  unit  (AHU)  is  delivered  to  the  space  through floor diffusers or sidewall diffusers at floor level, many in close proximity to the building occupants.  Air is returned at ceiling level. This produces an overall floor‐to‐ceiling air flow pattern that takes advantage  of the natural buoyancy produced by heat sources in the office and more efficiently removes heat loads and  contaminants  from  the  space  (REHVA,  2002;  Bauman,  2003  and  Chen,  2003). Stratified  air  distribution  systems  are  becoming  popular  for  modern  buildings  because  of  improved  indoor  air  quality  (Chen  and  Glicksman, 2003; Bauman and Daly, 2003). Some studies (Hu et al., 1999; Im et al., 2005) have reported that  the systems are more energy efficient thereby reducing energy demand. 

 

Boualem  Ouazia,  Iain  Macdonald  and  Alexandra  Thompson  are  research  officers  and  Daniel  Booth  a 

Technical  officer  at  the  Institute  for  research  in  Construction,  National  Research  Council  Canada,  Ottawa  Ontario. Michel Tardif is an engineer at Natural Resources Canada, Ottawa Ontario. 

(5)

Many previous studies (Lin et al., 2005; Kobayashi and Chen, 2003; and Yuan et al., 1998) indicate that the design parameters have significant impact on the ventilation and energy performance of stratified air distribution systems. Thus, proper selection of diffusers and ventilation systems is important to the air distribution created by DV and UFAD systems.

The approach presented in ASHRAE Standards 55-2004 and 129-1997 is often used in the literature as the reference method for the assessment of air distribution in rooms. The thermal performance of the air distribution system is assessed using two indices: the Draft rating Index (DR) and the Vertical Air Temperature Difference (VATD), which should be respectively lower than 20% and 3 K. The IAQ performance of the air distribution system is often assessed by using the contaminant removal effectiveness (CRE). CRE characterizes the ability of a system to remove air-borne contaminants.

The revision of Standard 62.1-2007 allows some adjustment in ventilation rates based on the ventilation effectiveness of the air distribution system, a feature that may give credit to UFAD and DV systems. Mixing-type air distribution systems can achieve a well mixed space at best, defined as having ventilation effectiveness of 1.0, as determined in accordance with

ASHRAE Standard 129-1997. By definition mixing-type systems cannot provide preferential ventilation (Ev > 1), in which

some credit could be obtained for improved air change effectiveness at the breathing level in the space. Displacement ventilation systems are known to provide improved ventilation effectiveness in the occupied zone. This performance characteristic is being addressed more specially in the ASHRAE Standard 62.1-2007 in which default values for ventilation effectiveness are recommended for different air distribution system configurations and modes of operation. The recommended values are (1) 1.2 for displacement ventilation system in cooling mode, (2) 0.7 for displacement ventilation system in heating mode, (3) 1.0 for an overhead system in cooling mode, and (4) 0.8 for an overhead system in heating mode. UFAD systems are not explicitly addressed, but it is expected that ventilation effectiveness for UFAD with floor diffusers will be less than or equal to 1.2 but higher than 1.0. As a result of their parametric study ASHRAE Research Project 1373 (Jiang and Chen (RP-1373 2008)) propose various values for air distribution effectiveness. In cooling mode, the CRE with UFAD and DV systems is 1.05 – 1.35 for offices and classrooms. In heating mode, the CRE for the DV and UFAD systems is 0.75 – 1.0 for indoor spaces.

Stratified systems are currently in place in North American buildings and in a situation where systems are being designed and installed at an increasingly rapid pace. However, a full understanding and characterization of some of the most fundamental aspects of these systems performance have yet to be done. There is some data on cooling season, but there is no reported data on their actual performance during the heating season. Previous research ignores the specific characteristics of the Canadian climate: the need to operate in both heating and cooling modes. Further on site research is required to measure the performance of DV in heating mode and assess the impact of a perimeter heating system on the performance of a displacement ventilation system in heating mode. In this paper, two field studies conducted in schools equipped with displacement ventilation systems are presented. Results include the performance of displacement systems in terms of indoor air quality and predicted thermal comfort.

STUDY BUILDINGS

Calmar Elementary School, located in Calmar (south west of the city of Edmonton) as shown in Figure 1, is the first new-build Alberta school to be LEED (Leadership in Energy & Environmental Design) Canada-NC 1.0 accredited. Thomas L. Wells Public School is located in Scarborough (residential suburb area of Toronto) (Figure 1) and it is an award winning school, recognized for its sustainable energy design and is the first “LEED Silver” certified elementary school in Canada. Calmar Elementary School

The school is a one-story building with a rectangular plan oriented along the East-West axis, with classrooms located in the east and west wings (see Figure 1). The LEED Canada-NC 1.0 accredited school’s key sustainability features relevant to indoor environmental quality include: operable windows, displacement ventilation, passive solar control, and daylighting in all occupied spaces. Daylighting is provided by south-facing upper sealed ribbon windows and lower peripheral operable windows. Users have access to light switches, lower peripheral operable windows but not to thermostat control.

(6)

in h c a f s s The venti ncoming air. T heating the out conditioned thr at floor level. T

ft3/min per occ

shelf radiators sidewall diffuse

ilation system i The heat recove tside air. The rough heating c

The total airfl cupant). In hea located at cei ers located at f Figure 2. Pla is 100% fresh ery wheel is sw system could coil and then d ow to each cla ting season, he iling level ove floor level and

an of Calmar S air (100% OA witched on wh also be used i delivered to the assroom is bas eat is delivered er the windows return grille lo Figure 1. F School - monito A) with a heat r enever supply in summer to p e space (classr sed on ASHRA d to the spaces s on the perim ocated at ceiling

Field Study Loc

ored classroom

recovery wheel fans are opera pre-cool outsid ooms and com AE standard 6 s (classrooms a meter. Air supp

g level.

cation.

ms (numbered ro

l) for preheatin ating and there de air with the mputer room) th 62.1-2007 (7.5 and computer ply to classroo

 

ooms) and com

ng and pre-coo is a requireme e building air. hrough sidewa L/s per occup room) through oms is delivere mputer room. oling of the ent for

pre-The air is ll diffusers pant) (15.9 h hot water ed through  

(7)

T f v e o c r lo f c a a ( a r t c P M o c o m v a Thomas L. W The schoo floor area of ventilation and environmental occupied space classrooms is c radiant floor sy ocated at floor The schoo for the kinderg characteristics a heating coil o airflow to each ASHRAE stan are installed at radiant floor he emperature. Th convected from PROCEDURE Measuremen Calmar S one day - Apri computer room orientation, occ main differenc varied from 9.7 afternoon. Wells Public S ol is a two-stor 5,554 m2 (59, d natural ven quality includ es. Users have centrally contro ystem. Mechan r level. Exhaust

ol is equipped garten and sec of a typical cla or cooling coil) h classroom is ndard 62.1-200 the ceiling clo eating system he water is th m the floor to th Figure 3 Plan E nt Schedule School - The p il 21st, 2009. M m were occup cupancy, numb es between th 7°C (45.5°F) (e School rey “H” shaped ,783 ft2). The ntilation (opera de: operable w access to ligh olled by the bu nical air supply

t air diffusers a with VAV dis cond floor nor assroom and th ) and then deliv

typically 234 04). Each clas ose to the exteri

located on the hen circulated t he room and oc n of Thomas L. performance as Measurements pied (students, ber of measure he monitored r early morning) d building orie e school has a able windows windows, displ ht switches, O uilding manag y in classrooms are located in t splacement ven rth and AHU he design speci vered to the sp 4 L/s (495.8 ft sroom has five ior wall. Suppl e perimeter. Th through an un ccupants. . Wells School ssessment of t were taken in , teacher and ement location rooms were th ) to 21.1°C (70

ented along the a hybrid venti s). The schoo lacement venti n/Off ventilati ement system s is delivered b the ceilings. ntilation system 2 for first flo ifications of th pace (classroom t3/min) based o e diffusers inst lemental heat d he hydronic sy nderfloor circui - monitored cl the DV system three classroo teaching assi ns and outdoor he room’s orie 0°F) (mid-aftern e East-West axi ilation system ol’s key susta ilation, passive ion switch and (BMS). Perim by displacemen m which consi oor and second he mechanical s ms) through sid on 7.5 L/s (15 talled in the in delivery to clas ystem provides it thus warmin lassrooms indi m at Calmar ele oms and a com istant) during temperature f entation, occup noon), leading is as shown in m integrating m ainability featu e solar contro d thermostat. T meter heating is nt ventilation th ists of two Air d floor south. system. The ai dewall diffuser 5.9 ft3/min per nterior wall at f ssrooms is ach s heat by warm ng the floor. H   cated with blac

ementary scho mputer room. T

the measurem for that day are

pancy and out g to higher supp Figure 3 and h mechanical dis ures relevant l, and dayligh The thermostat s provided by hrough sidewa Handling Uni Figure 3 show ir is conditione rs at floor level r occupant) pe floor level. Th ieved through ming water to a Heat is then ra ck points ol was conduc The three class ment period. e shown in Ta tdoor temperat ply air tempera

has a gross splacement to indoor hting in all t setting in a hydronic all diffusers its: AHU 1 ws general ed (through l. The total r occupant hree returns a hydronic a moderate adiated and cted during srooms and The room able 1. The ture which ature in the

(8)

o s o h M I w m th s d th C O N N O Thomas L of a short moni specified in Tab over sections o hydronic radian C O N N O Measuremen Measurem nstrumented m was used to me measure the re hree instrumen shown in Figu designing and b hree minutes a Classroom Orientation No. of pupils No. of measur Outdoor tempe L. Wells Scho itoring period t ble 2, measure of floor. Measu nt heating and Classroom Orientation No. of pupils No. of measurem Outdoor temper nt Procedure ments were c main pole was easure the air ference air tem nted poles are ure 4. The acc building the se and the average

Figure 4

Tab

ement locatio erature - °C (°

ool - The perfor that took place ments were tak urement locatio at the border b Table 2 ment locations rature - °C (°F) carried out in used for detail temperature an mperature and part of a mon curacy of the et-up. Samplin e of the 60 read 4. Main measu ble 1. Calmar N ons °F) 9.7 rmance assessm e in four pre-se

ken at three dif ons were over between the two . Thomas L. W 222 Nort 28 3 ) -7.4 (17 n compliance led spatial and

nd CO2 level a

relative humid nitoring kit, bu

sensors was t ng from all sen dings is recorde urement pole in School – Moni 17 orth 17 4 (45.5) 1 ment of the DV elected classroo fferent location sections of flo o sections of fl Wells School - M 2 th Sou 7.7) -7. with ASHRA d vertical chara at the return g dity at a height uilt for the mon the main conc nsors occurred ed. nstrumented wi itored spaces 10 South 12 4 4.9 (58.8) V system at Th oms on Februa ns in each class oor without hy loor. Monitored Spa 232 uth-West 33 3 1 (19.2) AE Standards acterization of grilles in the ro t of 1.1 m (0.3 nitoring requir erns (meeting at an interval ith anemomete Computer South 31 3 19.1 (66.4) homas L. Wells ary 10th 2010. D sroom, by mov ydronic radiant aces 236 South 24 3 -5.4 (22.3) s 113-2005, 1 the indoor env ooms and a ref

3 ft) above the rements of this ASHRAE sta of three secon ers, CO2 sensor 4 South 15 3 21.2 (70 s Public Schoo During the peri ving an instrum t heating, over 174 South-Ea 20 3 -4.5 (23.9 129-1997 and vironment. A r ference pole w e floor in the r s study, and m andard specific nds for a total d rs and RTDs h 0) ol consisted iod of time mented pole floor with ast 9) d 55-2004. return pole was used to room. The main pole is cations) in duration of

(9)

ANALYSIS

The performance of displacement ventilation systems in Calmar and Thomas L. Wells schools were assessed using three criteria: (1) Predicted thermal comfort – vertical air temperature difference and draft ratio and (2) IAQ – CRE. The following sections detail the measurements and calculations that apply to each of the above evaluation criteria.

Predicted Thermal Comfort

To quantify the extent of thermal stratification and the vertical air temperature difference for a standing and seating  person in the occupied spaces, air temperatures were measured at six heights 0.1, 0.6, 1.1, 1.7, 2.2, and 2.8 m (0.3, 2.0, 3.6, 5.6, 7.2 and 9.2 ft) above the floor in the monitored spaces. Measurements were taken at four spatial locations in classrooms 17 and 10 and at three locations in classroom 4 and computer room in Calmar school. According to the ASHRAE standard 55-2004 the temperature difference between the head level (1.7 m (5.6 ft) above the floor for a standing person, 1.1 m (3.6 ft) for a seated person) and the ankle level (0.1 m (0.3 ft) above the floor) should be less than 3°C to be considered acceptable conditions. Displacement-ventilated rooms could present occupant discomfort due to draft, because of air supplied at floor level closer to the occupants. To predict the extent of the thermal discomfort due to draft in the occupied spaces, mean air velocities were measured at four heights 0.1, 0.6, 1.1, and 1.7 m (0.3, 2.0, 3.6 and 5.6 ft) above the floor at different locations within classrooms and computer room. The percentage of people predicted to be dissatisfied due to draft is the Draft Ratio (DR) and should be less than 20%.

Indoor Air Quality

To quantify the indoor air quality two measures of ventilation effectiveness are used: the air contaminant concentration

distribution and CRE. CO2 concentrations were measured at three heights, breathing height of seated and standing person (1.1

m (3.6 ft) and 1.7 m (5.6 ft)), ceiling (2.8 m (9.2 ft)), and diffuser and return grille, respectively. ASHRAE Standard

62.1-2007 suggests an indoor CO2 concentration limit of outdoor concentration (300-500 ppm) plus 700 ppm, when outdoor air is

introduced into the room at the rate of 7.5 L/s per person. CRE indicates the efficiency of the ventilation process in controlling exposures to an indoor-generated contaminant emitted at locations spatially distributed within a building and

rooms. It is practical to measure the CO2 concentrations for CRE calculation, which should be representative of the CRE for

other occupant-generated pollutants. Since CO2 measurements were made at the breathing height of seated and standing

adults, for each measurement location within a classrooms two corresponding values of local CRE were calculated, one based

on CO2 measurement at seated breathing height and one based on CO2 measurements at standing breathing height – both

calculations also used CO2 data from the supply diffuser and return grille.

RESULTS AND DISCUSSION

The field measurements at Calmar school were carried out under spring outdoor conditions with the school HVAC

system functioning in a heating mode and the measured air supply temperature at diffusers varied between 20.5oC (68.9°F)

and 23.7oC (74.7°F). The field measurements at Thomas L. Wells school were carried out under winter outdoor conditions

with the school HVAC system functioning in a heating mode and the measured air supply temperature at diffusers varied

between 18oC (64.4°F) and 23oC (73.4°F).

Predicted Thermal Comfort

The average thermal comfort index VATD in all monitored classroom in both schools was lower than the maximum acceptable values of VATD < 3ºC. The average value for each classroom at seating position height (1.1 m) (3.6 ft) and standing position height (1.7 m) (5.6 ft) are presented in Figure 5 for Calmar School and in Figure 6 for Thomas L. Wells School.

(10)

Figure 5. Classroom average VATD at Calmar school

Figure 6. Classroom average VATD at Thomas L. Wells school

The average thermal comfort index DR ranged from 2.1 to 22.3 % at Calmar School (Figure 7). The thermal comfort was not met at 1.7 m (5.6 ft) height in classrooms 17 and 10 where the DR was slightly higher than the maximum acceptable of 20%. The average thermal comfort index DR ranged from 0.1 to 24.1% at Thomas L. Wells School (Figure 8). The thermal comfort due to draft was not met at 1.1 m (3.6 ft) height in classrooms 222, 232 and 236 where the DR was slightly higher than the maximum acceptable of 20%.

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 17 10 Computer 4 VATD (ºC) C la ssr o o m 1.7 m 1.1 m

(11)

Figure 7. Classroom average DR at Calmar school

Figure 8. Classroom average DR at Thomas L. Wells school Indoor Air Quality

The average CRE based on CO2 measurements at the breathing height of seated adults 1.1 m (3.6 ft), standing adult 1.7

m (5.6 ft) and at the nearby supply diffuser and return grille are presented for both schools in Figure 9 and figure 10. CRE at Calmar School was better than what has been reported for DV systems in heating mode (Jiang et Chen 2008) with the exception of classroom 4. As a result of their parametric study, ASHRAE Research Project 1373 proposes various values for air distribution effectiveness. In cooling mode, the CRE with the UFAD and DV systems is 1.05 – 1.35 for offices and classrooms. In heating mode, the CRE for the DV and UFAD systems was 0.75 – 1.0 for indoor spaces. Classroom 4 monitored in the afternoon was supplied with 100% outdoor air at 23.7 ºC, which demonstrated poor ventilation effectiveness

0 5 10 15 20 25 17 10 Computer 4 DR (%) C lassr o o m 1.7 m 1.1 m 0.6 m 0.1 m

(12)

in the occupied zone (CRE<1). The afternoon results do support the findings from the latest ASHRAE Research Project on ventilation effectiveness (Jiang et al. 2008), which state that the CRE index is below 1 during heating mode.

 

Figure 9. Classroom average CRE at Thomas L. Wells school

 

Figure 10. Classroom average CRE at Calmar school

The local average CO2 concentrations were below 700 ppm above outdoor air level (~450 ppm) in all classrooms and

computer room at Calmar School. However, local average concentration of CO2 was much higher than 700 ppm above

outdoor air level (~470 ppm) in all monitored classrooms at Thomas L. Wells School. The outdoor air intake was controlled

by CO2 sensor located in the return duct in the case of Thomas L. Wells School. It was discovered afterwards that the school

CO2 sensor has not been calibrated, which called for the minimum fresh air damper position despite a level of CO2

concentration way above the threshold imposed by the control strategy.

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 17 10 Computer 4 CRE (-) C la ssro o m 1.7 m 1.1 m

(13)

CONCLUSIONS

In-situ monitoring of thermal parameters was carried out in two schools with displacement ventilation systems in the buildings working in heating mode. The thermal comfort and indoor air quality indices (DR, VATD and CRE) were calculated for up to four measurement locations in classrooms to assess the in-situ performance of the displacement ventilation system. Average vertical air difference temperature index was within acceptable limits of VATD < 3°C in both schools. Calmar School measurements showed that threshold limits with regard to draft were generally not exceeded in the occupied zone (< 1.7 m) (< 5.6 ft); however, thermal comfort was not met at 1.7 m (5.6 ft) in classrooms 10 and 17 due draft issue. Thomas L. Wells presented an acceptable thermal comfort except at height of 1.1 m (3.6 ft) in Classrooms 236, 232

and 222, when DR was used as the criteria for assessment. The local average CO2 concentrations were below 700 ppm above

outdoor air level (~450 ppm) in all classrooms and computer room at Calmar School. However, local average concentration

of CO2 was much higher than 700 ppm above outdoor air level (~470 ppm) in all monitored classrooms at Thomas L. Wells

School.

With the exception of Classroom 4, Classrooms (17 and 10) and Computer room at Calmar School provide a satisfactory indoor environment in term of air quality index with average CRE > 1. Measured CRE at Thomas L. Wells School ranged from 0.87 to 1.16. The air quality index (CRE) with the exception of classroom 4 (Calmar school) was better than what is usually reported in heating mode for TDV system. These results contradict the latest ASHRAE Research Project on ventilation effectiveness (Jiang et Chen 2008), which states that the CRE index is below 1 during heating mode and equals to 0.7 as recommended by ASHRAE standard 62.1-2007. Even with secondary heating, the results of their study for classrooms showed that the TDV system does not perform as well as during cooling mode. The results from these two field studies, where the ventilation systems were in a heating mode with fairly low supply temperatures, do not support these findings and showed good performance of a displacement ventilation system in heating mode. However, the afternoon results in the case of classroom 4 at Calmar School with high supply temperature do support these findings and showed bad performance of a displacement ventilation system characterized by CRE<1. One explanation can be that the high supply air temperature could affect the distribution of contaminant in the space and produce a non-stratification distribution.

ACKNOWLEDGEMENTS

This project was supported by funding provided by both the federal government department of Natural resource Canada through the Panel of Energy Research & Development and by the National Research Council of Canada. The authors thank the Black Gold School Board and the Toronto School Board for giving us access to Calmar Elementary School and Thomas L. Wells Public School.

REFERENCES

ASHRAE Standard 62.1 (2007) Ventilation for acceptable indoor air quality. Atlanta: American Society of Heating Refrigerating and Air-conditioning Engineers, Atlanta, Inc.

ASHRAE Standard 55 (2004) “Thermal environmental conditions for human occupancy” American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

ASHRAE Standard 113 (2005) “Method of testing for room air diffusion” American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

ASHRAE Standard 129 (1997) (RA 2002) “Measuring air change effectiveness” American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Bauman F S (2003) “Underfloor Air Distribution (UFAD) Design Guide” American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Chen Q and Glicksman L (2003) “System Performance Evaluation and Design Guidelines for Displacement Ventilation” American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Hu, S., Q. Chen and L. Glicksman (1999). Comparison of energy consumption between displacement and mixing ventilation systems for different US buildings and climates. ASHRAE Transactions 105(2), pp. 453-464.

(14)

Im, P., A. Cho, and J. Haberl (2005). Literature review on under floor air distribution (UFAD) system. Technical Report of the Energy Systems Laboratory, Texas A&M University System, USA.

Jiang Z. and Chen Q (2008) “Air distribution effectiveness with stratified air distribution systems” ASHRAE Research report – 1373.

Kobayashi, N., and Q. Chen (2003). Floor Supply Displacement Ventilation in a Small Office. Indoor and Built Environment. 12(4), pp. 281-291.

LEED Canada-NC 1.0 (2004) “LEED Canada Reference Guide” Canada Green Building Council.

Lin, Z., T.T. Chow, K.F. Fong, Q. Wang, and Y.Li (2005) Comparison of performance of displacement and mixing ventilations. Part I: thermal comfort. International Journal of Refrigeration 28, pp. 276-287.

Lin, Z., T.T. Chow, K.F. Fong, C.F. Tsang, and Q. Wang (2005) Comparison of performance of displacement and mixing ventilations. Part II: indoor air quality. International Journal of Refrigeration 28, pp. 288-305.

Skistad, H., Mundt, E., Nielsen, P.V., Hagstrom, K., Railio, J. (2002) “Displacement ventilation in non-industrial premises” REHVA, Federation of European Heating and Air-conditioning Associations.

Yuan, X., Q. Chen, and L. Glicksman (1998). Critical review of displacement ventilation. ASHRAR Transactions. 104(1A), pp. 78-89. 

Figure

Figure 5. Classroom average VATD at Calmar school
Figure 8. Classroom average DR at Thomas L. Wells school  Indoor Air Quality

Références

Documents relatifs

1995 Solstice d'été, Centre d'exposition L'Imagier, Aylmer 1994 Dans ce monde qui baril, Maison de la culture Fronter 1992 Effet de ressac, Centre des arts actuels SKOL, Montré

Numerous examples of this phenomenon can be cited for both the East and West of the Roman world: tetradrachms minted in Rome for Syria; tetradrachms minted in Alexandria for

The new patterns and forms of migration seen among East European migrants in the West*in terms of circular and temporary free movement, informal labour market incorporation, cultures

While peripheral nervous system (PNS) can adapt to traumatic lesions by regenerating axons and, depending on the lesion severity, restore synaptic connectivity, adult

Les outils du web 2.0 ont démultiplié les indices de vivance, qui relèvent de l’inscription du Système dans la représentation de l’utilisateur, tout comme les sociatifs relèvent

Considering the serotonergic profile of escitalopram, and the 5-HT 2 and 5-HT 3 receptor blocking properties of mirtazapine [ 6 ], the latter drug was introduced at 15 mg/day, as

There had been no known effective control measures for this disease until Edward Jenner discovered a vaccine towards the end of the 18th century. This vaccine had been gradually used

(i) Catalytic antibody on phage surface binds and cleaves phosphate substrate; (ii) phenolic product loses fluoride forming a quinine methide; (iii) quinine methide bonds covalently