• Aucun résultat trouvé

Field test on an exhaust air heat recovery heat pump

N/A
N/A
Protected

Academic year: 2021

Partager "Field test on an exhaust air heat recovery heat pump"

Copied!
14
0
0

Texte intégral

(1)

Publisher’s version / Version de l'éditeur:

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

Building Research Note, 1985-02

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

NRC Publications Archive Record / Notice des Archives des publications du CNRC : https://nrc-publications.canada.ca/eng/view/object/?id=c825ebb0-26a2-48d5-8f1b-37bc56f41367 https://publications-cnrc.canada.ca/fra/voir/objet/?id=c825ebb0-26a2-48d5-8f1b-37bc56f41367

NRC Publications Archive

Archives des publications du CNRC

This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.

For the publisher’s version, please access the DOI link below./ Pour consulter la version de l’éditeur, utilisez le lien DOI ci-dessous.

https://doi.org/10.4224/40000490

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

Field test on an exhaust air heat recovery heat pump

(2)

BUILDING

RESEARCH

NOTE

r:.

q;

{ E \ . J ~ ~ ~ ~ Q U E

. . I

.

.

!rn.

. - izT

TEST ON AA EXHAUST

AIR IIEAT RECOVERY m,AT

PUMP

R.X. Chauhan

I

D i v i s i o n of B u i l d i n g Research, National Research C o u n c i l of Canada

Ottawa, February 1985

I

(3)

FIELD TEST OM AN EXHAUST AIR HEAT RECOVERY REAT PUMP by

R.B. Chauhan

ABSTRACT

This paper summarizes the results of the field testing of an Exhaust Air E e a t Recovery Heat Pump (EAHRHP) prototype which was installed in an unoccupied conventional house (House H3 of the BUDAC Mark X I Project Series), to determine its effectiveness as a supplementary heater, its effect on house a i r change rate and its overall performasce in actual use.

INTRODUCTION

A study conducted by Hooper and Angus 111 for the National Research Council i n d i c a t e d that an Exhaust Air Heat Recovery Beat Pump (EAHRRP) System should be a b l e t o reduce heating energy requirements in a house, improve indoor a i r q u a l i t y and reduce indoor humidity. As a result, t h e Division of Building Research commissioned ReepRite Inc. to design and b u i l d two prototype EAHRHP units based on the design parameters from the study done by Hooper and Angus Assoc. This f i e l d t e s t of one of these prototypes

was undertaken t o s e e how w e l l t h e prototype met t h e performance expectations.

As shown in Figure I, the space heating EAHRHP is a single unit that is installed inside t h e house, It is an a i r t o - a i r heat pump recovering heat from the exhaust a i r stream. Heat absorbed by the evaporator coil from t h e exhaust a i r stream plus t h e heat of compression is transferred to the house, from the condenser c o i l . Heated a i r is introduced either d i r e c t l y fnto a r0Qm or into the a i r distribution system of t h e house.

Air is s u p p l i e d to the heat pump from the building space. The s u p p l y

air temperature (Ti) is r e l a t i v e l y constant during t h e heating season, whereas the indoor relative humldlty (Elli) fluctuates with the rate of indoor moisture generation and t h e outdoor humidity

(RHO).

In essence, the b u i l d i n g a c t s as the supply plenum for the unit. Uhen t h e exhaust fan of the EAHRHP is on, the neutral pressure plane in the house i s r a i s e d , and the amount of a i r which is infiltrated i n t o the residence increases and the exfiltration decreases as compared to the natural value. The t o t a l rate of a i r infiltration (VT) is then equal t o the 8 U m of the forced ventilation

r a t e (VV) and the rate at which air exfiltrates through the building envelope

(VT

'

1.

Increasing the amount of air infiltrating into the house during t h e heating season by operating an exhaust fan, results in increasing the space heating load and decreasing the indoor relative humidity. Generally, if the natural ventilation rate is low, the relative humidity is high and there may be moisture-related building problems. In this case, the reduced RH is a d e s i r a b l e e f f e c t of the EAfIRHP, and reduced e x f i l r r a t i o n is also b e n e f i c i a l . The increased air infiltration, however, reduces the net energy savings of the E A R W .

(4)

DESCRIPTION OF W R H P PROTOTYPE

The prototype E A H W w a s 616 lam wlde x 687

mm

high x 464 mm deep. The refrigeration schematic is shown in Figure 2.

A summary of the components and d e s i g n conditions as provided by the designers [23 are as follows:

a) Evaporator c o t 1 consists of 5 rows of 9.52 mm diameter tubing w i t h f i n height of 203 mm and l e n g t h of 2 5 4 mm. There are 3.9 fins per a. Nominal air flow is 52 L / s at 60 Pa static pressure difference. b a t absorption rate is 2-7 kW at -20°C evaporating teqerature and air inlet temperature +20°C.

b ) Condenser coil consists of 5 rows of 7.94 mm diameter tubing with f i n height of 356 mm and length of 457 ma. There are 4.72 fins per cm. Nominal airflow is 260 L/s a t 60 Pa s t a t i c pressure difference. b a t rejection rate is 4.3 kW at 38% condensing temperature and air i n l e t temperature of +2D°C.

c ) Compressor is Tecumseh Model AB5527fI high e f f i c i e n c y R22 heat pump compressor with a nominal capacity of 7.9 kU.

d ) Blowers for both the evaporator and the condenser are single width, s i n g l e i n l e t type. The evaporator blower has a Torin 1060 housing with an impeller

160

mm in diameter and 59 m~ wide. The direct drive

three-speed motor i s capable of operating at 1330, 1140 and 1000 rpm. A t

1140 rpm it produces a f l o w of 52 LIB at 60 Pa static pressure difference.

The condenser blower has a Torin 1343 housing with a blower impeller 216 lam in diameter and 114 mm wide. The single speed direct drive motor runs at 1130 rpm, producing a flow of 269 L / s at 50 Pa static pressure difference.

e) Defrost timer l a a s o l l d s t a t e device which has been preset to provide a defrost cycle every 34 minutes. During a defrost c y c l e lasting

4.5 minutes t h e compressor is turned off and the evaporator fan

is

k e p t running.

DESCRIPTION OF THE INSTALLATION

The EMHRW was I n s t a l l e d in a two-storey detached house located in

Orleans, near O t t a w a . The house has 118 m2 -of l i v i n g area and a f u l l basement with cast-in-place concrete foundation. This house had been modified to have a measured natural ventilation rate under calm wind

conditions of 0.5 ac/h at an outdoor temperature of -lSDC. Indoor space temperature was maintained at 20°C. The EAEIBHP was installed as the f i r s t stage of a two-stage heating system with the electric furnace acting as a backup. The beating system was controlled by a two-stage thermostat, with the EAlBHP having priority over the- furnace. The furnace fan

ran

continuously to provide cdnstant a i r circulation.

Stage

I

of the thermostat turns the E A H W on. The EAHRHP would run to

s a t i s f y the space heating requirements and f f the heat demand w a s higher than the output of Zhe

EAHREP,

then the electric furnace would be brought on by the second stage of the thermostat.

(5)

This control strategy is ahown IZn Table 1.

The EMRIP and furnace interconnection is shown in F i g u r e 3. The exhaust air is drawn from the heated space (basement) at @ rate of 57 L/S

and the flow over the condenser is drawn from the basement at a rate of 191 L / s . !fhe heated air from the E m P condenser is then discharged into the return a i r plenum. The furnace fan is run continuously to allow for the distribution of the heated a i r s u p p l i e d by the EAHEW.

The heat supplied by the EAHIUP was measured by fitting the insulated condenser discharge duct with a d i f f e r e n t i a l thermopile to masure the temperature difference between air in khe duct and the basemeat air. The output of the thermopile was connected to an integrating counter, This counter had been calibrated a t an airflow rate of 191 L I s over the condenser cot1 to produce a pulse of the counter for every 170 kJ of heat supplied to the house.

I

TESTS CONDUCTED

The t e s t was carried out over a period from Dec. 2 4 , 1983 to May 10, 1984 w i t h some gaps, since t h i s house was also being used for some other t e a t s .

Monitoring of the EAHRWP and furnace energy consumption was done by reading the kWh meters once a day at 1400 hours.

Tests were conducted t o tmnitor the energy consumption af the EAHRHP and furnace in various operating modes over the duration of t h e test period.

a) During s e l e c t e d periods, the EAHRIIP was turned off and the energy used by the furnace was recorded.

b) Energy consumed by the furnace and EAHESP was recorded when the house was heated by this combination.

c) P e r i o d i c checks of EABRHP performnce were done t o d e t e d n e a i r temperature and volume of a i r flowing across It, This a l s o confirmed that there were no changes i n the conditions under which the EAHRHP was operating

.

d)

The

air change rate of the house was also measured throughout the

duration of the t e s t period. These Peasurements were done during varying outdoor conditions and under situations when the EABRBP was runrifng and when it was not running.

Weather information used for analysiug the t e s t results was obtained from the Ottawa Internatllonal Airport weather o f f i c e .

TEST RESULTS

Figure 4 shows the electric energy consumption

of

the furnace, t h e furnace and EAHRRP, and the EAEiRHP only. The purchased heating energy required to maintain t h e same space temperature is less with the

EAEIRHPlf uraace combination than it is with the furnace alone. Above the balance point, the furnace component of electric consumption consists OE the

(6)

furnace fan energy, since the fan ran continuously. Table 2

shows

a summary

of

the heating requirements of some selected indooroutdoor temperature differences. This shows that the heating energy required to maintain the same temperature difference is less by 23 t o 33% with the EAHRHPlfurnace combination compared to furnace only.

The electric energy consumption curve for the

EAHRHP

only shows that the EAHRHP s t a r t s t cl run continuously a t indooroutdoor temperature

difference

(ATi,)

of about 17 X. This means that the EAHRHP can supply all t h e heating requirements of the house above an outdoor temperature of 3 ' ~ . This varies somewhat depending an the solar and internal gains. B e l o w 3 ° C outdoor temperature, the EALlMP needs extra heat from the furnace or the space temperature will start t o drap from its thermostat set point.

Figure S shows the sir change rate of the house at d i f f e r e n t

ATio

conditions when the EAHBlHP is tunriing and when it is off. This shows that

a t a ATi,

of

35 K the house a i r change rate is about 0.5 ac/h when t h e

EARRHP is o.£f, i . e . , evaporator (exhaust) fan is o f f . This a i r change rate rises to about 0.67 ac/h when the EAHRHP is running. This increased

i n f i l t r a t i o n increases t h e heating laad due to i n f i l t r a t i o n by ,about 30%. The coefficient of performance (COP) is deftned as the r a t i o of heat output t o the work input 131. The- work input c~dsists of energy used by the EAHREIP (i.e., by the compressor, fans and controls)

(E

)

The

heat output c o n s i s t s of this energy (E lus. the heat gafned at evaporator from the exhaust air stream (Q,

:

m COP

-

$ElP

"

Qe ,

PELP

-

7

-

5

Figure 6 shows the d a i l y average COP of the ISAHRHP with respect: to ATio. The COP is essentially constant over the range of operating

temperature conditions. &frost cycles are initiated after every 34 minutes of continuous operation. At outdoor temperatures below 3'C, the compressor runs continuously. Thus t h e effect of defrost cycles is a s l i g h t

degradation in EAHREiP performance when operating below the balance point, Since the UHREiP is operati= indoors and the evaporator is exposed L O

air at room temperature {approximately 2 0 O ~ ) the evaporator load on the compressor does not fluctuate much, which in turn means that t h e compressor power draw remains s t a b l e . This suggests that the COP would be f a i r l y constant aver t h e heating season and the test results seem to confirm t h i s .

COMPUTER SI?WIATIONS

FOR

SEASONAL FERFORMANCE IN VARIOUS CLIPiATIC LOCATIONS To evaluate the seasonal petfanuance of the

E M P ,

computer

a i a l a t ions using an in-house computer program were performed [EAST Build'fng Heating Load Calculation Method by D. Sander]. The simulated performance of

the EAHRHP in the t e a t house for various climatic locations is l i s t e d fn Table 3.

The simulations indicate that the EAEiRFIP c o u l d reduce purchased heating energy requirements anywhere from 25 to 48%, depeadfng on severity of l o c a l

(7)

climatic conditions. This saving could be further

increased

if the

coefficient of performnce was raised by an Improved d e s i g n . However t h e absolute savings in electrical heating energy is about 5 MWmh per house per season in all regions.

C O W N T S ON

FIELD

PERFORMANCE OF THE EABRIIP

The installation, w i r i n g and controlling of the EAHRHP in the t e s t house was f a i r l y etraightforward.

Onc& i n s t a l l e d , the EAHRtIP operared without any problems. The defrost system worked well and it was easy t o dispose of the condensate via the basement drafn or through a laundry tub l o c a t e d nearby. The aperatfng n o i s e l e v e l of the EAFIRFiP was not high.

It

blended in w i t h the normal heating

system sound levels.

The exhaust a i r heat recovery heat pump d i d perform as predicted in the Hooper, Angus report, although at a lower c o e f f i c i e n t of performance, and with more defrost cycles. The EAHRBP w a s effective in supplying a

signff icant portion of the heating energy i n the t e s t house, with an increase in the base i n f i l t r a t i o n rate of the house.

Computer sirmrlations indicate that the

EAHRHP

can redurn seasonal

electric heating energy consumption by up to 48X depending on local climatic conditions, and it can supply up t o 972 of the required seasonal heating energy in m i l d e r climates.

ACKNOWLEDGEMENTS

The author wishes t o acknowledge the technical assistance of

David R. Wright in instrumenting the project. The author also wishes to thank

Dr.

C.Y. Shaw and

Dr.

A.K. K i m for their assistance in providing a i r

(8)

REFERENCES

1 . Booper and Angus Associates, Development of an Exhaust Air Beat Recovery Heat Pump: A Study.

DBR

Contract Report OSX800-0014S, prepared for National Research Counctl Canada, Division of Building Research, Ottawa, 19 81-82.

2. Blackmore, G.R., Design, Construction and Testing of Prototype Exhaust Air Heat Recovery Beat Pump, KeepRite Inc., DSS Contract

No. OSX83-00013, Brantford, Ontario, January, 1984.

3. Sauex, H.J. and Howell, R.H., Heat Pump Systems. John Miley and Sons, Elew Pork: Toronto, 1983, 7 2 1 pp.

(9)

Table 1:

E~REPIFURNACE

CONTROL STRATEGY M o r m a l Ilef rost

Component Cycle Cycle

Thermostat

S t a g e 1 Evap Fan ON-OFF OM

Cond Fan OM-OFF OFF Above

Compress or OM-OFF OFF Balance

Furnace Fan ON ON Point*

Furnace OFT OFF

Stage 2 Evap Fan ON ON

Cdnd Fan OW OFF B e l o w

omp pressor

ON OFF Balance

Furnace Fan OW ON Point*

Furnace ON*FF ON-OFF

*Balance p o i n t is the outdoor temperature above which t h e EAFIREIP can supply all the heating requirements of the dwelling.

Table 2: COMPARISON OF HEATING ENERGY CONSUMETION WITH (EAHRIIP

+

FURHACE) AND FUEWACE ONLY

Indooroutdoor temperature difference

K

Heating energyldayl (A) (B) Furnace only EAHWP+Furnace

k~ .hiday kU* hiday

(

&DdUC-

x 100)

A

(10)

Table 3: EAIIRHP COMPUTER SIMULATIONS FOR VARIOUS CANADIAN CITIES

Air change/bour base = 0.47 average; Internal g a i n s = 1.0 kW Air changehour w l t h EAHRHP = 0.63 Average

Vancouver Summerland Halifax Toronto O t t a w a Edmonton 2623 D P 3313

D W

3762 DB* 3911 D I P 4456 BD* 5628 DD* No. 1. Heat supplied by furnace, kWmh 259 2895 4009

3317

4971 8342 2, Heat s u p p l i e d by

EAHRHP,

kW-h 3. Total heat s u p p l t e d

1

(1)+(2)

1 ,

kW*h 110 3 17

4, Hear reqd i n base hause

1

without EAHRHPI, kW=h

5. Purchased energy f o r ElllLRHP at: COP 2.2 =

[ ( 2 ) 5 2 . 2 ] , kW*h 6. Total purchased energy [ (1)+(5)

1,

kW.h 7. Energy saved by m P [(4)-C6)1, kW*h 8. X Reduction in

purchased enerw due

9. % of total heating supplfff by EAHRllP

d

-

I

10.

Z

Increase in heating -

load due t o higher 12

(11)

\

OUTDOOR

AIR

COND ITION

T o , RHO)

f

A I R EXflLTRATlON

v;

T.

1

l NDOO R TEMPERATURE

To

OUTDOOR

TEMPERATURE

RH-

INDOOR

RELATIVE HUMIDITY

I

RH

OUTDOOR

RELATIVE HUM1

D

ITY

0

Q~

P

HEAT

DELIVERED BY EAHRHP

Qe

HEAT

GAIN

AT

EVAPORATOR

E~~

ENERGY

USED

BY

EAHRHP

v~

TOTAL

RATE

OF

A I R

lNFlLTRATlON

vv

FORCED

VENT

I

IATI

ON

R A E

'i

RATE

OF

A I R

EXFILTRATION

F I G U R E 1

(12)

ROOM

- A I R

FLOW

20°C

57

L l s

ROOM

-

A I R

FLOW

mOc

191

Ils

F I G U R E

2

R E F R l

G E R A T I O N S C H E M A T I C

(13)

SUPPLY RETURN EXHAUST F I G U R E 3 EAHRHP A N D FURNACE INTERCONNECTION F I G U R E 4

(14)

I 1 I I

0 EAHRHP FAN ON

10 20 30 40 5 0

INDOOR-OUTDOOR TEMPERATURE DIFFERENCE, K lDA l LY AVERAGE)

F I G U R E 5

A I R CHANGE R A T E W I T H E A H R H P

INDOOR-OUTDOOR TEMPERATURE DIFFERENCE, K IDA t LY AVERAGE)

COEFF I C IENT

OF

P E R F O R M A N C E

OF

E A H R H P B A S E D ON D A I L Y A V E R A G E V A L U E S

Figure

Figure  4  shows  the  electric energy consumption  of  the  furnace,  t h e   furnace  and  EAHRRP,  and the  EAEiRHP  only
Table  1:  E~REPIFURNACE  CONTROL  STRATEGY  M o r m a l   Ilef  rost
Table 3:  EAIIRHP  COMPUTER  SIMULATIONS  FOR  VARIOUS  CANADIAN  CITIES

Références

Documents relatifs

This paper illustrates the design of a supervision and control system for a pilot Rankine steam process for exhaust gas heat recovery from a spark-ignition (SI) engine, from

17 Demande Contexte Projet Analyse Étapes d’approbation 29 juin 2021 Séance du comité de démolition. CCU 23

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at Scale-Based Monotonicity Analysis in Qualitative Modelling with Flat

The National Roofing Contractors Association (NRCA) and the Institute for Research in Construction (IRC) collabo- rated on a study of blistering in hot- applied SBS-modified

We used a 1-D finite differences thermal model and a Monte-Carlo procedure to find the best estimates of these site perturbations: all the eight borehole temperature logs can

This paper deals with a Hybrid heat recovery system that reuses the thermal energy captured by exhaust gases to produce domestic hot water and generate electric power

Avec le vieillissement de la population et l’évolution des progrès techniques, les maladies chroniques connaissent un développement considérable dans le monde entier