METALLURGICAL AND ELECTROCHEMICAL BEHAVIOR OF S295 STEEL TUBES IN STEEL COOLING CIRCUITS

Amel BENDJAMA1, Karima MORAKCHİ2,3, Djamel BERDJANE1, Toufik CHOUCHANE1, Ouahida KHİREDDİNE1, Hiba MAHFOUD3,Samia CHETTOUH1,

1 Research Center in Industrial Technologies CRTI, P.O.BOX 64, Cheraga-16014 Algiers, Algeria 2 Department of Chemistry, Faculty of Science, BadjiMokhtar University ANNABA, ALGERIA

3 University Larbi BenMhidi, Analytical Sciences Materials and Environment Laboratory. Oum Bouaghi,ALGERIA

Abstract

Corrosion damage to industrial cooling systems in steel mills is a serious problem for industry and the environment. In order to reduce this phenomenon by the subsequent development of organic-based corrosion inhibitors, a preliminary identification study of the base material and the surrounding environment of the cooling circuits is essential.

To monitor the electrochemical behavior of unalloyed steel tubes, we studied the influence of the

"industrial cooling water" environment and the most influential physical parameters. This behavior of S295 grade steel will be determined by different stationary and non-stationary electrochemical methods, notably electrochemical impedance spectroscopy.

These investigations enabled us on the one hand the metallurgical knowledge of the base material, the nature of the corrosive medium, and on the other hand the evaluation of the potentials and the corrosion rates and to define the different reactions at the metal interface. middle.

In conclusion, the tubes studied in unalloyed steel have a low resistance to corrosion under the effect of the aggressiveness of the surrounding environment (Figure 1) in this case industrial cooling water hence the need to introduce corrosion inhibitors in cooling circuits. In our case, we will focus on natural organic inhibitors that ensure an economic and environmental balance.

Figure.1: Stationary and frequential electrochemical curves of the material / medium interaction

Keywords: Steel, corrosion, behavior, cooling water, impedance, temperature

Corresponding Author Email : a.bendjama@crti.dz / amel_bendjama@yahoo.fr

(2)

2

1. Introduction:

Corrosion results from a chemical or electrochemical action of an environment on metals and alloys. The consequences are significant in various fields and in particular in industry:

production stoppage, replacement of corroded parts, accidents and risks of pollution are frequent events with sometimes heavy economic impacts [1].

Since the massive use of iron alloys, it has been estimated a loss of 15% of the annual production of steel or 5 tons / second of corrosion [2]. Industrial installations exposed to corrosion damage are generally designed taking into account the composition of existing anti- corrosion products on the market. In fact, in terms of protection, corrosion inhibitors are a special means of protection against metallic corrosion [1].

Today, corrosion inhibitors are an original means of combating corrosion [3]. The originality of these inhibitors is to be the only means of intervention from the corrosive environment [4].

These are substances which, when added at low concentrations in corrosive media, reduce or even prevent the reaction of the metal with its environment [3].

Before beginning the development of corrosion inhibitors, eco-compatible and biodegradable, especially for steel cooling circuits, we have made a preliminary study on the metallurgical and electrochemical behavior of non-alloy grade steel pipes. S295 of these circuits.

2. Material and methods 2.1. Choice of material

Nuance and characterization of the material

The chemical analyzes of the seamless tube samples of the "FRX" X-Ray Fluorescence Oxygen Cooling System gave the results shown in Table 1.

Table 1: Chemical composition of the tube.

Content in chemical element in% by mass

Sample code C Mn Si P S V Cr Ni Cu Mo

TU 0,196 0,562 0,2239 0,014 0,003 0,02 0,041 0,101 0,173 0,01

Micro hardness tests

Micro hardness tests were carried out on samples taken from the tube. The results of Hv microhardness in different parts under a load of 5Kgf are shown in Table 2.

Table 2: micro-hardness filaments on the entire damaged tube Sample

code

HV1 HV2 HV3 HV4 HV5 HV6 HVmoy

Equivalent resistance RM (N/mm²)

TU 139 143 137 151 129 142 143 480-485

(3)

3

Metallographic examinations

Optical microscopic examinations of polished sections taken from tube samples at different magnifications revealed a fine ferrito-pearlitic structure with homogeneity of grain size and shape (fig.2). The phase distribution gave 80% Ferrite and 20% Perlite with an average grain size index of about 8 (according to ASTM E1382-97, ISO643 and ASTM E112).

G = 50X G = 100X Figure 2: Tube micrographs after Nital attack at 4%

Nuance: On the basis of the various investigations carried out and referring to the international standards NF EN 10025 ISO 683, NF A 49-212, NF A49-213, the tube conveying cooling water from the oxygen steelworks is similar to grade S295 (equivalent to TU 48 according to the old nomenclature for seamless tubes). It is an unalloyed low carbon steel with a good compromise between mechanical properties of strength and ductility.

2.2. The environment

The environment in which we tested the corrosion behavior of our S295 steel is an industrial cooling water, characterized by an alkaline pH of about 9.90 and a presence of chlorides. The physico-chemical analysis of this water is presented in Table 3 below:

Table 3: Physicochemical Parameters of Industrial Cooling Wate*

2.3- Electrochemical study and electrochemical study and testc conditions

Electrochemical methods used: The evolution of the electrochemical behavior of S295 steel and the study of the material / medium interface are realized by stationary and non-stationary methods and the test conditions are as follows:

Parameter TA TAC TH Cu Mg Cl- pH TDS MES COND T Unity °F °F °F °F °F Mg/l / Mg/l Mg/l µS °C concentration 1.8 4.4 8.4 5.8 2.6 42.6 9.90 231 30 322 22

(4)

4

The working equipment: The electrochemical parameters were calculated using the Autolab 302N controlled by a microcomputer at the corrosion laboratory of the applied research unit in the iron and steel industry URASM / CRTI / ANNABA. Polarization resistance measurements (Rp) were performed at a scanning rate of 1 mVs-1.

The measuring cell: the measuring cell used for the electrochemical tests is made of cylindrical pyrex glass with a volume of 250ml with double thermostatic walls.

Electrode References: During our experiment, three electrodes were used, a reference electrode Ag / AgCl, a platinum counter electrode and a steel grade S295 working electrode.

Working electrode: for reliable results, the working electrode must undergo a pretreatment before each test, which consists of polishing the surface of the working electrode with abrasive papers under water jet followed by drying under a flow of air. [5]

Experimental conditions According to the literature, because the behavior of materials including the tubes of industrial instatllations is influenced by the temperature change we play on this parameter after each change of temperature we observe our steel under optical microscope to see the degree of corrosion damage.

4. Results and Discussion 4.1. identification of nuance:

Différentes enquêtes sont effectuées et référencées aux normes internationales NF EN 10025, ISO 683, NF A 49-212, NF A49-213, le tube conducteur de l'eau de refroidissement à oxygène s'apparente à la nuance de grade S295 (équivalent à TU 48 selon l'ancienne nomenclature des tubes sans soudure). C’est un acier à base de carbone non allié avec un bon compromis entre les propriétés de résistance et de ductilité.

4.2. Comportement to the corrosion of theier S295 in the water of circuit:

the parameters deduced from these polarization curves are summarized in Table 4. The behavior of S295 steel has a low resistance to corrosion in interaction with the surrounding medium, despite the fact that the chloride content is not high enough, therefore, with a fairly high corrosion rate, at least the electrochemical properties are not present (Table 4). In this case, the speed, the resistance to polarization are higher at 50 ° C compared to the ambient temperature. It appears that temperature fluctuations disturb the environment environment, which is the industrial cooling water.

Table 4: Parmeters of polarization curves of S295 steel in cooling water

Paramètre Ecorr Icorr A/cm2 Corr rate mm/year Polar Rate Ω

Steel at 25°C -0.51115V 1.1656E-06 0.013544 50609

Steel at à 50°C -0.54139V 2.3583E-06 0.027403 24129

(5)

5

Figure 3: Polarization curves of S295 steel in cooling water at 25 ° C and 50 ° C

4.3. Electrochemical impedance spectroscopy SIE:

0 10000 20000 30000 40000 50000

0 2000 4000 6000 8000 10000 12000 14000 16000 18000

-Z (ohm)

Z (ohm)

temperature ambiante temperature 250

C

Figure 4: Impedance diagram of S295 steel in cooling water

To study the mechanisms of corrosion and protection of metals [6]; the impedance spectroscopy method proved to be the most efficient tool. Figure 4 shows the Nyquist diagram Z of S295 steel at room temperature and at 50 ° C. We note from this diagram that the size of the half circle increases with the increase in temperature which reflects the increase in resistance, this phenomenon results from the protective layer.

4.4. Image of steel under optical microscope after electrochemical test at different temperatures:

We tested our S295 steel in an alkaline cooling water with chlorides of different degrees of temperature. At an ambient temperature of 25 ° C, we noticed a piquartion on a part of the surface of the sample, from which we observe the structure under optical microscope "see Figure 2". Microphagy at 50 ° C: At this temperature the pitting surface is larger than 25 ° C.

The surface condition of steel under optical microscope is shown in Figure 4.

(6)

6

G = 50X G = 100X

Figure 3: Pitting of surface steel S295 at room temperature 25 ° C.

G = 50X G = 100X

Figure 4: Pitting of surface steel S295 at room temperature 50 ° C.

5- Conclusion :

The various investigations carried out and referring to the international standards NF EN 10025 ISO 683, NF A 49-212, NF A49-213, the tube conveying the cooling water of the oxygen steel plant is similar to the grade S295 (equivalent to TU 48 according to the old nomenclature of seamless tubes). It is an unalloyed low carbon steel with a good compromise between mechanical properties of strength and ductility.

The results of the polarization curves of steel S295 in cooling water circuit show that the electrochemical properties in this case potential, speed, polarization resistance are higher at 50

° C compared to ambient temperature which shows that temperature fluctuations can disturb the behavior of the surrounding environment, which is industrial cooling water.

This deduction is supported by electrochemical impedance spectroscopy, which reveals that the size of the semicircle increases with increasing temperature, which reflects the increase in resistance.

Soon we will proceed to the protection of our cooling system of the corrosion phenomenon by the development and introduction of our inhibitor-based extraction of natural products which meets the economic, societal and environmental needs.

(7)

7

References

[1]. Milcard Faustin, Study of the effect of alkaloids on the corrosion of C38 steel in 1M hydrochloric acid medium: Application to Aspidosperma album and Geissospermum laeve (Apocynaceae). University of the Antilles and Guyana Institute of Higher Education of Guyana Multidisciplinary doctoral school: Health, Environment and Societies in the Americas 200 pages. Doctoral thesis , 2013.

[2]. Boughaba Walid, Comparative study of the corrosion behavior of the temperature in H2SO4. Master's thesis in metallurgy. Badji Mokhtar University, Algeria 68 pages, Annaba, 2018.

[3] Imane Bouali, Study of metal corrosion inhibitors based on functionalized lamellar zirconium ortho-phosphates: synthesis, characterizations and applications. Materials.

University of Lorraine, Caddi Ayyad University, Marrakech (Morocco), 2018.

[4]. FHWA REPORT. FHWA, Office of Infrastructure Research and Development Report FHWA-RD-01-156, Corrosion costs and prevention strategies in the United States, report by CC Technologies.Laboratory, Inc, 2001

[5]. Abdelghani, Hemmal , Mechanical and electrochemical characterization of a welded steel joint API 5L X70Memory of graduation ENSMM-Annab (National School of Mining and Metallurgy) 84 pages, 2016.

[6] Dieter Landolt, Corrosion and surface chemistry of polytechnic presses, 552 pages, 1997.

Références

Documents relatifs

Quelle que soit la démarche choisie pour réaliser la construction de la base de règles (synthèse directe du système flou ou modification à partir d’une configuration

In conclusion, the tubes studied in unalloyed steel have a low resistance to corrosion under the effect of the aggressiveness of the surrounding environment (Figure 1) in this

This shift anodic and cathodic curves is a consequence of both cathodic and anodic reactions of API 5L X60 In the presence of GA, the slight change of both and in acid

Electrochemical polarization and electrochemical impedance spectroscopy measurements were performed in order to obtain information on the corrosion behaviour of steel N 80 in

Polarization curves obtained for the N80 steel immersed in albian water at different temperatures in the presence of inhibitor.. According polarization curves (Figure 3) it can be

This last assumption could explain the low value of the dielectric constant and the behavior observed in thick ceramics layers based on TiCl 3 , where the grain size ranges between

Its dependency on temperature is weak relative to mass flow rate, and consequently, the Peclet number is only a weak function of equivalence ratio in the liquid-fueled

Similarly, the presence of stereoisomers within a sample of molecules can lead to confu- sion in studies of molecular dynamics, because any measurements taken are generally averages