Furnace tests : the National Research Council of Canada is investigating a way to test the fire resistance of wall and floor assemblies that is more economical than doing full-scale tests

N/A
N/A
Protected

Academic year: 2021

Partager "Furnace tests : the National Research Council of Canada is investigating a way to test the fire resistance of wall and floor assemblies that is more economical than doing full-scale tests"

Copied!
5
0
0

Texte intégral

(1)

Publisher’s version / Version de l'éditeur:

Canadian Consulting Engineer, 44, May 3, p. 28, 32, 2003-05-01

READ THESE TERMS AND CONDITIONS CAREFULLY BEFORE USING THIS WEBSITE.

https://nrc-publications.canada.ca/eng/copyright

Vous avez des questions? Nous pouvons vous aider. Pour communiquer directement avec un auteur, consultez la

première page de la revue dans laquelle son article a été publié afin de trouver ses coordonnées. Si vous n’arrivez pas à les repérer, communiquez avec nous à PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca.

Questions? Contact the NRC Publications Archive team at

PublicationsArchive-ArchivesPublications@nrc-cnrc.gc.ca. If you wish to email the authors directly, please see the first page of the publication for their contact information.

NRC Publications Archive

Archives des publications du CNRC

This publication could be one of several versions: author’s original, accepted manuscript or the publisher’s version. / La version de cette publication peut être l’une des suivantes : la version prépublication de l’auteur, la version acceptée du manuscrit ou la version de l’éditeur.

Access and use of this website and the material on it are subject to the Terms and Conditions set forth at

Furnace tests : the National Research Council of Canada is

investigating a way to test the fire resistance of wall and floor

assemblies that is more economical than doing full-scale tests

Sultan, M. A.

https://publications-cnrc.canada.ca/fra/droits

L’accès à ce site Web et l’utilisation de son contenu sont assujettis aux conditions présentées dans le site LISEZ CES CONDITIONS ATTENTIVEMENT AVANT D’UTILISER CE SITE WEB.

NRC Publications Record / Notice d'Archives des publications de CNRC: https://nrc-publications.canada.ca/eng/view/object/?id=7fcb80a9-451e-4337-895f-c2fb2e3376d3 https://publications-cnrc.canada.ca/fra/voir/objet/?id=7fcb80a9-451e-4337-895f-c2fb2e3376d3

(2)

Furnace tests: the National Research Council of Canada is

investigating a way to test the fire resistance of wall and floor

assemblies that is more economical than doing full-scale tests

Sultan, M.A.

NRCC-46410

A version of this document is published in / Une version de ce document se trouve dans :

Canadian Consulting Engineer, v. 44, no. 3, May 2003, pp. 28, 32

(3)

Furnace tests

By Mohamed A. Sultan

In recent years, fire-rated floor and wall assemblies formed with new materials and construction methods have been used increasingly in residential buildings. To determine the fire resistance performance of these assemblies, full-scale tests are usually required. However, these tests are expensive and time consuming, and there is a need on the part of design engineers and architects, at least in the development of assemblies, to find an alternative solution. To satisfy this need, the National Research Council of Canada (NRC)has been developing a simpler and less expensive test method for these purposes.

As part of these efforts, NRC has just completed the construction of an intermediate-scale furnacethat can be used for testing loaded and unloaded wall and floor assemblies. However, to ensure that this furnace reflects full-scale test results, it must be characterized. Heat exposure in the furnaces is one of the critical parameters in determining the fire resistance performance of specimens. This article presents results of the heat exposure characterization tests carried out by NRC in both its full- and intermediate-scale fire resistance floor test furnaces. Details about the furnaces and specimens are shown in Table 1.

Table 1. Details on furnaces and specimen sizes.

Size Wall construction Specimen size

Full-size furnace, m 4 by 5 by 3 Insulated fire brick 4 by 5 by 0.15

Int.-size furnace, m 1.2 by 1.8 by o.5 Insulated fire brick 0.8 by 1.2 by 0.15

The Furnaces

The full-scale and intermediate-size furnaces areshown in Figures 1 and 2 respectively. . The

tests in each were carried out by exposing the specimens to heat using the propane-fired

horizontal furnace. The average furnace temperature in each case followed as closely as

possible the CAN/ULC-S101-M89 standard time-temperature curve that is similar to the

ASTM E119 curve.

Figure 1 NRC Full-scale Floor Furnace

Figure 2 NRCIntermediate-scale floor furnace

Test Specimens

The full-scale floor test specimen was a castable refractory slab, 4 m wide by 5 m long by

0.15 m thick.

The intermediate-scale specimen was also a castable refractory slab, 0.8 m wide by 1.2

m long by 0.15 m thick.

The total heat exposure (radiative and convective) to the test specimen

was measured by two Gardon Gauge heat flux sensors (see Figure 3), 2.5 cm diameter and 2.5

cm long copper cylinder, with an accuracy of

6

3%. The sensors were installed flush to the

surface of each specimen and are located each at the centre of the half specimen.

(4)

Figure 3 Water Cooled Gardon Gauge Heat Flux Sensor

The Tests

To study the effect of furnace size on the heat exposure in the two test furnaces, six tests were conducted: three repeat tests using the full-scale furnace and three repeat tests using the intermediate-scale furnace. The duration of each test was two hours and measurements were recorded every minute.

Results

A comparison of the average heat exposure of the three repeat tests using the two furnaces is plotted in Figure 4. The results showed that the heat exposure in the intermediate-scale furnace is approximately 15% higher than in the full-scale furnace. These results suggest that the effect of

furnace size on heat

exposure is significant.

Generally, the heat received by a test specimen in fire resistance test furnaces is by radiation

and convection. The radiative part is much greater than the convective part. In full-scale

furnaces, the convective heat occurs by natural convection while, in the smaller size furnaces,

it occurs by forced convection. Heat transfer by forced convection is greater than by natural

convection. As the furnace size increases, the convective heat to the specimen decreases,

which may explain why the heat exposure in an intermediate-scale furnace is higher than in a

full-scale furnace.

Time (min) 0 20 40 60 80 100 120 140 160 180 200 Heat Flux (kW/m 2) 0 50 100 150 200 250 Tempera ture (°C) 0 200 400 600 800 1000 1200

Full-Scale Furnace (average of 3 tests) Intermediate-Scale Furnace (average of 3 tests) Furnace Average Temperature

Average Heat Flux Measurements

Figure 4 Comparison of Heat Exposure in Full-scale vs Intermediate-scale

(5)

The heat exposure to test specimens in an intermediate-scale (1.2 m wide by 1.8 m long by

0.5 m deep) fire resistance furnace is 15% higher than in a full-scale (4m wide by 5 m long by

3 m deep) furnace.

For more information, contact Dr. Mohamed Sultan, who is a senior researcher in the Fire Risk Management Program of the National Research Council’s Institute for Research in Construction. He can be reached at mohamed.sultan@nrc.cnrc.gc.ca

Figure

Table 1. Details on furnaces and specimen sizes.
Figure 3 Water Cooled Gardon Gauge Heat Flux Sensor  The Tests

Références

Documents relatifs

So interpreted, Table III reveals marked differences in the various programs, whatever parallels were suggested above with respect to output... (2) Small enterprises

4 School of Physics State Key Laboratory of Nuclear Physics and Technology, Peking University,

Stepanov Institute of Physics, National Academy of Sciences of Belarus, Minsk, Republic of Belarus 90 National Scientific and Educational Centre for Particle and High Energy

This new combined diet (CD) comprises medium-chain fatty acids, polyunsaturated fatty acid, low glycaemic index carbohydrates, and a high BCAA/AAA ratio.. We first ascertained

L'analyse des données issues de ces expérimentations a permis de montrer (i) que l'eet des stress hydrique et azoté sur la formation des inorescences dans les bourgeons latents à

Our Baseline and Low-oil-price scenarios assume domestic tariffs remaining constant relative to the price of the imported non-energy good (see Annex B for indexation

would play a similar role in the growth cone periphery; tions of actin filaments: long filaments oriented parallel to the membrane and shorter, randomly oriented fila- however, we

A Maxwell’s fisheye lens, 30 on the other hand, is a kind of GRIN lens that can focus the wave from a point source on the edge of the lens to another point on the opposite edge of