Publisher’s version / Version de l'éditeur:

Canadian Acoustics, 34, September 3, pp. 92-93, 2006-09-01

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

NRC Publications Archive

Archives des publications du CNRC

This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

The Effect of ancillary volume on sound transmission measurements

using ASTM standard test method E336

King, F.; Nightingale, T. R. T.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

NRC Publications Record / Notice d'Archives des publications de CNRC:

https://nrc-publications.canada.ca/eng/view/object/?id=60865130-5555-4341-a512-bf0c61dbd63d https://publications-cnrc.canada.ca/fra/voir/objet/?id=60865130-5555-4341-a512-bf0c61dbd63d

(2)

http://irc.nrc-cnrc.gc.ca

T he Effe c t of a nc illa r y volum e on sound

t ra nsm ission m e a sure m e nt s using AST M

st a nda rd t e st m e t hod E3 3 6

N R C C - 4 5 6 0 6

K i n g , F . ; N i g h t i n g a l e , T . R . T .

A version of this document is published in / Une version de ce

document se trouve dans: Proceedings of Acoustics Week in

Canada, Canadian Acoustics, v. 34, no. 3, Sept. 2006, pp. 92-93

(3)

THE EFFECT OF ANCILLARY VOLUME ON SOUND TRANSMISSION

MEASUREMENTS USING ASTM STANDARD TEST METHOD E336

Frances King, Trevor R.T. Nightingale

Institute for Research in Construction, National Research Council, Ottawa, Ontario, Canada K1A OR6

1. INTRODUCTION

The ASTM Standard E336-05 provides methods to assess the airborne sound isolation between a source and receiving room. In certain field situations, the determination of what constitutes the source or receiving room and its volume may not be obvious. An example is a living room (principal volume) connected to a kitchen (ancillary volume) through an opening in the wall separating the two, and the party wall under test is a surface of the living room (principal volume). Some judgment may be required to define the volume and where the sound field of the “room” should be measured. The Standard requires that the ancillary volume be disregarded if the average sound pressure level in the ancillary volume is 6 or more decibels below the average level in the principal portion of the source or receiving room to which it is coupled at all measurement frequencies. Otherwise, the ancillary volume shall be included as part of the measurement space. This paper investigates the

suitability of this criterion.

2. MEASUREMENTS

AND

RESULTS

The basic premise was the Apparent Transmission Loss (ATL) should be invariant of the coupled ancillary volume. Thus, the appropriate measurement procedure is the one that best approximates the (reference) ATL measured when there was no coupled ancillary volume. To evaluate this and arrive at the recommended measurement procedure, different field scenarios were simulated using the four-room Flanking Transmission Facility at the NRC/IRC. (See sketches of Figures 1-3). The volume of the rooms ranged from about 35 to 50 m3. In Figures 1-3 the ATL was computed for both directions between room pairs AC and BD using sound field measurements of the principal volume only. The wall between C and D (lower horizontally separated rooms) was systematically opened up from 0%, 8%, 17%, 36% to 100% to increase the coupling to the ancillary volume. Absorption was added to one of the lower rooms to simulate heavy furnishings.

Ancillary Volume Coupled to Source Room has only

minimal effect on the ATL and this is largely independent of the size of the opening between the source and ancillary volumes. Although Figure 1 shows the case with an absorptive source room (worst case), similar results were observed when either ancillary or principal source volume

was highly absorptive (reverberation time, RT, ~ 0.4 s) or when both were not (RT > 1.0 s).

Ancillary Volume Coupled to Receiving Room will result

in an overestimation of the ATL if receive room

measurements are made only in the principal volume. The results shown in Figure 2 are typical of when both receive and coupled ancillary volumes are not highly absorptive. By comparing Figures 2 and 3, one can see the overestimation is greater when the principal volume is highly absorptive. It should be noted that effect is considerably less when the ancillary volume is highly absorptive relative to the receive room principal volume. For all cases considered the overestimation increased with opening size.

3. DISCUSSION

AND

CONCLUSIONS

The practical approach is to select the direction of measurement such that the ancillary volume, if present, is coupled to the source room. However, when the receive room is coupled to the ancillary volume a criterion is required to minimize the effect of an ancillary volume. Figures 4 and 5 (updated on Nov. 1, 2006) show when there is an ancillary volume coupled to the receive room, the difference in the ATL with and without (reference) an ancillary volume, is a function of two parameters. First is space-average level difference between the principal and ancillary volumes. Second is whether sound field

measurements include the ancillary volume. There is a data point for each one-third octave in the range 125-4kHz. The figures show that there is practically no ATL overestimation for two conditions, 1.) small level difference between the coupled volumes and the sound field averaged over both and the combined volume is used in calculations, 2.) large level difference between the coupled volumes and the sound field in principal volume is used in the calculations. For

intermediate conditions, the overestimation is appreciable and should be minimized. For the room volumes and reverberation times considered here, the regression lines suggest, when the difference in space average level between the principal and ancillary volumes is greater than about 6dB estimates of ATL can be obtained using sound field measurements restricted to the principal volume. However, when difference is less than 6 dB both principal and ancillary volumes must be used.

(4)

-2 -1 0 1 2 3 4 5 6 63 12 5 25 0 50 0 1k 2k 4k Frequency, H Dif fer en ce fro m ref er en ce AT L, 0% 8% 17% 36% 100% A B D C S ourc e R oo Ancillar V olum R ec eivin R oo

Figure 1: Effect of an ancillary volume and percent opening when coupled to a heavily furnished source room

-2 -1 0 1 2 3 4 5 6 63 125 250 500 1k 2k 4k Frequency, Hz Differe nce fro m refer enc e ATL , d B 8% 17% 36% 100% A B D C Source Room Ancillary Volume ReceivingRoom

Figure 2: Effect of an ancillary volume and percent opening when coupled to a receive room.

-2 -1 0 1 2 3 4 5 6 63 125 250 500 1k 2k 4k Frequency, Hz Di ff e re nc e f rom ref e renc e A T L, dB 0% 8% 17% 36% 100% A B D C Source Room Ancillary Volume ReceivingRoom

Figure 3: Effect of an ancillary volume and percent opening when coupled to a highly absorptive receive room.

In both cases, the room volume used in the calculation is consistent with the space where the sound fields were measured. Since there is a tendency to overestimate the ATL, an alternate procedure would be to compute the ATL twice – first using measurements made in the principal volume, and second using measurements in the combined volumes – and take the lower of the two values. For rooms typical of most apartments (volume 35-50 m3 and

reverberation times 0.4 – 1.0 s), this small systematic study has shown the E336 criterion is not optimal, but is close. The authors wish to thank Don MacMillan and Brian Fitzpatrick for their help in this study.

-1 0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Difference in SPL between Principal and Ancillary Volumes, dB

Diffe re nc e from re fe re nc e ATL, dB

ASTM Approach - Principal Volume Only ASTM Approach - Principal and Ancillary volumes A B D C Source Room Ancillary Volume PrincipalVolume

ASTM E336 Criterion 6dB

ATL Overestimated

Figure 4: ATL errors when an ancillary volume is coupled to receiving room. Open symbols are estimates obtained from measurements in both the ancillary and receive volumes. Closed symbols are estimates obtained from measurements in the principal receive volume. There is a data point for each one-third octave band in the range 125 – 4kHz. (updated on Nov. 1, 2006)

-1 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Difference in SPL between Principal and Ancillary Volumes, dB

Difference from reference ATL (with absorption), dB

ASTM Approach - Principal Volume Only ASTM Approach - Principal and Ancillary Volumes ASTM E336 Criterion 6dB ATL Overestimated A B D C Source Room Ancillary Volume Principal Volume

Figure 5: ATL errors when an ancillary volume is coupled to a heavily furnished receiving room. Open symbols are estimates obtained from measurements in both the ancillary and receive volumes. Closed symbols are estimates obtained from

measurements in the principal receive volume. There is a data point for each one third octave band in the range 125 – 4k Hz.(updated on Nov. 1, 2006)

Figure

Figure 1: Effect of an ancillary volume and percent  opening when coupled to a heavily furnished source room

Références

Documents relatifs

Measures of inequality of opportuity can be classified on the basis of three criteria: whether they take an ex-ante or ex-post perspective, whether they are direct or indirect

To  strictly  comply  with  the  test  administration  instructions,  a  teacher  faced with the  dilemma in  vignette  one must do nothing.  As expected, 

Subject to the conditions of any agreement between the United Nations and the Organization, approved pursuant to Chapter XVI, States which do not become Members in

A diagram of analytic spaces is an object of Dia(AnSpc) where AnSpc is the category of analytic spaces.. Cohomological motives and Artin motives. all finite X-schemes U ). an

Any 1-connected projective plane like manifold of dimension 4 is homeomor- phic to the complex projective plane by Freedman’s homeomorphism classification of simply connected

A second scheme is associated with a decentered shock-capturing–type space discretization: the II scheme for the viscous linearized Euler–Poisson (LVEP) system (see section 3.3)..

Any LDAP operation may be extended by the addition of one or more controls ([RFC2251] Section 4.1.12). A control’s semantics may include the return of zero or

What we want to do in this talk is firstly to explain when (§1) and why (§2) a presupposition trigger becomes obligatory in the very case where it is redundant, and secondly