3D simulation of Industrial Hall in case of fire

Benchmark between ABAQUS, ANSYS and SAFIR

Cajot L.G. & Vassart O. PROFILARBED Research, Lux

O'Connor M. & Shenkai Y. Corus UK Limited

Fraud C. & Zhao B. CTICM, Fr De la Quintana J. & Martinez de Aragon J.

Fundacion LABEIN (SPAIN)

Franssen J.M. & Gens F. University of Liège, B

INTRODUCTION

For simple storey buildings, the structural behaviour in case of fire is relevant only for the safety of the firemen. The protection of occupants and goods is a matter of fire spread, smoke propagation, active fire fighting measures and evacuation facilities. Brittle failure, progressive collapse and partial failure of façades elements outwards may endanger the fire fighters and have to be avoided. In order to deal with such an objective, the simulation softwares has to cover the 3D structural behaviour including membrane and restrained effects as well as the failure mode so that post-local failure stage can be analysed. Such calculation models (ANSYS, ABAQUS and SAFIR [1]) have been compared true a benchmark. In this benchmark, two different users used ABAQUS.

BENCHMARK DEFINITION

This benchmark is based on the following structure :

IPE 450 (S355) IPE 500 (S355) 20m 20m 5m 0,5m v1 = 4700 N/m h1 = 1300 N/m

The material laws for thermal and mechanical properties come from the EC3 Fire parts [2]. For the mechanical properties, the strain hardening is not considered.

All the profiles will be assumed class 1 section during the fire.

For the calculation of the temperature in the steel, an ISO fire curve is considered [3].

For the thermal transfer, convection and radiation have been considered true the following parameters: α = 25 W/m2K

ε = 0.5

No shadow effect has been taken into account.

The simple calculation method of EC3 [2] will be used to evaluate the temperature curves of steel members (IPE 450, IPE 500). This lead to an uniform distributed temperature in the cross sections.

(2)

The study is composed of 4 parts :

a double frame in 2 dimension a double frame in 3 dimensions partially maintained in the third dimension

a full study in 3 dimensions with more than one double frame

a full study in 3 dimensions with more than one double frame and hot purlins

RESULTS IN 2 DIMENSIONS

• Evolution of the horizontal and the vertical displacements at different places (Nodes a to c) with respect to time :

Horizontal displacement of the node a

0 300 600 900 1200 1500 1800 -0.25 -0.20 -0.15 -0.10 -0.05 0.00 Displacement [m] Time [sec]

Horizontal displacement of the node c

0 300 600 900 1200 1500 1800 -0.010 0.000 0.010 0.020 0.030 Displacement [m] Time [sec]

Structure submitted to fire

a b c

Safir Abaqus Labein Ansys Abaqus Corus

Vertical displacement of the node b

-1.80 -1.60 -1.40 -1.20 -1.00 -0.80 -0.60 -0.40 -0.20 0.00 0.20 0 300 600 900 1200 1500 1800 Time [sec] Displacement [m]

(3)

After analyse of these different figures it is expected that the left frame collapses towards the inside of the building. Unfortunately, the statical finite element calculation stops before the node a (top of the heated column) had come back to the inside part of the building.

In order to avoid this annoyance, the possibility to perform a dynamic analysis of the structure has been studied with the different softwares [4]. Dynamic approach has been applied to the full 3D calculation.

• Evolution of the normal force with respect to the time at the connection between the central column and the beam under fire :

Beam Axial Force

20000 25000 30000 35000 40000 45000 0 300 600 900 1200 1500 1800 Time [sec] Force [N]

This figure shows that until the end of the simulation, the hot part of the structure pushes on the cold part (which remains stable) and the value of this force is not bigger than the effect of the wind in service condition.

• Drawing of the deformed structure without amplification of the deformations :

This figure shows that the failure mechanism is a beam mechanism. The right frame, which is not under fire, remains at its initial position and does not suffer from the left frame collapse.

RESULTS IN 3 DIMENSIONS One frame in 3 dimensions

This case represents the same structure as the one in 2 dimension, but the out-of-plane displacements are here allowed. For recall, the supports of the structure are made of hinges, it means that some fixations in the third dimension must be added (the 11 fixations in the third direction are shown on the next figure). These restrains are provided, in the reality, by the purlins.

The only initial deformation is in the plan XY according to the Y axis. The maximum value is L/1000 = 0.01 m. There is no initial deformation for the column because moment at the top should be sufficient to initiate displacement perpendicular to the plan XZ.

(4)

So the two next figures show the fixed points in the third dimension Y and a scheme of the initial deformations:

• Evolution of the horizontal and the vertical displacements at different places (Nodes a to d) with respect to time :

As you can see in the following figure, the node d is located at 1/4 of the length of the first beam:

Horizontal displacement Node a

0 200 400 600 800 1000 1200 1400 -0.25 -0.20 -0.15 -0.10 -0.05 0.00 Displacement [m] Time [sec]

Vertical displacement Node b

-0.30 -0.25 -0.20 -0.15 -0.10 -0.05 0.00 0.05 0 200 400 600 800 1000 1200 Time [sec] Displacement [m]

Horizontal displacement Node c

0 200 400 600 800 1000 1200 -0.005 0.000 0.005 0.010 0.015 0.020 0.025 0.030 Displacement [m] Time [sec]

Displacement in third axis Node d

-0.01 0 0.01 0.02 0.03 0.04 0.05 0.06 0 200 400 600 800 1000 1200 Time [sec] Displacement [m]

The collapse of the structure occurs some minutes before the 2D analysis due to the lateral buckling of the beam under fire.

a d b c

(5)

• Evolution of the normal force with respect to the time at the connection between the central column and the beam under fire and at the connection of the central column and the beam without fire :

Beam Axial force

25000 30000 35000 40000 45000 0 200 400 600 800 1000 1200 Time [sec] Force [N]

The axial forces applied on the cold part of the structure are on the same order of magnitude than the 2D analysis.

• Drawing of the deformed structure with amplification of the deformations :

(6)

In 3 dimensions with more than one frame

The frame is now included in a full 3D structure with other parallel frames connected to the first one by purlins. As in the precedent cases, the only central left frame is heated.

The initial deformations are the same ones as at the preceding point and are applied only to the central double frame.

The 3 displacements (X, Y, Z) are the same for the purlins and for the beam.

For the rotation, the rotation around the Z axis are the same for the beam and for the purlins because the purlins are fixed by 2 bolts on the beam. But the rotation around the X axis, Y axis and the warping are free between the purlins and the beam.

The structure is maintained in several points to simulate the presence of wind bracing. For the loads, every purlins are loaded to have a simulation closed to the reality.

• Evolution of the horizontal and the vertical displacements at different places (Nodes a to d) with respect to time :

As you can see in the following figure, the node d is located at 1/4 of the length of the first beam :

Horizontal displacement Node a

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 -0.30 -0.25 -0.20 -0.15 -0.10 -0.05 0.00 Displacement [m] Time [sec]

Vertical displacement Node b

-0.20 -0.15 -0.10 -0.05 0.00 0.05 0 2000 4000 6000 8000 10000 Time [sec] Displacement [m]

Horizontal displacement Node c

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 -0.005 0.000 0.005 0.010 0.015 0.020 0.025 0.030 Displacement [m] Time [sec] 20 m 20 m 7.5 m 7.5 m 7.5 m 7.5 m a b c d

(7)

Displacement in the third axis Node d -0.5 -0.4 -0.3 -0.2 -0.1 0 0.1 0 2000 4000 6000 8000 10000 Time [sec] Displacement [m]

The collapse of the structure is not really visible. Progressively, the loads applied to the central frame are transferred to the neighbouring frames, and finally the two neighbouring frames through the purlins withstand the central frame. That explains why the reached time is greater in this case than in the 3D case with only one frame. This phenomenon is due to the fact that in this case, the purlins remain cold.

• Evolution of the normal force with respect to the time at the connection between the central column and the beam under fire and at the connection of the central column and the beam without fire :

Beam Axial Force

0 10000 20000 30000 40000 50000 60000 70000 80000 0 2000 4000 6000 8000 10000 Time [sec] Force [N]

• Drawing of the deformed structure with amplification of the deformations = 10X : Safir Abaqus Labein Ansys Abaqus Corus

(8)

In 3 dimensions with more than one frame and with hot purlins

The structure and the hypotheses are exactly the same than in the precedent point but the number of hot profiles is different, the purlins connected to the heated frame are also affected by the fire.

In a first step, statical analyses were made using the different softwares. But a lateral buckling of a purlin occurs after approximately 790 seconds (see following figures). This event explains why the static analysis stops at this time. The dynamic analysis allows following this buckling and so that post-local failure stage can be analysed.

-0.05 0 0.05 0.1 0.15 0.2 0.25 0.3 0 200 400 600 800 1000 1200 1400 Time (s)

Out of plane displacement

from purlin (m)

As you can see in the following figure, the node d is located at 1/4 of the length of the first beam :

Horizontal displacement Node a

0 200 400 600 800 1000 1200 1400 -0.5 0.0 0.5 1.0 1.5 2.0 Displacement [m] Time [sec]

Vertical displacement Node b

-5 -4 -3 -2 -1 0 1 0 200 400 600 800 1000 1200 1400 Time [sec] Displacement [m]

Horizontal displacement Node c

0 200 400 600 800 1000 1200 1400 -0.03 -0.02 -0.01 0 0.01 0.02 0.03 Displacement [m] Time [sec] a b c d

Safir Abaqus Labein Ansys Abaqus Corus

-0.05 0 0.05 0.1 0.15 0.2 0.25 750 752 754 756 758 760 762 764 766 768 770 Static analysis Dynamic analysis

(9)

displacement in the third axis Node d -4 -3.5 -3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1 0 200 400 600 800 1000 1200 1400 Time [sec] Displacement [m]

• Evolution of the normal force with respect to the time at the connection between the central column and the beam under fire and at the connection of the cold frame and the purlins under fire :

Beam Axial Force Node c

-20000 -10000 0 10000 20000 30000 40000 50000 60000 70000 0 200 400 600 800 1000 1200 1400 Time [sec] Force [N]

Beam Axial Force Node e

-60000 -40000 -20000 0 20000 40000 60000 0 200 400 600 800 1000 1200 1400 Time [sec] Force [N]

The evolution of the normal forces in the purlin at point e shows the instantaneous buckling at approximately 800 seconds. When the purlin buckles the normal force falls. That physical phenomenon made the convergence not possible for simulation without activate the dynamic approach. At the final time, the hot part of the building pulls on all the cold parts but the value of this force remains acceptable to not endanger this part.

c

e

(10)

• Drawing of the deformed structure without amplification of the deformation :

y

This figure shows that we can now simulate the behaviour of the global structure until the complete failure and very large displacements.

CONCLUSION

This paper has presented a comparison between different FEM softwares (ABAQUS, ANSYS and SAFIR) analysing 3D structures. Some benchmarks were realised in the past to compare different softwares [5] but always simulations in two dimensions. Some new regulation imposed to predict the failure mode and to verify the non-progressive collapse. So that 3D model are required. This benchmark shows that the three softwares give close results for the three dimensional analysis. In the last simulation, the dynamic analysis has enable to analyse the structural behaviour after the buckling of the purlins so that post-local failure stage could be analysed.

By means of theses three softwares, it’s now possible to simulate the complete failure mechanism, to predict the influence of a local failure on the global behaviour of the structure and to follow eventually the progressive collapse. Therefore the resistance time is now really determined where in the past many numerical failure corresponding to local failure were interpreted as resistance time of the whole structure.

REFERENCES

[1] SAFIR , A Computer Program for Analysis of Structures Submitted to the Fire, University of Liège, Department Structures du génie Civil, Service Ponts et Charpentes (2000)

[2] EC-3 prEN 1993-1-2, European Prestandard Draft, Eurocode 3 : “Design of steel structures“,

Part 1.2 : Structural fire design, European Committee for Standardisation – CEN, Brussels

(2001)

[3] ISO 894-1, Fire-resistance tets – Elements of buildings construction, Part 1: General

requirements, ISO (International Organisation for Standardisation), Geneva

[4] “Fire Safety of Industrial Halls and Low-rise Buildings : Realistic Fire Design, Active Safety

Measures, Post-local failure simulation and Performance Based Requirements”, ECSC

Research 7210-PA/PB/PC/PD/378

[5] J.B. Schleich, L-G. Cajot, J. Kruppa, D. Talamona, W. Azpiazu, J. Unanue, L. Twilt, J. Fellinger, R-J. Van Foeken, J-M. Franssen, “Bucking curves of hot rolled H steel sections

submitted to fire”, ECSC Research 7210-SA/316/515/618/931, Final report EUR 18380 EN,

Références

Documents relatifs

As a consequence, the two piles are controlling the behaviour of this structure and despite its dimensions (44 m length x 13 m wide x 49 m height) the longitudinal and

But in the case when individual components are highly reliable (in the sense that failure rates are much smaller than the repair rates), this often requires a very long computation

L’archive ouverte pluridisciplinaire HAL, est destinée au dépôt et à la diffusion de documents scientifiques de niveau recherche, publiés ou non, émanant des

The achieved load carrying capacity of the compressed column in FEM corresponds closely to the maximum load recorded in the experiment (values taken from three attempts)..

Fires are a detriment factor in many type of industries and constitutes a potential source of human loss, equipment damage and environmental impact and as the oil

Analysis of high-SO 2 events revealed that such occasions were associated with northeasterly winds at AECI and Athlone, with both prevailing wind directions at Southern Works, and

M Size of memory of agent’s farming strategies and practices 10 F0 Proportion of small-farm farmers among all farmers 0.3 F1 Proportion of medium-farms farmers among all farmers

Metabolic studies to assess whole body palmitate oxidation and insulin sensitivity, muscle biopsies for mitochondrial palmitate oxidation, diacylglycerol, fatty acyl Co-A and fatty