I
ALTERNATIVE ELECTRICAL ENERGY SOURCES FOR MAINE SUMMARY REPORT
W.J. Jones M. Ruane
MIT Energy Laboratory Report No. MIT-EL 77-010 December 1977
ALTERNATIVE ELECTRICAL ENERGY SOURCES FOR MAINE
W.J. Jones M. Ruane
SUMMARY REPORT
This report, prepared for the Central Maine Power Company, presents a comparative discussion of twelve technologies which were evaluated as possible alternatives to the construction of a 600 MWe coal-fired gener-ating plant.
The evaluations are published as appendices, each devoted to a spe-cific technology.
Acknowledgments
Numerous people shared reports and data with us and provided
comments on the draft material. We hope that everyone has been
acknowledged through the references in the technical sections,
but if we missed anyone, thank you!
Ms. Alice Sanderson patiently weathered out many drafts and
prepared the final document with the assistance of Ms. Dorothy
Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F Appendix G Appendix H Appendix I Appendix J Appendix K Appendix L
Conversion of Biomass - C. Glaser, M. Ruane
Conservation - P. Carpenter, W.J. Jones, S. Raskin, R. Tabors
Geothermal Energy Conversion - A. Waterflow
Ocean Thermal Energy Conversion - M. Ruane
Fuel Cells - W.J. Jones
Solar Energy Conversion - J. Geary, W.J. Jones
Conversion of Solid Wastes - M. Ruane
Storage of Energy - M. Ruane
Wave Energy Conversion - J. Mays
Ocean and Riverine Current Energy Conversion - J. Mays
Wind Energy Conversion - T. Labuszewski
Environmental Impacts - J. Gruhl
Initial literature reviews and drafts of the various technical appendices were prepared by the persons listed.
Preface
The Energy Laboratory of the Mass. Inst. of Tech. was retained by the Central Maine Power Company to evaluate several technologies as possible alternatives to the construction of Sears Island #1 (a 600 MWe coal fired generating plant scheduled for startup in
1986).
The assessments were made on the basis that a technology should be:
1) an alternative to a base -load electric
power generation facility. Base - load is
defined as ability to furnish up to a rated
capacity output for 6570 hours per year.
2) not restricted to a single plant. It
may be several plants within the state of Maine. The combined output, when viewed in isolation, must be a separate, "stand-alone" source of power.
LIST OF TABLES
Table Page
1.1 Technologies Considered 10
2.1 Components of Alternatives 22
2.2 Capacities and Annual Energies from Alternative
Technologies 25
3.1 Summary of Environmental Impacts of Alternative
Technologies 29
4.1 Special Requirements for Alternative Technologies 32
5.1 Levelized Fixed Charge Rate Assumptions 35
5.2 Optimistic Electricity Costs from Alternative
ALTERNATIVE ELECTRICAL ENERGY
SOURCES FOR MAINE
Page
Conclusions 6
1.0 Introduction 10
1.1 Scope of the Study 10
1.2 Methodology 11
1.3 Discussion 12
1.4 Caveats 14
2.0 Status of Technological Development 17
2.1 Principles of Operation 17 2.2 Components of Alternatives 21 2.3 Technical "Quantification" 21 3.0 Environmental Effects 27 4.0 Applicability to Maine 30 4.1 Special Requirements 31
4.2 Estimates of Energy and Capacity 31
5.0 Economics 33
5.1 Economic Assumptions 33
5.2 Cost of Electricity 36
LIST OF FIGURES
Page
1.1 Projected Electric Sales for Central Maine Power 13 Figure
Conclusions
A) The alternative technologies to a coal-fired steam/electric
plant considered in this report cannot be relied upon to supply the
expected increase in demand for electricity in Maine by 1986.
Tech-nical, regulatory, and institutional limitations, and the lack of
com-mercial experience indicate that they could not reliably be expected
to supply the power and energy of the proposed plant.
B) Several of the alternative technologies (biomass,
conserva-tion, solar space and hot water heating, solid waste conversion,
sto-rage, and wind) appear to offer some potential of increased energy
ef-ficiency and renewable indigenous energy supplies with acceptable
re-duced environmental impacts. These near-term technologies could begin
to contribute to Maine's energy supply between now and 1986. They
should be examined further and encouraged to determine if they are
en-vironmentally and economically desirable.
C) Other alternative technologies (central station solar
ther-mal, central station solar photovoltaic, dispersed solar photovoltaic,
waves, and currents), combined with energy-storage systems, also
ap-pear to offer potential for renewable indigenous energy supplies and
reduced environmental impacts. These technologies cannot expected to
contribute to Maine's electricity supply until some time after 1986.
Maine should follow their development in other locations more
favor-able to their development.
D) Maine does not have the conditions and resources required for
ocean thermal and most forms of geothermal energy conversion. Hot dry rock geothermal energy conversion in Maine might be possible but would
not contribute to Maine's electricity supply until after the year 2000. Maine should follow its development in other, more favorable
geological locations.
E) Reliable quantification of the power and energy potential,
costs, and environmental impacts of the alternative technologies is
not possible without further basic data collection in Maine followed
by specific design studies. If Maine hopes to utilize these
technolo-gies in the future, such data collection and design studies will be
necessary.
F) Best case approximations of performance for the alternative
technologies indicate that, regardless of costs, they cannot
indivi-dually supply or eliminate the expected increase in demand for
elec-tricity. Based on available information, it is entirely conjectural
to estimate the possible composite performance if all the
alterna-tive technologies were implemented. Even the individual best case
ap-proximations are subject to possible errors which could lead to
se-rious undercapacity and economic problems if Maine were to rely on the
alternative technologies.
G) Many of the alternative technologies (solar space and hot
wa-ter heating, wind, central station solar thermal, central station
so-lar photovoltaic, dispersed soso-lar photovoltaic, waves, and currents)
are best operated in a fuel-saver mode, in which they supply energy as
it becomes available. Unless extensive energy storage is included,
these technologies provide on a random basis either peaking or
inter-mediate energy, rather than base load power.
On a statistical performance/demand basis these types of energy
facilities can present a "capacity credit" of "reliable" power within
a given utility system. This "reliable" power can be expressed as a
fraction of the rated capability per facility. There are current
in-vestigations which should result in a methodology for arriving at
"capacity credit" equivalencies for a number of dispersed energy
sta-tions. The studies are not complete.
H) Best case approximations of performance for the near-term
al-ternative technologies indicate that their electricity costs in 1986
will be between 50 and 100 mills/KWh. Actual costs will probably be
higher but can only be quantified by actual design studies. Estimated
costs for mid-term technologies fell in a range from 75 to 200
mills/Kwh in 1986 dollars. The above are "busbar" costs, that is, the
costs of electricity at the output terminals of the generation
plants. Allowance for funds used during construction (see p. 34) must
be added to these estimates to determine the total busbar costs.
I) The overall environmental effects of the alternative
techno-logies appear to be roughly equivalent to or possibly less than the
ef-fects due to coal-fired generation. The absence of commercial
experience or even full-scale prototypes makes quantification of the
impacts difficult.
J) Based on the information in Table 2.1, note that only
conver-sion of biomass, conservation, distributed solar space and hot water
heating, solid waste incineration, storage, and wind conversion are
only conservation, solid waste incineration, and storage have some
es-tablished commercial experience. The others of this group have the
po-tential to be commercially developed in time to supply energy for 1986.
It should be recognized that the necessary lead times for
design-ing and licensdesign-ing these alternative technologies may preclude their
availability by 1986 even though the commercial technology is
available by then.
1.0 INTRODUCTION
1.1 Scope of the Study
The Energy Laboratory of the Massachusetts Institute of
Techno-logy (MIT) was retained by the Central Maine Power Company (CMP) to
e-valuate several technologies (Table 1.1) as possible alternatives to
the construction of Sears Island #1 (a 600 MWe coal-fired generating
plant scheduled for startup in 1986). This report presents the
re-sults of the study.
Table 1.1
TECHNOLOGIES CONSIDERED
conversion of biomass
increased conservation
geothermal energy conversion
· ocean thermal energy conversion
fuel cells
solar energy conversion
conversion of solid wastes
storage of energy
wave energy conversion
ocean and riverine current energy conversion
· wind energy conversion
On a national scale, the technologies of Table 1.1 have
stimula-ted interest because of their independence from conventional fossil
and/or nuclear fuels and because they offer the potential of more
1.2 Methodology
The study of the technologies was based primarily on critical
re-views of the available literature, supplemented, when possible, by
discussions with researchers, government agencies, equipment vendors,
and architect/engineering firms. Each technology was reviewed
sepa-rately. The results of these separate studies are included as
ap-pendices. The body of this report presents comparative discussions,
based on the appendices, using four categories:
Status of Technological Development: description of the
alter-native approaches in terms of their principles of operation,
ma-jor components, operating experience, projected development
sched-ule, anticipated technical problems. This was a generic study of
the technologies per se.
Applicability to Maine: special requirements for utilization;
availability of requirements in Maine; potential energy
produc-tion in Maine; instituproduc-tional objecproduc-tions to use.
Economics of Operation: economic assumptions; capital and
ope-rating costs; projected electricity costs.
Environmental Consequences: air, water, and land use impacts of
conversion technology; impacts of ancillary operations;
envi-ronmental benefits.
1.3 Discussion
Increased efficiency in the generation and consumption of energy
and the use of renewable energy sources should, in general, be
en-couraged in the face of our nation's growing dependence on fossil
fuels. Several of the technologies studied by MIT offer this
poten-tial to Maine. An exploration in more detail would be necessary to
determine those most appropriate for contribution to Maine's energy
supply.
This study, however, had a narrower purpose in that it was
searching for alternatives which could possibly eliminate or delay the
need for the coal-fired 600 MWe generation planned at Sears Island.
For this search, the load forecast of CMP (Figure .1) was taken as a
given. Each technology was evaluated to answer the following:
1) Under what conditions could this technology supply
(con-serve) the power and energy to be supplied by Sears Island
#]?
2) What would be the best performance to be expected from this
technology?
In some cases, a successful commitment to a single or a combination of
alternative technologies could conceivably delay the need for coal
generation for a year or two although the energy costs would probably
be higher. This was not considered to be a true alternative, since
the plant would still be needed to supply Maine's lonq-term energy
Capability Responsibility, Millions of Kilowatts (106) Y) N i O cm CO c N.c - c Od .d . .~ -. .. . . - .
r-1--J Ni
. i
,
I
i-
I
L ' \\r ib~---- I \')U , : 4 CY ) T.I r~~ 9-: .. II 0 c i In. I=....
. .*..L
-- · 1i\
. * . . .c'
--- ---- z- [i ----!- ---- \ \~- .. . . . .. .1e_I
^4t
.
--
\
a 4-.Q I' .i.. I - . - l : - --- : -- : - : --1 \ j-.-
- i.
]- )-I.
·----
,_
.. '} - -1 - --l \ i-' ,-. --0 - \-.- ;. .. -: _. . ., i ,. .. .. , :. .:,, · i _, clo . -- ..I *-.---.--- r-- ."
__I..,,._-h'-"-."-.: .i' ... -i,.!.. '-- "
~.m.
-T...i....
O O'I cO r-_ *. . L) t- (') CM O
(6) *s.AnH 42eMol)l o suoLJJL sa[IS OLl4a[l3
1.4 Caveats
A. The reader should keep in mind several limitations associated
with comparative evaluations performed on the basis of the available
literature:
Comparison of alternatives is imprecise since critical
as-sumptions made by different authors are often unstated or
irreconcilable, particularly between very different
tech-nologies, e.g., solar energy conversion and burning solid
waste.
Published reports tend to be optimistic. Extrapolations to
Maine of reported pilot or demonstration plant experience
can only indicate gross costs or benefits. More detailed
design evaluations and specific engineering studies are
required before a firm commitment to any of the alternative
technologies can be made.
B. Uncertainty surrounds almost every facet of the analysis
per-formed in choosing alternative generation technologies to meet Maine's
electrical demand in 1986 and beyond. No absolute answers are
pos-sible in this situation. Usually, the wisest policy is to pursue
se-veral courses of action simultaneously. What should be avoided is the
closing off of options which may become very important in the
uncer-tain future.
C. To concentrate solely on one or more of the alternative
tech-nologies could conceivably leave Maine in a serious undercapacity
their hoped-for energy. The adverse consequences for Maine of such
undercapacity would be principally economic. However, both the
Fede-ral Power Commission (FPC, 1976, p. 5) and the National Electric
Reli-ability Council (NERC, 1976, p. 3) have warned of the possibility of
widespread capacity deficiencies by the mid-1980's. Such shortages
could lead to brownouts and blackouts. Utilities would probably
in-stall short procurement time generation in the form of gas turbines to
the extent possible. The present capacity of the manufacturers of gas
turbines is sized to meet normal growth requirements. The industry
would require several years to design, manufacture and install the
machinery required to increase gas turbine production. Gas turbine
installations would adversely affect the generation mix by poorly
matching generation characteristics to the load. The resulting mix
would contain too much intermediate and peaking capacity and too
little base load capacity. More light distillate oil would have to be
burned, if allowed by national energy policy.
Undercapacity has the effect of reducing reserve margins and the
associated carrying costs for capacity. Although there may be a
trade-off between the carrying costs for reserve margins and the costs
of reduced reliability levels, this issue is best addressed directly,
rather than "backed into" by a poor choice of technologies for
opera-tion.
D. Adverse environmental effects could also result from an
un-dercapacity situation. The urgency of bringing capacity on line might
create pressures for bypassing environmental hearings which require
time. Older, less efficient, and less environmentally sound plants
might have to be kept in service longer.
E. What happens if Maine concentrates only on the construction
of Sears Island #1? A commitment to the conventional coal alternative
does not altogether eliminate the possibility of an undercapacity
sit-uation, although it reduces its chances of occurrence. However, this
course of action could conceivably later have its own economic and
en-vironmental drawbacks. Several of the alternative technologies might
offer unique economic benefits which would be missed, such as
encour-aging new industries and increasing employment and, in the case of
conservation, reduced cost-of-living and doing business in Maine.
Re-liance on indigenous renewable energy sources would also help reduce
Maine's out-of-state energy payments. In some situations (e.g.,
ra-pidly rising coal costs), the alternative technologies might even
re-sult in lower consumer energy costs. Most of the renewable sources of
energy appear to be environmentally comparable to burning coal.
Choosing only the coal option could deny Maine the opportunity for
in-troducing new, possibly less environmentally harmful energy supplies.
F. Choosing to develop both the coal plant at Sears Island and
some set of alternative technologies also has associated problems.
The alternative technologies are more risky investments than a coal
plant, so someone will have to pay a risk premium to attract the
ne-cessary capital. If the alternatives are developed by the utility
in-dustry, either electricity consumers or electric utility stockholders
would pay the risk premium. If the alternatives fail or are not
eco-nomically competitive with conventional generation, someone must
ab-sorb the losses. Even so, it seems to be in Maine's best interests to
2.0 STATUS OF TECHNOLOGICAL DEVELOPMENT*
2.1 Principles of Operation
Our evaluation searched for technologies which could possibly be
substituted for Sears Island #1. Such technologies would have to be
capable of producing or conserving 600 MW of electrical power and
roughly 4 billion KWh of energy per year. In general either a few
large centralized facilities (e.g., biomass combustion power plants)
or numerous small decentralized facilities (e.g., wind turbines) offer
the best use of the characteristics of alternative technologies.
In the following discussions only the most promising form of each
technology will be considered. Thus, while it may be technically
pos-sible to erect a 1 KW wind turbine for every household, this
discus-sion would only consider the more likely design of several hundred 1-3
MW units. Furthermore, only the most promising of the candidate 1-3
MW wind turbine designs will be presented. Otherwise the list of
al-ternatives becomes unwieldy and the comparisons entirely
conjec-tural. The various appendices give more justification for the choice
of the following as the best prospective designs.
CONVERSION OF BIOMASS: Multiple harvesting in conjunction
with commercial logging and pulp operations would be used to remove
the presently noncommercial portions of the forest for use as fuel.
The fuel wood would be chipped in the forest and trucked to several
small, centrally located conversion plants. These plants would burn
*Note: The technologies were first examined for the intrinsic characteristics (capabilities, status of development and/or commer-cialization, environmental impact, and anticipated cost of generated electricity). In Section 4.0, the applicability of each technology to Maine is discussed.
the chips to produce steam for the generation of electricity. A plant
of about 50 MWe size appears to be optimal.
CONSERVATION: Utilities, industries, commercial
estab-lishments, and residential users would take action to reduce
elec-tricity consumption by foregoing demands and increasing the efficiency
of end use. Heroic changes in lifestyle are not considered.
Con-servation produces no electricity but might reduce the need for new
generation in 1986.
GEOTHERMAL ENERGY CONVERSION: In the absence of natural
wet or dry steam reservoirs, hot dry rock technology is needed to tap
any geothermal resources. Deep wells must be drilled, after which the
hot rocks would be fractured and water pumped through the cracks to
transfer heat to the surface. Depending on the temperatures involved,
the hot water would be used to vaporize water or another working fluid
to drive a turbine, generating electricity. Plant sizes on the order
of 100 MWe are considered.
OCEAN THERMAL ENERGY CONVERSION: Warm surface ocean water
would be used to vaporize a low boiling point working fluid to drive a
turbine, generating electricity. Cool ocean water, taken from depths
below 1500 ft, is used to condense the turbine exhaust. Floating
con-crete hulls with 100 MWe capacity are considered.
FUEL CELLS: Hydrocarbon fuels would be chemically combined
with air (oxygen), without combustion, to generate direct current
electricity. Power conditioning equipment would then produce 60 Hz
electricity for public use. Because modular design is basic to this
SOLAR ENERGY CONVERSION: Several solar technologies are
considered. At central station solar thermal plants area-extensive
mirror systems would focus sunlight on a central receiver-boiler to
develop steam. The steam would be used to generate electricity
imme-diately or the steam or generated electrical energy would be stored
for use when the sun was not available. Central plants on the order
of 100 MWe are considered. Central station photovoltaic plants would
utilize arrays of photovoltaic cells to instantaneously produce direct
current electricity. This would then be converted to 60 Hz
electri-city for public use. Central plants of 100 MWe are considered. Solar
space and water heating involves dispersed residence or
single-structure technologies. Either air or water would be circulated from
the solar collectors to the living area or hot water system. No
elec-tricity would be produced, but elecelec-tricity used for space conditioning
might be replaced by solar-derived energy, resulting in reduced demand
from conventional sources at those times when collectible sunshine was
available. Dispersed solar photovoltaic systems for small-scale
(single-structure) use would operate on the principles of the central
systems. Direct current from photovoltaic cells would be converted to
60 Hz electrical power to satisfy the demands of the user.
Storage technology is critical to most economic uses of solar
energy. The increased size of collection facilities to "charge" the
storage also places an economic burden on solar energy technologies.
CONVERSION OF SOLID WASTES: Municipal solid wastes would
be collected at a series of transfer stations and then transported by
truck to several central energy conversion plants. There, the solid
wastes would either be incinerated to produce steam for electricity
generation or processed into another form to be used as a
supplemen-tary fuel for coal- or oil-fired utility boilers. Incineration units
sized at about 50 MWe are considered.
STORAGE OF ENERGY: Storage devices would allow energy
col-lected or converted in one time period to be used in another, and
would result in more reliable and efficient operation of both
alterna-tive and conventional generation technologies. Dedicated storage
would be associated with a single conversion technology. Storage
could utilize thermal, pumped hydro, mechanical, or electrical
energy. System storage would store electricity from a variety of
sources. Storage facilities could be any size since their modular
units could be combined to form larger capacities.
WAVE ENERGY CONVERSION: Buoy-type systems or floating cams
could convert the kinetic energy of waves into mechanical energy to
compress air or pump water for eventual electricity production. Wave
energy systems would have to be moored off the coast with undersea
ca-bles for transmission of electricity to shore. The size of the
sys-tems would be limited by mooring and transmission considerations, and
would probably be on the order of 1-5 MW capacity.
OCEAN AND RIVERINE CURRENT ENERGY CONVERSION: River
cur-rents could be used to turn turbines for electricity production in a
manner similar to waterwheels. River current turbines would have to
be moored in the river and would require cable systems for energy
transmission to the shore. Unit sizes would be a function of river
WIND ENERGY CONVERSION: A tower-mounted, horizontal axis
turbine could convert the kinetic energy of the wind into rotational
energy to turn a generator to produce electricity. Proper siting and
storage would be critical to sustained, reliable electricity
produc-tion. Unit sizes from 1.5 MWe to 3 MWe are being considered.
2.2 Components of Alternatives
For most of the technologies there are critical new components
which are needed for successful commercial operation. In addition
there are other components which are essentially established,
off-the-shelf technologies. These are summarized in Table 2.1, along
with a list of the major anticipated technical problems and estimates
of the availability of the technologies.
2.3 Technical "Quantification"
For most of the technologies there is a shortage of adequate
ba-sic data about the available primary energy sources. The data which
are available have often been collected for purposes other than energy
assessments and, as a result, are incomplete or inappropriate. For
example, wind speed data have typically been collected near ground
level at airports (which are chosen for their low wind speeds). Such
data do not completely represent the elevated wind speed data which
would be found at an optimal wind turbine site. Collection efforts
for data on energy generation potential of wind, waves, currents, and
solar insolation in Maine would improve future assessments. Biomass
and solid waste production data are also needed on a more
site-specific basis. A particularly weak point in existing data is the lack of time-dependent information on a daily time scale.
E E 1- I--0) 03 C C E o 0 - _.J _.J a) I- . 0 0 Q a, 4- 4-a) 0) > C ) 0 2 __-j ina (U in r -0)n 4aEE In a)(1 22 -J o · ,I o 0 . 'oc 0 _ S.-2=0 in oo in C -- (i D'. .- eI~ ( r 4- 4J 4-4to A C C inu -- U54)( 0 . 0) i) 0e S.. 4) C C-E < E a
~~~0a)
Z Q oa C] V1 ' = .a- ) a a) c - 0 in triV7 in 0ro , . 4-0 o, . 4 - - ~-- U ) t-~,r) a O. 4. > E~~~~
=~
~~~~~~~m
( ·4 - ¢) , . 0*) . Q ) o a) .cC n 4-: o -~40 X C C 0u 00 00>
~~~~~~~~~~~~~a)
( >A 4 > ( >1a4 a) 0 0 4-- - 04-CL C " C 4-) a - ' : 0. 0. '- *U 4w w C C C 0. -3) u la 0 C .( 0 .C E~~~~ tn
~
· ,-0 i E, 0- EC .0 (A 0 CL 4 2 c ) cn~~
in O 00. a E) 0) S- E E 0 o i o4. .a o - a '. ' * n an - a 4 ~ n C ) a -~ 4 4n (A >,, >,_ 0 in --. 0~~~~~~~~~L (A :3( A . a) 0 n . 0 *-0 a -0 ip C 41 ° ro w > 4 4J ._ -Oin 04- .- (n 4- Q)0 c.i o C o c- a) '- - a ' ' o > ( n0 >: O ' cr .3 : 3 · . u- O -LIn sC al~~~~~~~~~-,---"~,
-~ J[ i (n DI I A x C la 0 ncv CE 4 F 2 .- ' C n 0 0 E 4 C i .- n a) 3 n>- ( (aU t s i in 4C Q S > co m n (A o_ n a) >' VI (A 4- -c S- W~:
*3 so o c in 4)- . a a) > > E E F2 E E U3 c4-
E
)
Lu*
a) Q0.)a *
a) S
- a) >, 4
uD
-*
U -C 4 S.. 4) m o u 5 +4) a) ,-4- S-+ - C) L4 0 (A_- Co.) *- * :3 w 4-I c C L u O u 'ain (a LAn v U L- c E Q) n o a) 4) u 0 la Io cS <W >, >>. >, r U >, 4)*_
a-0. .0 4) S- 0 +4-, : C '--0 0 In la OV S-.In J ;, c) CCO. 4_
E4) 5-a) t 0. 4C C) u L u L O_ o- E 0 0' a) - EaQ
ci 4. S-a) 4- x a) -4) S-u . a)w 4 S.- o a) E i 4 u
s>-4 * Ela 0.5- u u m ( CM u Cm > cn In 4 iV
M _a) E L. m _ Mntn Qa
.CinC ,-( 4-1- 4-E- .S.-. s en c * v In-#4-'5 *~~~~~~~~~~~~~~~~~~~~' n S.4- E -. >- nf-$. 41 + O0 o a n uc
cn)S C ') O 0 0 CC -'0 0 0 0o 0 cn4)0 I Q 3 0 VI~ : 0 E 0 0_ C : Cl) ~x 4 I ~ S.- L- t IL 0 4 : :C0a) 0 4 o 1 4C) 2 4-Q S- -*4-I
~~~~~~
0
cC L'i1,z
0L)-j
-J ; Lii I- -co Cii C.D 0 (23 -- J LJ L i -- J c: CD i.- _.) _J I-L.) 0 C) .) _C-) = C) I-) a,: W I-cC I-0 -U Lii C-, c.) I-C) C) C) 0. I-n :x -C) Ln-'o 4o- S.-a) 0. CL ox-I' 4)04 ) --.0...'E-C n~ 0 a 0. C) .-2 S.. a) - S-(U L 2-E E S-. S.-I c-5- 0) a) 0 e * C S.-la (U 0 S.. a) 2 E 5- I- 5-(D a) .5' a) * 0 4)O u (U S.. S.- a) . 0_ L a) in 0 in .C , S.-4) ,E-; (-i 0 .in 0 E E. S..a o) I I-- S.--0 IC a) E: Z .. a) 0 G a) 0. >1 0 4' 0 S.-0. _0 -,-So E 4-) 0r- . ~ · -o ~o5 n 5-.0.3
:, IT a) Ad(U C] > a) 0. 0 4. _40 S.-0. in o -a .0. S.- o 0 0. ~- o a)o -) (U 4 0 0 n) -' a 4-: Co m) *) S (s 0 . -(A (U 4) e~! -C a) .'4-c0 (U 0 Fly CA 4-aj E 0 0. 0 W a) J-0 0 r 0 0 : uo2 0 C 0 a) f-a) 4-' (U 4-'q7 a) aV 0 o C C O o O o o 0 E. -E 10 a) S. E SI -S. la 0sQ} ca ) S- 0r-S. c-'E Lit>S a = . CA to0
·,
:>0 0 -
"
4C) 0 C 0 S- c - S-S -E E E - o CL E o O C: C) .n 1- %-(1 * CA 1(-P%.r- L>o >r JZ: S-L U > C4 0 4 E la ._ ,a cl U O C cn m0 0L 04 CO CO W 0 a) IC L n t_ O 4) E ) E i - Ox aE
LE D
,vn
*c -3
CeC .- 0 O 0*-0 4) 5. 0. Sv ELL S =c2) E _-LAi !: C U) V) W LACJ 33
23 orC 4-J 'o S. O.r C) I-UC
.0 S -·- :O un E tO O -a. 0- 0J CC CL X O uL 0 0 4-) C 4s r-· .~ 0 -0 tn N 0 _ = 0 L.3 E f. a) 0 c0 o a s- 0 -* E o C C * L o0 X C.) O cn C) I00
o a 4-- 4-) a·J O4-4J -IJ C C =n O 4 C c 3 3 O C - -In In C C L LE E U U E E S S *_ o 0r 00 CO cn 90 S.-0 In C 0 E S-o u S 0 IU L la 4 a) c Z (1 s- o O o_ r- Eo 0 a -c.> 0a -r-0r 4. In C n 0 4 0 O e . 4 4-) N O 4 'U c 5 4 0) -)-
E
oC) aI E u, o >i 0 L 4 o N a) - y 4 -4C O m I r 0.. >4-o
N' In C) In 40 O I 0 QO 0-E 4--0 s-0 I0 'U s-0 0 L.) _ _I_ _I
_
_
For several of the technologies, there is a trade-off between the
cost and design complexity and the energy production of the
techno-logy. The added cost and complexity result from the necessity of
col-lecting and storing energy for those periods when the basic energy
source (e.g., sunlight, wind, or waves) is not available. Matching
generation and storage is in general a complex and critical problem
and is best done as part of specific design studies. For this report
an attempt has been made to consider storage with central station
so-lar thermal and central station soso-lar photovoltaic generation, in
or-der to facilitate their comparison as base load technologies. Energy
Costs for these technologies would be more attractive if they were
operated in a fuel saver mode. In general, adding storage increases
energy costs while making capacity ratings more reliable.
Capacity and energy estimates were prepared (Table 2.2).
Capa-city estimates were made for the rated (maximum) operating capaCapa-city
for the likely unit design of each alternative technology. Energy
es-timates are based upon the rated capacity and typical capacity
fac-tors. Also given is the approximate number of units of each
techno-logy which would be needed to replace the contribution of Sears Island
#1.
The figures in Table 2.2 are annual averages since shorter time
scale data are generally unavailable. Annual averaging masks daily
and seasonal problems such as reduced insolation, wind speed
varia-tions, and so forth. To guarantee adequate year-long capacity and
energy production would require oversizing several alternative
CAPACITIES Technology Biomass Conservation b Ocean Thermal Geothermal Fuel Cells AND ANNUAL Unit Rated Capacity (MWe) 50 100 100 20 Table 2.2
ENERGIES FROM ALTERNATIVE TECHNOLOGIES
Energy Unitsa Unitsa
of Rated to Provide to Provide
Unit 600 MWe at 3.7 x 109 KWh (109 KWh) Rated
Capacity
__ _ .307 12 12 .614 .614 0.131 6 6 30 6 6 29 SolarCentral Station Thermal 100
Central Station Photovoltaic 100
Space & Water Heating
NAC Dispersed Photovoltaice .006 .614 .614 2.9x10- 5 3.1xlO-5 6 6 NAC See note d Solid Wastes Storageb Waves Currents Wind 50 1.5 1 1.5-3.0 .360 .005-.026f .001f .005-.010f
aIgnores daily and seasonal variation.
bDoes not produce any energy; replaces need
CProvides thermal not electrical energy; may be energy
dCapacity depends strongly on assumptions about
eBased on study for Arizona.
fStorage not included.
NA: not applicable. 25
for capacity
substituted for electrical
storage. 6 6 130,000 117,000 12 10 600-120 600 400-200 7 1 0-1 4 0f 3700f 740-370f -·__
Estimates of the impact of conservation on electricity demand are
highly unreliable; in addition, some conservation measures tend to
re-duce only peaking and intermediate capacity requirements, rather than
base load requirements. We estimate that an all-out conservation
ef-fort could theoretically eliminate 325 MW of capacity requirements and
2 billion KWh/yr of energy demand by 1986.
This is what could be saved only if the complete and sustained
conservation effort were implemented by the government on a national
basis. (Electricity customers in Maine cannot be asked to freeze
slowly in the near dark while the rest of the nation lives the "good
life.")
If a utility system has excess base-load energy, storage can be
employed at the system level to reduce or postpone new peaking and
in-termediate capacity requirements by making better use of existing base
load generation. System level storage in itself does not directly
serve system energy demands although it can provide additional
capa-city. Since system level storage depends on excess base load energy
to provide intermediate and peaking energy and capacity, it is not an
3.0 ENVIRONMENTAL EFFECTS
Appendix L (Environmental Impacts) presents the results of a
special literature review on the comparative environmental impacts of
the alternative technologies. Some authors have found the total
im-pacts of technologies such as burning solid wastes, burning forest
wastes, and geothermal energy conversion to be comparable to the
im-pacts of coal-burning plants.
The alternative technologies for electricity production are not
environmental panaceas. Several have as yet unresolved environmental
problems which could have a serious impact on Maine. Others, when in
operation, have minimal environmental impact.
Many of the alternative sources considered do rely upon
re-newable primary energy sources and avoid most of the environmental
air, water, and land pollution impacts of conventional coal, oil, and
gas generation. With adequate planning and good design, it appears
that most of these renewable primary energy resources can be utilized
indefinitely with no long-term environmental effects comparable to the
potential problems of coal mining and utilization. The construction
of the facilities requires materials and manufactured products for
which environmental impacts must be considered. There are substantial
economic costs associated with even some of the least environmentally
damaging technologies. Maine must decide if the benefits warrant the
additional costs.
The major impacts of the alternative technologies considered in
this report are given in Table 3.1. Conservation has the least
im-pact, closely followed by the dispersed solar energy-derived
technolo-gies, (thermal, photovoltaic) wind, current and wave conversion.
Cen-tral solar facilities and ocean thermal facilities may be in about the
middle. At the high impact end are the burning of solid waste, and
Table 3.1
SUMMARY OF ENVIRONMENTAL IMPACTS OF ALTERNATIVE TECHNOLOGIES
cr~~(
Energy Resource Depletion Conversion Area
Transmission Area Water Consumption Use of Air Space
Air Pollution - Particulate Air Pollution - Gaseous Water Pollution Construction Activity Heavy Metals/Toxic Thermal Discharge Solid Waste Visual Intrusion Noise Public Health Transportation TOTALS :E c. 1 3 3 1 3 1 1 1 3 1 1 1 3 1 1 1 -1 CD 1 3 3 1 1 1 1 1 4 1 1 1 4 1 1 2 27 01
(b
uD 1 4 3 1 1 1 1 1 4 1 1 1 4 1 1 2 28 C)0
CD La 1 3 2 1 1 1 1 1 3 1 1 1 2 1 1 1 220
U) _., CD U) (D 2 3 3 4 1 4 3 3 3 3 4 2 3 3 2 ) SOLAR c)0
0
o
1 3 1 1 1 1 1 1 2 1 1 1 2 1 1 1 20 I -_. 1 3 1 1 1 1 1 1 2 1 1 1 2 1 1 1 20 ,) :00
c-0
1 4 3 1 3 1 1 1 3 1 2 1 3 1 1 1 28Impact Rating: 1 - negligible 2 - slight
3 - moderate 4 - severe
O
indicates ratings for which the more optimistic value of a spread was chosen.29 G) O
0
CD 01 __J.. 3 3 3 3 4 2 3 2 3 2 1 C40
U) U) 2 4 3 3 1 4 3 3 3 2 4 2 3 3 1C
C fD U) 4 2 2 2 1 1 1 1 3 1 2 1 2 1 1 1 26 n C--c') =r 1) -S 01 3 ml 1 4 3 2 3 1 1 1 3 1 3 1 3 1 1 1 300
CD o 1 --I 3 01 2 4 3)3
)l 2 3 1 2 1 1 ) 2 2 30 C-)0
ID 1rt
-.0
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 164.0 APPLICABILITY TO MAINE
Each of the technologies was examined to identify special
re-quirements for its satisfactory production of electricity in Maine
(for example, wind speed regimes, solar insolation levels, etc.).
When possible, the ability of Maine to provide these requirements was
quantified and estimates were made of the resulting available
electri-cal capacity and energy. This approach is necessarily subject to the
possibility of large errors because the performance of the
technolo-gies is highly site-dependent. Specific siting and design studies
were beyond the scope of this evaluation.
In an attempt to draw reliable conclusions about the
alterna-tives to construction of the Sears Island 600 MWe plant, a best case
approach was used to evaluate the uncertain performance information of
the alternative technologies. The maximum electrical output of each
technology under best case assumptions was determined. This number
could then be compared with the minimum requirements for replacing the
Sears Island plant. In some cases (e.g., ocean thermal energy)
Maine's total resources were clearly too limited to allow operation of
the alternative technology.
In other cases (e.g., wind energy) it is conjectural to say what
Maine's resources are, but statements can be made like, "Over 2000
one-MWe wind turbines would be needed to produce 95% reliable 600 MWe
capacity." The reader is cautioned to note that whether 2000 one-MWe
wind turbines can actually be sited, licensed, and built by 1986 is
only partly a technical question. Considerable institutional and
of wind turbines would be possible. The numbers given in the
fol-lowing two sections represent our estimates of the best possible
per-formance, without regard to the non-technical barriers which might
exist or arise.
4.1 Special Requirements
The special requirements discussed in this section are not
tech-nological requirements, such as the development of manufacturing
meth-ods for the mass production of wind turbine blades. Rather, the
fol-lowing special requirements encompass the basic energy and raw
ma-terial needs of the alternative technologies (Table 4.1).
With two exceptions, all of the technologies could clearly
con-tribute to the electrical energy supply in Maine.
A. Ocean thermal systems will not operate in the relatively cold
and shallow waters off the Maine coast.
B. Geothermal systems must rely upon hot dry rock technology
be-cause Maine has no known hydrothermal or geopressured resources.
No data are available on the extent and characteristics of
Maine's hot dry rock resources.
4.2 Estimates of Energy and Capacity
The fact that the remaining technologies can theoretically be
operated in Maine is interesting but may be only academic. More
im-portant is the question of how much energy and capacity can be
pro-duced or saved by the technologies.
Table 4.1
SPECIAL REQUIREMENTS FOR ALTERNATIVE TECHNOLOGIES
Technology Requirements Availability in Maine
Biomass Biomass supply 90% forested; collection
could be a problem;
compe-tition from pulp industry. Conservation Mandatorv Measures
--Ocean Thermal Geothermal Fuel Cells Solar Energy Solid Wastes Storage Waves Currents Wind
and Public Support
Thermal gradient
totaling 150C
Hot dry rocks
Clean gaseous or liquid fuels from coal Solar insolation Solid waste supply Suitable sites Coastal Access River Sites High Wind Speeds None Unknown None
Low insolation levels; a(
verse weather
Small, rural population;
collection problems
Limited
300-400 miles of open wal
coastline; fishing inter*
ference
Numerous; icing and ship
interference
Coastal reoions and moun
I-ter
5.0 ECONOMICS
Because there is, in general, little or no commercial experience
with the alternative technologies studied here, estimates of their
cost are necessarily approximate. In many cases there are no data
whatsoever on the costs of certain components or operations.
The cost data which exist are very sensitive to the assumptions
made in their derivation. Unfortunately many of those assumptions are
not reported in the literature, making it necessary for us to
inter-pret the available data in order to draw even rough comparisons. The
technical appendices have noted these assumptions and include
inter-pretations when appropriate.
5.1 Economic Assumptions
In order to allow at least an order of magnitude comparison of
the economics of the various alternative technologies, a common
eco-nomic methodology was applied. The numbers which this methodology has
produced are probably low in an absolute sense but should be
repre-sentative of the relative costs of the alternatives. Only a specific
design study including issues such as siting, licensing, transmission,
and environmental impact minimization could provide accurate absolute
cost data. Even then, costs will be no more reliable than the
avail-able performance data, most of which are still based on prototype
units that are still in the experimental stages or "paper" designs.
Our basis of cost comparison of the electricity produced by the
various technologies has been the cost in mills/KWh, at the output
terminals of the generation plant, . A comparison year, 1986, was
chosen. All reported costs have been converted to 1986 dollars by
using an escalation rate of 5% per year. Escalation was not
compoun-ded.
No attempt was made to determine a lifetime cost for operating
the various technologies. Costs after 1986 were not compared as it is
considered to be too far into the future for numbers to make sense.
The quality of the economic and operating data simply does not justify
adding another set of assumptions to develop lifetime costs. If a
specific design study were undertaken, then such a year-by-year
an-alysis should be performed.
Electricity costs were found by dividing the total annual
ca-pital and operating costs by the energy produced in one year.
Matura-tion problems, which might cause low energy producMatura-tion during the
first few years of plant operation, were ignored. Whenever
as-sumptions were necessary, optimistic but reasonable asas-sumptions were
used, so the resulting energy costs are probably as low as possible.
In most cases, it was impossible to quantify the effects of mass
pro-duction of equipment and services on the 1986 prices, so this effect
is not included. No attempt was made to determine secondary economic
effects (increased employment, sales of goods and services in Maine,
etc.) of the alternative technologies as a possible credit against
their costs.
Annual capital costs were determined by converting the capital
investment for an alternative technology, say a wood burning plant,
into an annual levelized charge. A levelized fixed charge rate (LFCR)
of 18% was used for all the alternatives and reflects the annual cost
of owning a capital investment. Debt service, equity return,
depreci-ation, state and local income taxes, investment tax credit, insurance,
Service life strongly affects the calculation of LFCR, with
im-portant implications for the evaluation of the alternative
technolo-gies. Because they are new technologies, their service life can only
be estimated and will certainly vary from one technology to another.
Given this uncertainty and the uncertainties of the basic economic
da-ta, there seemed to be little justification for adding the refinement
of individually calculated LFCR's. Over a range of posssible service
lives (10-30 years), and using the assumptions of Table 5.1, the value
of the LFCR changed between roughly 15% and 19%.
Table 5.1
LEVELIZED FIXED CHARGE RATE ASSUMPTIONS
Bond Interest 9.75%
Bond Fraction 52.00%
Common Stock Interest 14.50%
Common Stock Fraction 34.00%
Preferred Stock Interest 10.00%
Preferred Stock Fraction 14.00%
State Income Tax 7.00%
Federal Income Tax 48.00%
Investment Tax Credit 10.00%
Investment Tax Credit Fraction 75.00%
Property Tax, Insurance 1.50%
Service Life - N 10-33 years
Allowance for funds used during construction (AFUDC) was not
in-cluded in the costs calculated for the technologies. Depending on the
length of the construction period these could increase the capital
charges by as much as 30%. If this increase were included instead in
the LFCR, LFCR would range between 19% and 24%. An LFCR of 18% was
arbitrarily chosen as an optimistic but representative LFCR.
Operating costs were taken directly from the literature,
calcu-lated from known components of plant operation, or estimated as a
fraction of plant investment.
Energy generated was based on the rated capacity of the
alter-native technologies and their estimated capacity factors. In most
cases there is no commercial experience on which to base forced outage
and maintenance estimates.
5.2 Cost of Electricity
Based on the optimistic approach outlined in Section 5.1, 1986
costs of electricity from each of the alternative technologies were
derived (Table 5.2). These costs should be considered as best case
numbers, (i.e., "most optimistic"), in the sense that it is expected
that commercially installed units will not provide electricity below
these costs, even with reasonably likely technological and
manufactu-ring breakthroughs. Actual commercial costs may turn out to be higher
by a factor of two or more.
Conservation is one method that can actually pay consumers for
their investment. The economics of conservation vary according to the
measures taken and the cost of the electricity.
Storage costs have two components: the cost of the stored
energy, which depends on its generating source, and the cost of the
storage equipment. The incremental storage equipment costs are the
same for all generating units, so the determining factor is the cost
of the stored energy. Base load generation is needed so that the
energy taken from storage can be economically competitive with
Table 5.2
OPTIMISTIC ELECTRICITY COSTS FROM ALTERNATIVE TECHNOLOGIES
Technology Range of Busbar Electricity Costs Mills/KWha in 1986 dollars
Conversion of Biomass 50 - 70
Conservationb
Ocean Thermal Energy Conversion 70 - 90
Geothermal Energy Conversion 25 - 80
Fuel Cells 55 - 70
Solar Energy Conversion
Central Station Thermal 600 - 800
Central Station Photovoltaic 346 - 3000C Space Heating and Coolingd
Dispersed Photovoltaice
Conversion of Solid Wastes 40 - 90
Storage of Energyb
Wave Energy Conversionf 25 - 116
Ocean and Riverine Current Energy Conversion 200 - 260
Wind Energy Conversion 65 - 100
aThese figures do not include AFUDC. Depending upon fuel costs, if AFUDC is included, the busbar cost of electricity can increase up to 30%
bCosts depend on the cost of the energy conserved or stored.
CCost depends on assumptions made about projected reductions in photovol-taic cell costs.
dMay be economic for average homeowner (depending upon his alternatives). eMay be economic if photovoltaic cell costs fall drastically, but utility
backup supply still needed.
flow by as much as a factor of 3 due to missing costs.